[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964925":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},964925,701,1,"单选题","消防对讲电话单路通话断开的排查方法是（ ）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","脱开外部线路，故障仍然存在，需更换电话总机",false,{"key":16,"text":17,"correct":14},"B","脱开外部线路故障恢复，需分段检查外接总线找出故障点",{"key":19,"text":20,"correct":14},"C","测试消防电话分机与主机间相互呼叫与通话，呼叫铃声和通话语音应清晰",{"key":22,"text":23,"correct":24},"D","用一个51K电阻接在输出端子T+T-上，如果故障消除，说明外部线路出现问题，需分段检查外接线路找出故障点",true,"消防对讲电话单路通话断开的排查方法是用一个51K电阻接在输出端子T+T-上，如果故障消除，说明外部线路出现问题，需分段检查外接线路找出故障点。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]