[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964846":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},964846,701,1,"单选题","消防设备电源状态监控器有自检、消音、复位功能，关于这些功能说法错误的是（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","监控器应具有手动检查其音响器件、面板所有指示灯和显示器的功能",false,{"key":16,"text":17,"correct":18},"B","监控器的自检时间超过3min或不能自动停止自检时，不应影响非自检部位的正常工作",true,{"key":20,"text":21,"correct":14},"C","监控器在故障排除后，故障信号可自动或手动复位",{"key":23,"text":24,"correct":14},"D","监控器的故障声信号应能手动消除，再有故障信号输入时，应能再启动","消防设备电源状态监控器的基本功能： （1）消音功能监控器的故障声信号应能手动消除，再有故障信号输入时，应能再启动。 （2）自检功能监控器应具有手动检查其音响器件、面板所有指示灯和显示器的功能。监控器的自检时间超过lmin或不能自动停止自检时，不应影响非自检部位的正常工作。 （3）复位功能监控器在故障排除后，故障信号可自动或手动复位。复位后，监控器应在100s内重新显示尚存在的故障。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]