[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964798":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},964798,701,1,"单选题","柴油机消防水泵的供油箱应根据火灾延续时间确定，且油箱最小有效容积应按1.5L\u002FkW配置，油箱内储存的燃料不应小于（ ）%的储量。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","90",false,{"key":16,"text":17,"correct":14},"B","80",{"key":19,"text":20,"correct":14},"C","70",{"key":22,"text":23,"correct":24},"D","50",true,"当釆用柴油机消防水泵时应符合下列规定： （1）柴油机消防水泵应釆用压缩式点火型柴油机； （2）柴油机的额定功率应校核海拔高度和环境温度对柴油机功率的影响； （3）柴油机消防水泵应具备连续工作的性能，试验运行时间不应小于24h； （4）柴油机消防水泵的蓄电池应保证消防水泵随时自动启泵的要求； （5）柴油机消防水泵的供油箱应根据火灾延续时间确定，且油箱最小有效容积应按1.5L\u002FkW配置，柴油机消防水泵油箱内储存的燃料不应小于50%的储量。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]