[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964795":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},964795,701,1,"单选题","消防用电设备的配电线路暗敷时，应穿管并应敷设在不燃烧体结构内且保护层厚度不应小于（ ）mm。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","10",false,{"key":16,"text":17,"correct":14},"B","20",{"key":19,"text":20,"correct":21},"C","30",true,{"key":23,"text":24,"correct":14},"D","40","消防配电线路应满足火灾时连续供电的需要，其敷设应符合下列规定： （1）明敷时（包括敷设在吊项内），应穿金属导管或釆用封闭式金属槽盒保护，金属导管或封闭式金属槽盒应釆取防火保护措施；当釆用阻燃或耐火电缆并敷设在电缆井、沟内时，可不穿金属导管或釆用封闭式金属槽盒保护；当釆用矿物绝缘类不燃性电缆时，可直接明敷。 （2）暗敷时，应穿管并应敷设在不燃性结构内且保护层厚度不应小于30mm。 （3）消防配电线路宜与其他配电线路分开敷设在不同的电缆井、沟内；确有困难需敷设在同一电缆井、沟内时，应分别布置。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]