[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964767":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},964767,701,1,"单选题","消防设备末端配电装置自投不自复的工作方式说法错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","正常时主电源断路器供电",false,{"key":16,"text":17,"correct":18},"B","当主电源失电时，控制装置使主电源断路器闭合，备用电源断路器断开，备用电源供电",true,{"key":20,"text":21,"correct":14},"C","当主电源恢复供电时，控制装置维持备用电源断路器供电",{"key":23,"text":24,"correct":14},"D","转换时间可调整（0-120s）","销防设备末端配电装置自投不自复的工作方式：正常时主电源断路器供电。当主电源失电时，控制装置使主电源断路器断开，备用电源断路器闭合，备用电源供电。当主电源恢复供电时，控制装置维持备用电源断路器供电。转换时间可调整（0~120s）。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]