[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964746":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},964746,701,1,"单选题","关于水（气）传动管启动水喷雾灭火系统工作原理说法不正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","传动管内充满压缩空气或压力水",false,{"key":16,"text":17,"correct":14},"B","当传动管上的闭式洒水喷头受火灾高温影响动作后，传动管内的压力迅速下降，打开封闭的雨淋报警阀",{"key":19,"text":20,"correct":21},"C","传动管的火灾报警信号通过报警阀传到火灾报警控制器和水泵控制柜，直接启动水泵或同时由报警控制器启动水泵",true,{"key":23,"text":24,"correct":14},"D","通过雨淋报警阀、管网将水送到水雾喷头，水雾喷头开始喷水灭火","水（气）传动管启动水喷雾灭火系统是以传动管作为火灾探测系统，传动管内充满压缩空气或压力水，当传动管上的闭式洒水喷头受火灾高温影响动作后，传动管内的压力迅速下降，打开封闭的雨淋报警阀。为了尽量缩短管网充水的时间，雨淋报警阀前的管道内应为充满水的状态。传动管的火灾报警信号通过压力开关传到火灾报警控制器和水泵控制柜，直接启动水泵或同时由报警控制器启动水泵，通过雨淋报警阀、管网将水送到水雾喷头，水雾喷头开始喷水灭火。传动管启动水喷雾灭火系统一般适用于防爆场所，或者不适合安装普通火灾探测系统的场所。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]