[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964674":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},964674,701,1,"单选题","建筑高度低于100m的一类高层民用公共建筑，其高位消防水箱最低有效水位应满足最不利点处的静水压力不应低于（ ）MPa。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","0.05",false,{"key":16,"text":17,"correct":14},"B","0.08",{"key":19,"text":20,"correct":21},"C","0.1",true,{"key":23,"text":24,"correct":14},"D","0.15","依据《消防给水及消火栓系统技术规范》GB50974-2014，高位消防水箱的设置位置应高于其所服务的水灭火设施，且最低有效水位应满足水灭火设施最不利点处的静水压力，一类高层公共建筑，不应低于0.l0MPa，但当建筑高度超过100m时，不应低于0.15MPa。本题答案为C。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]