[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964539":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},964539,701,1,"单选题","下列哪项不是预作用报警阀组压力表读数不在正常范围故障原因（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","预作用装置前的供水控制阀未打开。",false,{"key":16,"text":17,"correct":14},"B","压力表管路堵塞。",{"key":19,"text":20,"correct":14},"C","预作用装置的报警阀体漏水。",{"key":22,"text":23,"correct":24},"D","消防用水水质存在问题。",true,"预作用报警阀组压力表读数不在正常范围故障原因有预作用装置前的供水控制阀未打开；压力表管路堵塞；预作用装置的报警阀体漏水。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]