[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964537":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},964537,701,1,"单选题","预作用装置的功能性检测下列描述错误的是：（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","模拟火灾探测报警，火灾报警控制器确认火灾后，自动启动预作用装置（雨淋报警阀）、排气阀入口电动阀以及消防水泵；水流指示器、压力开关动作。",false,{"key":16,"text":17,"correct":18},"B","报警阀组动作后，测试水水力警铃声强，不得低于80dB。",true,{"key":20,"text":21,"correct":14},"C","开启末端试水装置，火灾报警控制器确认火灾2min后，其出水压力不低于0.05MPA。",{"key":23,"text":24,"correct":14},"D","消防控制设备准确显示电磁阀、电动阀、水流指示器以及消防水泵动作信号，反馈信号准确。","报警阀组动作后，测试水水力警铃声强，不得低于70dB：",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]