[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964493":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},964493,701,1,"单选题","任意一台火灾报警控制器所连接的火灾探测器、手动火灾报警按钮和模块等设备总数和地址总数，均不应超过（ ）点，其中每一总线回路连接设备的总数不宜超过（ ）点，且应留有不少于容量（ ）的余量。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","1600，100，5%",false,{"key":16,"text":17,"correct":14},"B","1600，100，10%",{"key":19,"text":20,"correct":14},"C","3200，200，5%",{"key":22,"text":23,"correct":24},"D","3200，200，10%",true,"任意一台火灾报警控制器所连接的火灾探测器、手动火灾报警按钮和模块等设备总数和地址总数，均不应超过3200点，其中每一总线回路连接设备的总数不宜超过200点，且应留有不少于容量10%的余量。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]