[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964353":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},964353,701,1,"单选题","建筑高度大于27米且小于54米的高层住宅建筑的室内消火栓的栓口动压不应小于（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","0.15",false,{"key":16,"text":17,"correct":14},"B","0.25",{"key":19,"text":20,"correct":21},"C","0.35",true,{"key":23,"text":24,"correct":14},"D","0.45","高层建筑、厂房、库房和室内净空高度超过8m的民用建筑等场所，消火栓栓口动压不应小于0.35MPa，且消防水枪充实水柱应按13m计算；其他场所，消火栓栓口动压不应小于0.25MPa，且消防水枪充实水柱应按10m计算。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]