[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964232":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},964232,701,1,"单选题","关于火灾报警传输设备的手动报警功能说法不正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","传输设备在传输火灾报警、监管、故障、屏蔽或自检信息期间，应能优先进行手动报警操作和手动报警信息传输。",false,{"key":16,"text":17,"correct":14},"B","传输设备在手动报警操作并传输信息时，手动报警指示灯应闪亮",{"key":19,"text":20,"correct":14},"C","在得到监控中心的正确接收确认后，手动报警指示灯应常亮并保持60s。当信息传送失败时应发出声、光信号。",{"key":22,"text":23,"correct":24},"D","传输设备应设手动报警按键（钮），当手动报警按键（钮）动作时，应发出指示手动报警状态的光信号，并在305内将手动报警信息传送给监控中心。",true,"传输设备应设手动报警按键（钮），当手动报警按键（钮）动作时，应发出指示手动报警状态的光信号，并在10s内将手动报警信息传送给监控中心。传输设备在手动报警操作并传输信息时，手动报警指示灯应闪亮，在得到监控中心的正确接收确认后，该指示灯应常亮并保持60s。当信息传送失败时应发出声、光信号。传输设备在传输火灾报警、监管、故障、屏蔽或自检信息期间，应能优先进行手动报警操作和手动报警信息传输。",{"id":6,"name":27,"category":28,"favorite":29},"高级技能","建筑工程",0]