[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-964031":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},964031,700,1,"单选题","防火卷帘自动控制功能调试，下列说法不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","控制分隔防火分区的防火卷帘由上限位自动关闭到中位（1.8m）处停止",true,{"key":16,"text":17,"correct":18},"B","防火卷帘控制器接到感烟火灾探测器的报警信号后控制防火卷帘自动关闭到中位（1.8m）处停止",false,{"key":20,"text":21,"correct":18},"C","防火卷帘控制器接到感温火灾探测器的报警信号时，继续关闭到全闭",{"key":23,"text":24,"correct":18},"D","防火卷帘半降、全降的动作信号应反馈到消防控制室。","自动控制功能调试时，当防火卷帘控制器接收到火灾报警信号后，应输出控制防火卷帘完成相当动作的信号，并应符合下列要求： （1）控制分隔防火分区的防火卷帘由上限位自动关闭至全闭。 （2）防火卷帘控制器接到感烟火灾探测器的报警信号后控制防火卷帘自动关闭到中位（1.8m）处停止，接收到感温火灾探测器的报警信号时，继续关闭到全闭， （3）防火卷帘半降、全降的动作信号应反馈到消防控制室。",{"id":6,"name":27,"category":28,"favorite":29},"基础知识（通用）","建筑工程",0]