[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-963802":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},963802,700,1,"单选题","消防水泵房设置不符合要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","独立建造的消防水泵房耐火等级不应低于二级",false,{"key":16,"text":17,"correct":14},"B","附设在建筑物内的消防水泵房，不应设置在地下三层以下，或室内地面与室外出入口地平高差大于10m的地下楼层",{"key":19,"text":20,"correct":21},"C","附设在建筑物内的消防水泵房，应采用耐火极限不低于1.50h的隔墙和楼板与其它部位隔开",true,{"key":23,"text":24,"correct":14},"D","水泵房疏散门应直通安全出口，且开向疏散走道的门应采用甲级防火门","附设在舰建筑物内的消防水泵房，应采用耐火极限不低于2.0h的隔墙和1.50h的楼板与其它部位隔开，其疏散门应直通安全出口，且开向疏散走道的门应采用甲级防火门。",{"id":6,"name":27,"category":28,"favorite":29},"基础知识（通用）","建筑工程",0]