[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-963320":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},963320,700,1,"单选题","防护区围护结构承受内压的允许压强不宜低于（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1．2kpa",true,{"key":16,"text":17,"correct":18},"B","1．5kpa",false,{"key":20,"text":21,"correct":18},"C","1．0h",{"key":23,"text":24,"correct":18},"D","1．01kpa","为防止防护区结构因火灾或内部压力增加而损坏，要求防护区围护结构及门窗的耐火极限不宜低于0.5h，吊顶的耐火极限不宜低于0.25h，防护区围护结构承受内压的允许压强不宜低于1200Pa。",{"id":6,"name":27,"category":28,"favorite":29},"基础知识（通用）","建筑工程",0]