[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-963210":3},{"question":4,"library":20},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":13,"analysis":19},963210,700,3,"判断题","当建筑内每个防火分区的通风、空气调节系统均独立设置时，水平风管与竖向总管的交接处可不设置防火阀。",[11,15],{"key":12,"text":13,"correct":14},"A","正确",true,{"key":16,"text":17,"correct":18},"B","错误",false,"防火阀的设置部位。下列部位应设置防火阀。通风、空气调节系统的风管在下列部位应设置公称动作温度为70℃的防火阀：穿越防火分区处；穿越通风、空气调节机房的房间隔墙和楼板处；穿越重要或火灾危险性大的场所的房间隔墙和楼板处；穿越防火分隔处的变形缝两侧；竖向风管与每层水平风管交接处的水平管段上。当建筑内每个防火分区的通风、空气调节系统均独立设置时，水平风管与竖向总管的交接处可不设置防火阀。",{"id":6,"name":21,"category":22,"favorite":23},"基础知识（通用）","建筑工程",0]