[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-963093":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},963093,700,1,"单选题","高层建筑内充可燃油的高压电容器和多油开关室宜采用（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","预作用系统",false,{"key":16,"text":17,"correct":14},"B","雨淋系统",{"key":19,"text":20,"correct":21},"C","水喷雾灭火系统",true,{"key":23,"text":24,"correct":14},"D","水幕系统","《建筑设计防火规范》（GB50016）规定以下场所应设置自动灭火系统，并宜采用水喷雾灭火系统。 （1）单台容量在40MV·A及以上的厂矿企业油浸变压器，单台容量在90MV·A及以上的电厂油浸变压器，单台容量在125MV·A及以上的独立变电站油浸变压器。 （2）飞机发动机试验台的试车部位。 （3）设置在高层建筑内充可燃油的高压电容器和多油开关室。",{"id":6,"name":27,"category":28,"favorite":29},"基础知识（通用）","建筑工程",0]