[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-963061":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},963061,700,2,"多选题","下列关于气体灭火防护区的安全设置符合要求的有（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","防护区应有保证人员在30s内疏散完毕的通道和出口；",true,{"key":16,"text":17,"correct":14},"B","防护区内的疏散通道及出口，应设应急照明与疏散指示标志；",{"key":19,"text":20,"correct":14},"C","防护区内应设火灾声报警器；防护区入口处应设火灾声、光报警器和灭火剂喷放指示灯，以及防护区采用的相应气体灭火系统的永久性标志牌；",{"key":22,"text":23,"correct":14},"D","防护区的门应向疏散方向开启，并能自行关闭；地下防护区和无窗或设固定窗扇的地上防护区，应设置机械排风装置。",{"key":25,"text":26,"correct":27},"E","气体灭火防护区内的应具最低的防护抗压等级，围护结构抗压等级不能低于1500Pa",false,"ABCD","防护区的安全设置防护区应有保证人员在30s内疏散完毕的通道和出口；防护区内的疏散通道及出口，应设应急照明与疏散指示标志；防护区内应设火灾声报警器；防护区入口处应设火灾声、光报警器和灭火剂喷放指示灯，以及防护区采用的相应气体灭火系统的永久性标志牌；防护区的门应向疏散方向开启，并能自行关闭；地下防护区和无窗或设固定窗扇的地上防护区，应设置机械排风装置。E项防护区围护结构承受内压的允许压强，不宜低于1200Pa。北京中教安达题库提示气体防护区内要预出30s如果防护区内有人要让他们逃生撤出人员，然后要有提示，然后要方便人逃生则需要门朝外开启（所有消防疏散通道上的门都有这要求）因为气体灭火剂有毒，所有要装排风机，灭完火后排完后进去检查，或戴空气呼吸器进去检查。",{"id":6,"name":31,"category":32,"favorite":33},"基础知识（通用）","建筑工程",0]