[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-962831":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},962831,700,1,"单选题","保证短路电流在导体和连接件产生的热效应和机械力造成危害之前分断该短路电流，分断能力不应小于保护电器安装的预期短路电流。但在上级已装有所需分断能力的保护电器时，下级保护电路的分断能力允许小于预期短路电流属于（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","短路保护",true,{"key":16,"text":17,"correct":18},"B","过负载保护",false,{"key":20,"text":21,"correct":18},"C","防雷保护",{"key":23,"text":24,"correct":18},"D","接地故障保护","短路保护短路保护装置应保证短路电流在导体和连接件产生的热效应和机械力造成危害之前分断该短路电流，分断能力不应小于保护电器安装的预期短路电流。但在上级已装有所需分断能力的保护电器时，下级保护电路的分断能力允许小于预期短路电流。此时该上下级保护电器的动作特性必须配合，使得通过下级保护电器的能量不超过其能够承受的能量，应在短路电流使导体达到允许的极限温度之前分断该短路电流。",{"id":6,"name":27,"category":28,"favorite":29},"基础知识（通用）","建筑工程",0]