[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-962820":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},962820,700,2,"多选题","下列关于电力负荷等级，可不采用一级负荷等级的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","座位数超过1500个的电影院",true,{"key":16,"text":17,"correct":18},"B","建筑高度为55m的丙类生产厂房",false,{"key":20,"text":21,"correct":18},"C","建筑高度为30m的医院住院楼",{"key":23,"text":24,"correct":14},"D","任一楼层建筑面积大于3000m2的商店",{"key":26,"text":27,"correct":14},"E","省（市）级以上的广播电视建筑","ADE","一级负荷适用场所：建筑高度大于50m的乙、丙类生产厂房和丙类物品库房，一类高层民用建筑，一级大型石油化工厂，大型钢铁联合企业，大型物资仓库等。二级负荷适用场所：室外消防用水量大于35L\u002Fs的可燃材料堆场，可燃气体储罐（区）和甲、乙类液体储罐（区），粮食仓库及粮食筒仓，二类高层民用建筑，座位数超过1500个的电影院、剧场，座位数超过3000个的体育馆，任一楼层建筑面积大于3000m2的商店和展览建筑，省（市）级以上的广播电视、电信和财贸金融建筑，室外消防用水量大于25L\u002Fs的其他公共建筑。",{"id":6,"name":31,"category":32,"favorite":33},"基础知识（通用）","建筑工程",0]