[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-962539":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},962539,700,2,"多选题","下列关于消防水泵房的平面布置说法符合规范规定的是（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","独立建造的消防水泵房耐火等级不应低于二级",true,{"key":16,"text":17,"correct":18},"B","不应布置在人员密集场所的上一层、下一层或贴邻",false,{"key":20,"text":21,"correct":14},"C","附设在建筑内的消防水泵房，不应设置在地下三层及以下，或室内地面与室外出入口地坪高差大于10m的地下楼层",{"key":23,"text":24,"correct":14},"D","附设在建筑内的消防水泵房，应采用耐火极限不低于2.00h的隔墙和1.50h的不燃性楼板与其他部位隔开，其疏散门应直通室外或安全出口，且开向疏散走道的门应采用甲级防火门",{"key":26,"text":27,"correct":18},"E","应采用耐火极限不低于2.00h的防火隔墙和1.50h的不燃性楼板与其他部位隔开","ACD","消防水泵房的设置： （1）独立建造的消防水泵房耐火等级不应低于二级； （2）附设在建筑内的消防水泵房，不应设置在地下三层及以下，或室内地面与室外出入口地坪高差大于10m的地下楼层； （3）附设在建筑内的消防水泵房，应采用耐火极限不低于2.00h的隔墙和1.50h的不燃性楼板与其他部位隔开，其疏散门应直通室外或安全岀口，且开向疏散走道的门应釆用甲级防火门。",{"id":6,"name":31,"category":32,"favorite":33},"基础知识（通用）","建筑工程",0]