[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-962529":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},962529,700,1,"单选题","两座一级耐火等级的厂房，当相邻较低一面外墙为防火墙且较低一座厂房的屋顶耐火极限不低于1.00h，甲、乙类厂房之间的防火间距不应小于（ ）m；丙、丁、戊类厂房之间的防火间距不应小于（ ）m。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","4；6",false,{"key":16,"text":17,"correct":18},"B","6；4",true,{"key":20,"text":21,"correct":14},"C","3；2",{"key":23,"text":24,"correct":14},"D","4；3","厂房之间及与乙、丙、丁、戊类仓库、民用建筑的防火间距不应小于相应规范的规定，注：两座一、二级耐火等级的厂房，当相邻较低一面外墙为防火墙且较低一座厂房的屋顶耐火极限不低于1.00h，或相邻较高一面外墙的门、窗等开口部位设置甲级防火门、窗或防火分隔水幕或按《建筑设计防火规范》（GB50016）的规定设置防火卷帘时，甲、乙类厂房之间的防火间距不应小于6m；丙、丁、戊类厂房之间的防火间距不应小于4m。",{"id":6,"name":27,"category":28,"favorite":29},"基础知识（通用）","建筑工程",0]