[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-960057":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},960057,699,1,"单选题","当采用包括背火面温升作耐火极限判定条件的防火卷帘时，其耐火极限不低于（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","1.5h",false,{"key":16,"text":17,"correct":14},"B","2h",{"key":19,"text":20,"correct":14},"C","2.5h",{"key":22,"text":23,"correct":24},"D","3h",true,"本题考查的是防火卷帘的设置要求（1）在设置防火墙确有困难的场所，可采用防火卷帘作防火分区分隔。当采用包括背火面温升作耐极限判定条件的防火卷帘时，其耐火极限不低于3h；当采用不包括背火面温升作耐火极限判定条件的防火卷帘时，其卷帘两侧应设独立的闭式自动喷水系统保护，系统喷水延续时间不应小于3h。（2）设在疏散走道上的防火卷帘，应在卷帘的两侧设置启闭装置，并应具有自动手动和机械控制的功能。（3）防火卷帘应具有防烟性能，与楼板、梁和墙、柱之间的空隙应采用防火封堵材料封堵",{"id":6,"name":27,"category":28,"favorite":29},"初级技能","建筑工程",0]