[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-959829":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},959829,699,1,"单选题","火灾报警控制器的备用电源在放电至终止电压条件下充电24h，其容量应可提供火灾报警控制器在监视状态下工作8h后，在火灾报警控制器容量不超过10个报警部位时，所有报警部位均处于报警状态条件下工作（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","30min",true,{"key":16,"text":17,"correct":18},"B","60min",false,{"key":20,"text":21,"correct":18},"C","90min",{"key":23,"text":24,"correct":18},"D","120min","火灾报警控制器的备用电源在放电至终止电压条件下充电24h，其容量应可提供火灾报警控制器在监视状态下工作8h后，在下述条件下工作30min：当火灾报警控制器容量不超过10个报警部位时，所有报警部位均处于报警状态；当火灾报警控制器容量超过10个报警部位时，1\u002F15的报警部位（不少于10个报警部位，但不超过32个报警部位）处于报警状态。",{"id":6,"name":27,"category":28,"favorite":29},"初级技能","建筑工程",0]