[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-959822":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},959822,699,1,"单选题","某建筑高度为100m的住宅建筑，高位消防水箱的设置高于其所服务的水灭火设施，且最低有效水位应满足水灭火设施最不利点处的静水压力不应低于（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.05MPa",false,{"key":16,"text":17,"correct":18},"B","0.07MPa",true,{"key":20,"text":21,"correct":14},"C","0.10MPa",{"key":23,"text":24,"correct":14},"D","0.15MPa","5.2.2高位消防水箱的设置位置应高于其所服务的水灭火设施，且最低有效水位应满足水灭火设施最不利点处的静水压力，并应按下列规定确定： （1）一类高层公共建筑，不应低于0.10MPa，但当建筑高度超过100m时，不应低于0.15MPa； （2）高层住宅、二类高层公共建筑、多层公共建筑，不应低于0.07MPa，多层住宅不宜低于0.07MPa； （3）工业建筑不应低于0.10MPa，当建筑体积小于20000m3时，不宜低于0.07MPa； （4）自动喷水灭火系统等自动水灭火系统应根据喷头灭火需求压力确定，但最小不应小于0.10MPa； （5）当高位消防水箱不能满足本条第1款～第4款的静压要求时，应设稳压泵。",{"id":6,"name":27,"category":28,"favorite":29},"初级技能","建筑工程",0]