[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-959820":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},959820,699,1,"单选题","建筑高度为32m的医疗建筑，设置的高位消防水箱的有效容积和最低有效水位应满足水灭火设施最不利点处的静水压力分别不应小于（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","36m3；0.1MPa",true,{"key":16,"text":17,"correct":18},"B","18m3；0.1MPa",false,{"key":20,"text":21,"correct":18},"C","36m3；0.15MPa",{"key":23,"text":24,"correct":18},"D","18m3；0.07MPa","5.2.1临时高压消防给水系统的高位消防水箱的有效容积应满足初期火灾消防用水量的要求，并应符合下列规定：一类高层公共建筑，不应小于36m3，但当建筑高度大于100m时，不应小于50m3，当建筑高度大于150m时，不应小于100m3；5.2.2高位消防水箱的设置位置应高于其所服务的水灭火设施，且最低有效水位应满足水灭火设施最不利点处的静水压力，并应按下列规定确定：一类高层公共建筑，不应低于0.10MPa，但当建筑高度超过100m时，不应低于0.15MPa；",{"id":6,"name":27,"category":28,"favorite":29},"初级技能","建筑工程",0]