[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-959795":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},959795,699,1,"单选题","消防闸阀阀体强度试验说法正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","闸阀应能承受4倍于额定工作压力的静水压，保持5min，试验时闸板应全开，试验后阀体应无渗漏、变形和损坏",true,{"key":16,"text":17,"correct":18},"B","闸阀应能承受4倍于额定工作压力的静水压，保持3min，试验时闸板应全开，试验后阀体应无渗漏、变形和损坏",false,{"key":20,"text":21,"correct":18},"C","闸阀阀板处于关闭状态位置时，进水口应能承受2倍于额定工作压力的静水压，保持5min，阀门各密封处应无渗漏",{"key":23,"text":24,"correct":18},"D","闸阀阀板处于关闭状态位置时，进水口应能承受2倍于额定工作压力的静水压，保持3min，阀门各密封处应无渗漏","阀体强度闸阀应能承受4倍于额定工作压力的静水压，保持5min，试验时闸板应全开，试验后阀体应无渗漏、变形和损坏（A正确B错误）。密封性能闸阀阀板处于关闭状态位置时，进水口应能承受2倍于额定工作压力的静水压，保持5min，阀门各密封处应无渗漏。",{"id":6,"name":27,"category":28,"favorite":29},"初级技能","建筑工程",0]