[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-959731":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},959731,699,1,"单选题","当发生监管报警时，下列关于监管报警的处理方法错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","首先应按火灾报警控制器的“复位”键，恢复控制器监管警报",true,{"key":16,"text":17,"correct":18},"B","然后根据火灾报警控制器的报警信息检查发生监管报警的部位，确认是否有监管报警发生",false,{"key":20,"text":21,"correct":18},"C","若确认有监管报警发生，应根据监管的外部设备类型采取相应措施",{"key":23,"text":24,"correct":18},"D","若为误报警，应检查是否由于监管模块误动作，或者由于人为或其他因素造成误报警","监管报警的处理方法：当发生监管报警时，首先应按火灾报警控制器的“消音”键，终止控制器监管警报声。然后根据火灾报警控制器的报警信息检查发生监管报警的部位，确认是否有监管报警发生。若确认有监管报警发生，应根据监管的外部设备类型采取相应措施。例如，监管报警信号为水流指示器动作、信号阀关闭、空调停机等，应联系维保人员或厂家进行处理。若为误报警，应采取如下措施：检查是否由于监管模块误动作，或者由于人为或其他因素造成误报警。按“复位”键使火灾报警控制器恢复正常状态，观察是否还会误报；如果仍然发生误报，应通知维保人员或厂家进行维修。",{"id":6,"name":27,"category":28,"favorite":29},"初级技能","建筑工程",0]