[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-605-47":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":637},{"id":5,"name":6,"category":7,"favorite":8},605,"消防技术综合能力(一级、二级)","建筑工程",0,47,50,2974,[13,34,46,58,70,82,94,106,118,130,142,154,172,187,199,209,221,229,241,253,265,277,292,304,316,328,340,352,364,376,388,400,412,424,436,451,466,478,490,505,517,529,544,556,568,580,592,601,613,625],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":27,"analysis":33},936995,1,"单选题","某储存丙类液体的储罐去共有6座单座容积为1000m3的地上固定顶罐，分两排布置，每排三座，设置水喷雾灭火系统进行防护冷却。在计算该储罐区的消防冷却用水量时，最多考虑同时冷却（ ）座储罐。",[19,23,26,30],{"key":20,"text":21,"correct":22},"A","2",false,{"key":24,"text":25,"correct":22},"B","4",{"key":27,"text":28,"correct":29},"C","3",true,{"key":31,"text":32,"correct":22},"D","5","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":27,"analysis":33},936996,"下列场所的消防用电应按一级负荷供电的是（ ）。",[38,40,42,44],{"key":20,"text":39,"correct":22},"室外消防用水量大于30L\u002Fs的厂房（仓库）",{"key":24,"text":41,"correct":22},"二类高层民用建筑",{"key":27,"text":43,"correct":29},"建筑高度大于50m的丙类厂房",{"key":31,"text":45,"correct":22},"粮食仓库及粮食筒仓",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":20,"analysis":33},936997,"某炼油厂容积10×104m3的外浮顶原油储罐，设置泡沫灭火系统，则系统设计保护面积应按（ ）确定。",[50,52,54,56],{"key":20,"text":51,"correct":29},"储罐罐壁与泡沫堰板间的环形面积",{"key":24,"text":53,"correct":22},"储罐表面积",{"key":27,"text":55,"correct":22},"储罐横截面面积",{"key":31,"text":57,"correct":22},"防火堤内的地面面积",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":27,"analysis":33},936998,"特等、甲等剧场、超过1500个座位的其他等级剧场和超过2000个座位的会堂或礼堂的舞台葡萄架下部宜选择哪种自动喷水灭火系统（ ）。",[62,64,66,68],{"key":20,"text":63,"correct":22},"湿式系统",{"key":24,"text":65,"correct":22},"预作用系统",{"key":27,"text":67,"correct":29},"雨淋系统",{"key":31,"text":69,"correct":22},"水幕系统",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":31,"analysis":33},936999,"以下关于室内消火栓设置的叙述中，不准确的有（ ）。",[74,76,78,80],{"key":20,"text":75,"correct":22},"消防电梯前室应设消火栓",{"key":24,"text":77,"correct":22},"消火栓应设置在明显且易于操作的部位",{"key":27,"text":79,"correct":22},"消火栓栓口处的出水压力大于0.7MPa时，应设置减压设施",{"key":31,"text":81,"correct":29},"采用临时高压给水方式的室内每个消火栓处均应设置消防启动按钮",{"id":83,"libraryId":5,"type":15,"typeLabel":16,"stem":84,"options":85,"answer":27,"analysis":33},937000,"送修灭火器时，一次送修数量不得超过计算单元配置灭火器总数量的（ ）。",[86,88,90,92],{"key":20,"text":87,"correct":22},"1／2",{"key":24,"text":89,"correct":22},"1／3",{"key":27,"text":91,"correct":29},"1／4",{"key":31,"text":93,"correct":22},"1／5",{"id":95,"libraryId":5,"type":15,"typeLabel":16,"stem":96,"options":97,"answer":20,"analysis":33},937001,"对于A类火灾场所，采用局部应用系统的泡沫灭火系统，则系统设计应符合（ ）。",[98,100,102,104],{"key":20,"text":99,"correct":29},"四周不完全封闭的A类火灾场所，可采用局部应用系统",{"key":24,"text":101,"correct":22},"覆盖保护对象的时间不应小于2min",{"key":27,"text":103,"correct":22},"覆盖保护对象最高点的厚度不应大于0.6m",{"key":31,"text":105,"correct":22},"泡沫混合液连续供给时间不应大于12min",{"id":107,"libraryId":5,"type":15,"typeLabel":16,"stem":108,"options":109,"answer":20,"analysis":33},937002,"防护区内设置的预制灭火系统的充压压力不应大于下列。（ ）。",[110,112,114,116],{"key":20,"text":111,"correct":29},"2.5MPa",{"key":24,"text":113,"correct":22},"4.2MPa",{"key":27,"text":115,"correct":22},"4.3MPa",{"key":31,"text":117,"correct":22},"5.6MPa",{"id":119,"libraryId":5,"type":15,"typeLabel":16,"stem":120,"options":121,"answer":27,"analysis":33},937003,"下列关于各系统适用范围的叙述中，（ ）是错误的。",[122,124,126,128],{"key":20,"text":123,"correct":22},"湿式系统适用于：温度不低于4℃并不高于70℃的环境",{"key":24,"text":125,"correct":22},"干式系统适用于：温度低于4℃，或高于70℃",{"key":27,"text":127,"correct":29},"预作用系统适用于：在低温和高温环境中替代干式系统，但不可替代湿式系统",{"key":31,"text":129,"correct":22},"水幕系统适用于：防火分隔水幕适用于局部防火分隔处",{"id":131,"libraryId":5,"type":15,"typeLabel":16,"stem":132,"options":133,"answer":20,"analysis":33},937004,"下列关于细水雾灭火系统喷头选型的说法，不正确的是（ ）。",[134,136,138,140],{"key":20,"text":135,"correct":29},"对于闭式系统，应选择响应时间指数（RTI）不大于的喷头",{"key":24,"text":137,"correct":22},"对于电子信息系统机房的地板夹层，宜选择适用于低矮空间的喷头",{"key":27,"text":139,"correct":22},"对于闭式系统，选择的喷头公称动作温度宜高于环境最高温度30℃",{"key":31,"text":141,"correct":22},"对于环境条件易使喷头喷孔堵塞的场所，应选用具有相应防护措施且不影响细水雾喷放效果的喷头",{"id":143,"libraryId":5,"type":15,"typeLabel":16,"stem":144,"options":145,"answer":20,"analysis":33},937005,"以下关于室内消火栓设置的叙述中，不正确的是（ ）。",[146,148,150,152],{"key":20,"text":147,"correct":29},"消防电梯前室应设消火栓，但不应计入消火栓使用数量",{"key":24,"text":149,"correct":22},"住宅的室内消火栓宜设置在楼梯间及其休息平台",{"key":27,"text":151,"correct":22},"同一楼梯间及其附近不同层设置的消火栓，其平面位置宜相同",{"key":31,"text":153,"correct":22},"冷库的室内消火栓应设置在常温穿堂或楼梯间内。",{"id":155,"libraryId":5,"type":156,"typeLabel":157,"stem":158,"options":159,"answer":171,"analysis":33},937006,2,"多选题","下列项目中，至少每月检查一次的是（ ）。",[160,162,164,166,168],{"key":20,"text":161,"correct":22},"灭火控制器运行情况",{"key":24,"text":163,"correct":22},"启动气体储瓶和驱动气体储瓶压力",{"key":27,"text":165,"correct":29},"驱动气体储瓶充装量",{"key":31,"text":167,"correct":29},"干粉储存装置部件",{"key":169,"text":170,"correct":22},"E","防护区及干粉储存装置间","CD",{"id":173,"libraryId":5,"type":156,"typeLabel":157,"stem":174,"options":175,"answer":186,"analysis":33},937007,"干粉灭火系统采用局部应用灭火系统的保护对象，应符合（ ）。",[176,178,180,182,184],{"key":20,"text":177,"correct":29},"当保护对象有可燃气体，易燃、可燃液体供应源时，启动干粉灭火系统之前或同时，必须切断气体、液体的供应源",{"key":24,"text":179,"correct":22},"当保护对象为可燃液体时，液面至容器缘口的距离不得小于200mm",{"key":27,"text":181,"correct":29},"在喷头和保护对象之间，喷头喷射角范围内不应有遮挡物",{"key":31,"text":183,"correct":29},"保护对象周围的空气流动速度不应大于2m\u002Fs",{"key":169,"text":185,"correct":29},"扑灭BC类火灾的干粉一般选择是碳酸氢钠干粉，扑灭A类火灾的干粉一般选择是磷酸铵盐干粉","ACDE",{"id":188,"libraryId":5,"type":15,"typeLabel":16,"stem":189,"options":190,"answer":20,"analysis":33},937008,"某电子计算机主机房为无人值守的封闭区域，室内净高为3.6m，采用全淹没式七氟丙烷灭火系统防护。该防护区设置的泄压口下沿距离防护区楼地板的高度不应低于（ ）m。",[191,193,195,197],{"key":20,"text":192,"correct":29},"2.4",{"key":24,"text":194,"correct":22},"1.8",{"key":27,"text":196,"correct":22},"3.0",{"key":31,"text":198,"correct":22},"3.2",{"id":200,"libraryId":5,"type":15,"typeLabel":16,"stem":201,"options":202,"answer":27,"analysis":33},937009,"泡沫消防泵中的泡沫液泵应能耐受不低于（ ）min的空载运转。",[203,204,205,207],{"key":20,"text":28,"correct":22},{"key":24,"text":32,"correct":22},{"key":27,"text":206,"correct":29},"10",{"key":31,"text":208,"correct":22},"15",{"id":210,"libraryId":5,"type":15,"typeLabel":16,"stem":211,"options":212,"answer":24,"analysis":33},937010,"以下有关自动喷水灭火系统的描述中（ ）是不合理的。",[213,215,217,219],{"key":20,"text":214,"correct":22},"为避免系统管道充水低温结冰或高温气化，可用预作用系统替代湿式系统",{"key":24,"text":216,"correct":29},"在准工作状态严禁管道漏水的场所和为改善系统滞后喷水的现象，可采用干式系统替代预作用系统",{"key":27,"text":218,"correct":22},"在设置防火墙有困难时，可采用闭式系统保护防火卷帘的防火分隔形式替代防火分隔水幕",{"key":31,"text":220,"correct":22},"为扑救高堆垛仓库火灾，设置早期抑制快速响应喷头的自动喷水灭火系统，可采用干式系统替代湿式系统",{"id":222,"libraryId":5,"type":15,"typeLabel":16,"stem":223,"options":224,"answer":24,"analysis":33},937011,"固定式泡沫灭火系统的设计应满足在泡沫消防水泵或泡沫混合液泵启动后，将泡沫混合液或泡沫输送到保护对像的时间不大于（ ） min。",[225,226,227,228],{"key":20,"text":28,"correct":22},{"key":24,"text":32,"correct":29},{"key":27,"text":206,"correct":22},{"key":31,"text":208,"correct":22},{"id":230,"libraryId":5,"type":15,"typeLabel":16,"stem":231,"options":232,"answer":27,"analysis":33},937012,"下列关于消防给水形式的叙述中，错误的是（ ）",[233,235,237,239],{"key":20,"text":234,"correct":22},"按管网的水压可分为低压、高压、临时高压消防给水系统",{"key":24,"text":236,"correct":22},"建筑物、堆场等场所室外宜采用低压消防给水系统，工艺装置区、储罐区等场所应采用高压或临时高压消防给水系统，当室外采用高压或临时高压消防给水系统时，宜与室内合用",{"key":27,"text":238,"correct":29},"室内应采用高压或临时高压消防给水系统，可以与生产生活给水系统合用",{"key":31,"text":240,"correct":22},"消防给水系统应根据建筑的用途功能、体积、高度、耐火等级、火灾危险性、重要性、次生灾害、商务连续性、水源条件等因素综合确定其可靠性和供水方式",{"id":242,"libraryId":5,"type":15,"typeLabel":16,"stem":243,"options":244,"answer":20,"analysis":33},937013,"非水溶性甲、乙、丙类液体固定顶储罐泡沫灭火系统中，当采用液下喷射系统时低倍数泡沫液不应选择（ ）。",[245,247,249,251],{"key":20,"text":246,"correct":29},"蛋白泡沫液",{"key":24,"text":248,"correct":22},"氟蛋白泡沫液",{"key":27,"text":250,"correct":22},"成膜氟蛋白泡沫液",{"key":31,"text":252,"correct":22},"水成膜泡沫液",{"id":254,"libraryId":5,"type":15,"typeLabel":16,"stem":255,"options":256,"answer":31,"analysis":33},937014,"气体灭火采用均衡系统的优点，下列叙述中错误的是。",[257,259,261,263],{"key":20,"text":258,"correct":22},"灭火剂在防护区里容易做到喷放均匀，利于灭火",{"key":24,"text":260,"correct":22},"可不考虑灭火剂在管网中的剩余量，做到节省",{"key":27,"text":262,"correct":22},"减少设计工作的计算量",{"key":31,"text":264,"correct":29},"减少管材",{"id":266,"libraryId":5,"type":15,"typeLabel":16,"stem":267,"options":268,"answer":20,"analysis":33},937015,"下列（ ）自动喷水灭火系统的设置场所可不设置火灾报警系统。",[269,271,273,275],{"key":20,"text":270,"correct":29},"设置湿式系统的场所",{"key":24,"text":272,"correct":22},"设置预作用系统的场所",{"key":27,"text":274,"correct":22},"设置雨淋系统的场所",{"key":31,"text":276,"correct":22},"设置自动控制水幕系统的场所",{"id":278,"libraryId":5,"type":156,"typeLabel":157,"stem":279,"options":280,"answer":291,"analysis":33},937016,"根据《火灾自动报警系统施工及验收规范》GB 50166—2019的规定，下列属于消防联动控制器调试内容的有（ ）。",[281,283,285,287,289],{"key":20,"text":282,"correct":29},"自检功能和操作级别",{"key":24,"text":284,"correct":29},"屏蔽功能",{"key":27,"text":286,"correct":29},"检查消音、复位功能",{"key":31,"text":288,"correct":29},"控制器的负载功能",{"key":169,"text":290,"correct":22},"高限报警或低、高两段报警功能","ABCD",{"id":293,"libraryId":5,"type":15,"typeLabel":16,"stem":294,"options":295,"answer":20,"analysis":33},937018,"消防水池大于500m3应分成两格的主要原因是（ ）。",[296,298,300,302],{"key":20,"text":297,"correct":29},"分成两格是一个水池检修时，另一个水池仍能供应消防用水",{"key":24,"text":299,"correct":22},"分成两格能更好的供消防车取水",{"key":27,"text":301,"correct":22},"分成两格能缩短消防水池的补水时间",{"key":31,"text":303,"correct":22},"分成两格主要是防止消防水泵吸水时互相影响",{"id":305,"libraryId":5,"type":15,"typeLabel":16,"stem":306,"options":307,"answer":20,"analysis":33},937019,"自动喷水灭火系统设置场所的危险等级应根据建筑规模、高度以及火灾危险性、火灾荷载和保护对象的特点等确定。下列建筑中，自动喷水灭火系统设置场所的火灾危险等级为中危险级Ⅰ级的是（ ）。",[308,310,312,314],{"key":20,"text":309,"correct":29},"建筑高度为50m的办公楼",{"key":24,"text":311,"correct":22},"建筑高度为23m的四星级旅馆",{"key":27,"text":313,"correct":22},"2000个座位剧场的舞台",{"key":31,"text":315,"correct":22},"总建筑面积5600m2的商场",{"id":317,"libraryId":5,"type":15,"typeLabel":16,"stem":318,"options":319,"answer":20,"analysis":33},937020,"灭火器挂钩、托架等附件安装后，挂钩、托架能够承受（ ）倍的手提式灭火器的静载荷，承载（ ）min后，不出现松动、脱落、断裂和明显变形等现象。",[320,322,324,326],{"key":20,"text":321,"correct":29},"5，5",{"key":24,"text":323,"correct":22},"3，5",{"key":27,"text":325,"correct":22},"3，10",{"key":31,"text":327,"correct":22},"5，10",{"id":329,"libraryId":5,"type":15,"typeLabel":16,"stem":330,"options":331,"answer":24,"analysis":33},937021,"某商业综合体建筑，其办公区、商业区分别设置消防控制室，并将办公区的消防控制室作为主消防控制室，其它区作为分消防控制室，各分消防控制室内的消防设备之间可以相互传输、显示状态信息，但不应相互控制。消防控制室图像显示装置记录容量不应少于（ ）",[332,334,336,338],{"key":20,"text":333,"correct":22},"5000",{"key":24,"text":335,"correct":29},"10000",{"key":27,"text":337,"correct":22},"20000",{"key":31,"text":339,"correct":22},"50000",{"id":341,"libraryId":5,"type":15,"typeLabel":16,"stem":342,"options":343,"answer":20,"analysis":33},937022,"下列关于消防水源设计的叙述中，（ ）是错误的。",[344,346,348,350],{"key":20,"text":345,"correct":29},"市政给水、消防水池、天然水源等可作为消防水源，并宜采用消防水池",{"key":24,"text":347,"correct":22},"天然水源的设计枯水流量保证率应根据城乡规模和工业项目的重要性、火灾危险性和经济合理性等综合因素确定，宜为90%-97%",{"key":27,"text":349,"correct":22},"设有消防车取水口的消防水池，应设置消防车到达取水口的消防车道和消防车回车场或回车道",{"key":31,"text":351,"correct":22},"当生产、生活用水量达到最大，市政给水管网或入户引入管不能满足室内、室外消防给水设计流量时，应设置消防水池",{"id":353,"libraryId":5,"type":15,"typeLabel":16,"stem":354,"options":355,"answer":20,"analysis":33},937023,"在广州市建设一座地下车库，采用自动喷水灭火系统保护，系统的设计详见数按照火灾危险等级的中危险Ⅱ判断，其作用面积不应小于（ ）m2。",[356,358,360,362],{"key":20,"text":357,"correct":29},"160",{"key":24,"text":359,"correct":22},"192",{"key":27,"text":361,"correct":22},"206",{"key":31,"text":363,"correct":22},"208",{"id":365,"libraryId":5,"type":15,"typeLabel":16,"stem":366,"options":367,"answer":31,"analysis":33},937024,"根据现行国家标准《自动喷水灭火系统施工及验收规范》GB 50261—2017，下列关于自动喷水灭火系统维护的说法中，不正确的是（ ）。",[368,370,372,374],{"key":20,"text":369,"correct":22},"内燃机驱动的消防水泵应每月启动运转一次",{"key":24,"text":371,"correct":22},"当消防水泵为自动控制启动时，应每月模拟自动控制的条件启动运转一次",{"key":27,"text":373,"correct":22},"每月应利用末端试水装置对水流指示器进行试验",{"key":31,"text":375,"correct":29},"室外阀门井中，进水管上的控制阀门应每个月检查一次，核实其处于全开启状态",{"id":377,"libraryId":5,"type":15,"typeLabel":16,"stem":378,"options":379,"answer":31,"analysis":33},937025,"建筑灭火器配置验收按照单栋建筑独立验收，局部验收按照规定要求申报。各验收子项目缺陷划分为严重缺陷项 A、重缺陷项 B、和轻缺陷项 C、灭火器配置验收的合格判定条件为（ ）。",[380,382,384,386],{"key":20,"text":381,"correct":22},"A=0，且B≤2，且B+C≤6为合格",{"key":24,"text":383,"correct":22},"A=0，且B≤1，且B+C≤6为合格",{"key":27,"text":385,"correct":22},"A=0，且B≤2，且B+C≤4为合格",{"key":31,"text":387,"correct":29},"A=0，且B≤1，且B+C≤4为合格",{"id":389,"libraryId":5,"type":15,"typeLabel":16,"stem":390,"options":391,"answer":31,"analysis":33},937026,"下列关于火灾延续时间的叙述中，（ ）是错误的。",[392,394,396,398],{"key":20,"text":393,"correct":22},"火灾延续时间是水灭火设施达到设计流量的供水时间",{"key":24,"text":395,"correct":22},"甲类液体覆土油罐火灾延续时间不应小于4.0h",{"key":27,"text":397,"correct":22},"高层商业楼火灾延续时间应按3.0h算",{"key":31,"text":399,"correct":29},"替代防火墙的防火分隔水幕的火灾延续时间不应小于1.0h",{"id":401,"libraryId":5,"type":15,"typeLabel":16,"stem":402,"options":403,"answer":31,"analysis":33},937027,"某建筑采用临时高压消防给水系统，经计算消防水泵设计扬程为0.9MPa。选择消防水泵时，消防水泵零流量时的压力应在（ ）MPa之间。",[404,406,408,410],{"key":20,"text":405,"correct":22},"0.9~1.08",{"key":24,"text":407,"correct":22},"1.26~1.35",{"key":27,"text":409,"correct":22},"1.26~1.44",{"key":31,"text":411,"correct":29},"1.08~1.26",{"id":413,"libraryId":5,"type":15,"typeLabel":16,"stem":414,"options":415,"answer":31,"analysis":33},937028,"有一座高度大于54的商业办公综合体，下列关于本综合体消火栓系统施工安装要求的描述中正确的是（ ）",[416,418,420,422],{"key":20,"text":417,"correct":22},"室内消火栓内设置的消火栓按钮应具备启动消防水泵的功能",{"key":24,"text":419,"correct":22},"第5层与第7层的消火栓应在同一个水平位置，左右误差不得大于20mm",{"key":27,"text":421,"correct":22},"室内消火栓管道安装顺序是主干管、干管、分支管、垂直管、横管",{"key":31,"text":423,"correct":29},"室内消火栓栓口出水方向安装应朝下，并设置在消火栓箱开门处",{"id":425,"libraryId":5,"type":15,"typeLabel":16,"stem":426,"options":427,"answer":27,"analysis":33},937029,"下列建筑中，自动喷水灭火系统设置场所的火灾危险等级为中危险级Ⅱ级的是（ ）。",[428,430,432,434],{"key":20,"text":429,"correct":22},"建筑高度为80米综合楼",{"key":24,"text":431,"correct":22},"图书馆",{"key":27,"text":433,"correct":29},"地下停车场",{"key":31,"text":435,"correct":22},"总建筑面积45000平方米的图书城",{"id":437,"libraryId":5,"type":156,"typeLabel":157,"stem":438,"options":439,"answer":450,"analysis":33},937030,"下列关于工业建筑设置需要排烟系统的说法正确的是（ ）。",[440,442,444,446,448],{"key":20,"text":441,"correct":29},"人员较多的丙类生产场所",{"key":24,"text":443,"correct":29},"丙类厂房内建筑面积为500m2且经常有人停留或可燃物较多的地上房间",{"key":27,"text":445,"correct":29},"高度大于32m的高层厂房（仓库）内长度为40m的疏散走道",{"key":31,"text":447,"correct":22},"建筑面积大于5000m2的丁类仓库",{"key":169,"text":449,"correct":29},"占地面积大于1OOOm2的丙类仓库","ABCE",{"id":452,"libraryId":5,"type":156,"typeLabel":157,"stem":453,"options":454,"answer":465,"analysis":33},937031,"下列关于细水雾灭火系统的说法中错误的是（ ）。",[455,457,459,461,463],{"key":20,"text":456,"correct":22},"喷头的最低设计工作压力不应小于1.20MPa",{"key":24,"text":458,"correct":22},"闭式系统的作用面积不宜小于140m2",{"key":27,"text":460,"correct":29},"采用全淹没应用方式的开式系统，其防护区数量不应大于5个",{"key":31,"text":462,"correct":29},"开式系统的设计响应时间不应大于60s",{"key":169,"text":464,"correct":29},"用于扑救厨房内烹饪设备及其排烟罩和排烟管道部位的火灾时，系统的设计持续喷雾时间不应小于10s，设计冷却时间不应小于10min","CDE",{"id":467,"libraryId":5,"type":15,"typeLabel":16,"stem":468,"options":469,"answer":27,"analysis":33},937032,"下列关于消防水泵的启动的说法中正确的是（ ）。",[470,472,474,476],{"key":20,"text":471,"correct":22},"消防水泵应能手动启停和自动启动，且应确保从接到启泵信号到水泵正常运转的自动启动时间不应大于1min",{"key":24,"text":473,"correct":22},"消防水泵宜设置自动停泵的控制功能，停泵也可由具有管理权限的工作人员根据火灾扑救情况确定",{"key":27,"text":475,"correct":29},"消火栓按钮不宜作为直接启动消防泵的开关，但可作为发出报警信号的开关或启动干式消火栓系统的快速启闭装置等",{"key":31,"text":477,"correct":22},"稳压泵应由消防水泵出水干管上设置的压力开关、高位消防水箱出水管上的流量开关，或报警阀压力开关等开关信号启停",{"id":479,"libraryId":5,"type":15,"typeLabel":16,"stem":480,"options":481,"answer":27,"analysis":33},937033,"早期抑制快速响应喷头的响应时间指数是（ ）。",[482,484,486,488],{"key":20,"text":483,"correct":22},"RTI≤50（m·s）0.5",{"key":24,"text":485,"correct":22},"RTI≤350（m·s）0.5",{"key":27,"text":487,"correct":29},"RTI≤28±8（m·s）0.5",{"key":31,"text":489,"correct":22},"RTI≤50±8（m·s）0.5",{"id":491,"libraryId":5,"type":156,"typeLabel":157,"stem":492,"options":493,"answer":504,"analysis":33},937034,"某办公楼设置了火灾自动报警系统，该办公楼在日常运行过程中某些场所的探测器经常误报警，导致误报警的原因可能是（ ）。",[494,496,498,500,502],{"key":20,"text":495,"correct":29},"探测器选型不对",{"key":24,"text":497,"correct":29},"误报警的场所使用功能发生了改变",{"key":27,"text":499,"correct":22},"报警总线与探测器底座接触不良",{"key":31,"text":501,"correct":29},"环境因素",{"key":169,"text":503,"correct":29},"探测器产品质量存在问题","ABDE",{"id":506,"libraryId":5,"type":15,"typeLabel":16,"stem":507,"options":508,"answer":31,"analysis":33},937035,"某消防工程中单位在消火栓系统安装结束后对系统进行调试，根据现行国家标准《消防给水及消火栓系统技术规范》（GB 50974），关于消火栓调试和测试的说法中，正确的是（ ）。",[509,511,513,515],{"key":20,"text":510,"correct":22},"只需测试一层消火栓的出流量、压力",{"key":24,"text":512,"correct":22},"应根据试验消火栓的流量，检测减压阀的减压能力",{"key":27,"text":514,"correct":22},"应在消防水泵启动后，检测消防水泵自动停泵的时间",{"key":31,"text":516,"correct":29},"应检查旋转型消火栓的性能",{"id":518,"libraryId":5,"type":15,"typeLabel":16,"stem":519,"options":520,"answer":31,"analysis":33},937036,"下列关于消防水泵控制的说法中正确的是（ ）。",[521,523,525,527],{"key":20,"text":522,"correct":22},"消防水泵控制柜在平时有人值班时应使消防水泵处于手动动启泵状态",{"key":24,"text":524,"correct":22},"消防水泵控制柜应设置机械应急启泵功能，机械应急启动时，应确保消防水泵在报警后3min内正常工作",{"key":27,"text":526,"correct":22},"消防水泵的双电源自动切换时间不应大于5s，一路电源与内燃机动力的切换时间不应大于30s",{"key":31,"text":528,"correct":29},"消防水泵控制柜设置在专用消防水泵控制室时，其防护等级不应低于IP30；与消防水泵设置在同一空间时，其防护等级不应低于IP55",{"id":530,"libraryId":5,"type":156,"typeLabel":157,"stem":531,"options":532,"answer":543,"analysis":33},937037,"某建筑内设有火灾自动报警系统，下列关于火灾自动报警系统的安装检查结果中，不符合安装要求的是（ ）。",[533,535,537,539,541],{"key":20,"text":534,"correct":29},"点型感烟探测器距离空调送风口的距离1m",{"key":24,"text":536,"correct":22},"宽度为2．5m的内疏散走道上设置的感烟探测器，间距12m",{"key":27,"text":538,"correct":22},"探测器至墙壁、梁边的水平距离0．5m",{"key":31,"text":540,"correct":29},"从接线盒引到探测器底座的线路采用长度3m的金属软管保护",{"key":169,"text":542,"correct":29},"建筑内被高度为650mm的结构梁隔断的区域未设火灾探测器","ADE",{"id":545,"libraryId":5,"type":15,"typeLabel":16,"stem":546,"options":547,"answer":31,"analysis":33},937038,"关于自动喷水灭火系统湿式和干式二种报警阀功能的叙述中，错误的是（ ）。",[548,550,552,554],{"key":20,"text":549,"correct":22},"均具有喷头动作后报警水流驱动水力警铃和压力开关报警的功能",{"key":24,"text":551,"correct":22},"均具有防止系统水流倒流至水源的止回功能",{"key":27,"text":553,"correct":22},"均具有接通或关断报警水流的功能",{"key":31,"text":555,"correct":29},"均具有延迟误报警的功能",{"id":557,"libraryId":5,"type":15,"typeLabel":16,"stem":558,"options":559,"answer":27,"analysis":33},937039,"报警阀组的安装顺序为（ ）。",[560,562,564,566],{"key":20,"text":561,"correct":22},"报警阀-水源控制阀-报警阀辅助管道",{"key":24,"text":563,"correct":22},"报警阀-报警阀辅助管道-水源控制阀",{"key":27,"text":565,"correct":29},"水源控制阀-报警阀-报警阀辅助管道",{"key":31,"text":567,"correct":22},"水源控制阀-报警阀辅助管道-报警阀",{"id":569,"libraryId":5,"type":15,"typeLabel":16,"stem":570,"options":571,"answer":31,"analysis":33},937040,"湿式报警阀组设置时，水力警铃与报警阀连接的管道直径应为（ ）mm，总长度不宜大于（ ）m。",[572,574,576,578],{"key":20,"text":573,"correct":22},"15，20",{"key":24,"text":575,"correct":22},"15，25",{"key":27,"text":577,"correct":22},"20，15",{"key":31,"text":579,"correct":29},"20，20",{"id":581,"libraryId":5,"type":15,"typeLabel":16,"stem":582,"options":583,"answer":24,"analysis":33},937041,"下列关于室外消防给水管的布置中错误的是（ ）。",[584,586,588,590],{"key":20,"text":585,"correct":22},"工业园区、商务区和居住区等区域采用两路消防供水，当其中一条引入管发生故障时，其余引入管在保证满足70%生产生活给水的最大小时设计流量",{"key":24,"text":587,"correct":29},"接市政消火栓的环状给水管网的管径不应小于DN200，枝状管网的管径不宜小于DN150",{"key":27,"text":589,"correct":22},"设有市政消火栓的市政给水管网宜为环状管网，但当城镇人口小于2.5万人时，可为枝状管网",{"key":31,"text":591,"correct":22},"向室外、室内环状消防给水管网供水的输水干管不应少于两条，当其中一条发生故障时，其余的输水干管应仍能满足消防给水设计流量。",{"id":593,"libraryId":5,"type":15,"typeLabel":16,"stem":594,"options":595,"answer":20,"analysis":33},937042,"消防联动控制器应能按设定的控制逻辑向各相关的受控设备发出联动控制信号，并接受相关设备的联动反馈信号；联动控制器应在（ ）秒内按设定的控制逻辑准确发出联动控制信号给相应的消防设备。",[596,597,598,599],{"key":20,"text":28,"correct":29},{"key":24,"text":32,"correct":22},{"key":27,"text":206,"correct":22},{"key":31,"text":600,"correct":22},"30",{"id":602,"libraryId":5,"type":15,"typeLabel":16,"stem":603,"options":604,"answer":24,"analysis":33},937043,"关于消防稳压泵的说法错误的是（ ）。",[605,607,609,611],{"key":20,"text":606,"correct":22},"当高位消防水箱最低有效水位不能满足水灭火设施最不利点处的静水压力要求时，应设稳压泵",{"key":24,"text":608,"correct":29},"稳压泵的设计流量应小于消防给水系统管网的正常泄漏量和系统自动启动流量",{"key":27,"text":610,"correct":22},"稳压泵的设计压力应满足系统自动启动和管网充满水的要求",{"key":31,"text":612,"correct":22},"稳压泵的设计压力应保持系统最不利点处水灭火设施在准工作状态时的静水压力应大于0.15MPa",{"id":614,"libraryId":5,"type":15,"typeLabel":16,"stem":615,"options":616,"answer":31,"analysis":33},937044,"下列关于报警阀组的叙述中，（ ）是错误的。",[617,619,621,623],{"key":20,"text":618,"correct":22},"保护室内钢屋架等建筑构件的闭式系统，应设独立的报警阀组",{"key":24,"text":620,"correct":22},"串联接入湿式系统配水干管的其他自动喷水灭火系统，应分别设置独立的报警阀组",{"key":27,"text":622,"correct":22},"水幕系统应设独立的报警阀组或感温雨淋阀",{"key":31,"text":624,"correct":29},"某5层商场设湿式系统，每层有200个喷头，设一个报警阀组",{"id":626,"libraryId":5,"type":15,"typeLabel":16,"stem":627,"options":628,"answer":24,"analysis":33},937045,"下列关于火灾自动报警系统和消防应急广播系统的联动控制设计的说法，正确的是（ ）",[629,631,633,635],{"key":20,"text":630,"correct":22},"设置消防联动控制器的火灾自动报警系统，火灾声光警报器只能由消防联动控制器控制",{"key":24,"text":632,"correct":29},"同一建筑内设置多个火灾声警报器时，火灾自动报警系统应能同时启动和停止所有火灾声警报器工作",{"key":27,"text":634,"correct":22},"消防应急广播系统的联动控制信号应由火灾报警控制器发出，当确认火灾后，应同时向全楼进行广播",{"key":31,"text":636,"correct":22},"集中报警系统可不设置消防应急广播",[638,641,644,647,650,653],{"id":15,"name":639,"category":7,"favorite":640},"领导干部任职前廉政法规知识测试题",92,{"id":642,"name":643,"category":7,"favorite":15},595,"建筑结构与设备",{"id":645,"name":646,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":648,"name":649,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":651,"name":652,"category":7,"favorite":8},534,"BIM工程师",{"id":654,"name":652,"category":7,"favorite":8},535]