[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-605-4":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":664},{"id":5,"name":6,"category":7,"favorite":8},605,"消防技术综合能力(一级、二级)","建筑工程",0,4,50,2974,[13,38,52,67,79,94,106,118,130,142,157,172,184,196,208,220,235,250,262,274,286,298,313,328,340,352,364,376,388,400,412,424,436,448,460,475,489,501,516,528,540,552,566,578,590,602,614,626,638,650],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":36,"analysis":37},934824,2,"多选题","(2017年真题) 关于疏散楼梯最小净宽度的说法， 符合现行国家技术标准的有（??）。",[19,23,27,30,33],{"key":20,"text":21,"correct":22},"A","除规范另有规定外， 多层公共建筑疏散楼梯的净宽度不应小于1.00m",false,{"key":24,"text":25,"correct":26},"B","汽车库的疏散楼梯的最小净宽度不应小于1.10m",true,{"key":28,"text":29,"correct":26},"C","高层病房楼的疏散楼梯净宽度不应小于1.30m",{"key":31,"text":32,"correct":22},"D","高层办公建筑疏散楼梯的净宽度不应小于1. 40m",{"key":34,"text":35,"correct":22},"E","人防工程中商场的疏散楼梯 净宽度不应小于1.20m","BC","",{"id":39,"libraryId":5,"type":40,"typeLabel":41,"stem":42,"options":43,"answer":24,"analysis":37},934826,1,"单选题","(2018年真题) 对某三层影院进行防火检查，安全疏散设施的下列检查结果中，不符合现行标准要求的是（??）",[44,46,48,50],{"key":20,"text":45,"correct":22},"建筑室外疏散通道的净宽度为 3.5m",{"key":24,"text":47,"correct":26},"首层疏散门净宽度 1.30m",{"key":28,"text":49,"correct":22},"首层疏散门外 1.50m 处设置踏步",{"key":31,"text":51,"correct":22},"楼梯间在首层通过 15m 的疏散走道通至室外",{"id":53,"libraryId":5,"type":15,"typeLabel":16,"stem":54,"options":55,"answer":66,"analysis":37},934827,"(2018年真题) 某建筑高度为36m的高层住宅楼，疏散楼梯釆用剪刀楼梯间，设有消防电梯，剪刀楼梯间共用前室，且与消防电梯的前室合用。该住宅楼的下列防火检查结果中，符合现行国家标准要求的有( )。",[56,58,60,62,64],{"key":20,"text":57,"correct":26},"每户的入户门为净宽1.0m的乙级防火门",{"key":24,"text":59,"correct":26},"消防电梯轿厢内设有专用消防对讲电话",{"key":28,"text":61,"correct":22},"合用前室的使用面积为10㎡，短边长度为2.4m",{"key":31,"text":63,"correct":26},"消防电梯内铭牌显示其载重量为1200kg",{"key":34,"text":65,"correct":22},"消防电梯轿厢内采用阻燃木饰面装修","ABD",{"id":68,"libraryId":5,"type":40,"typeLabel":41,"stem":69,"options":70,"answer":20,"analysis":37},934828,"(2018年真题) 某鳗鱼饲料加工厂，其饲料加工车间，地上 6 层，建筑高度 36m，每层建筑面积 2000㎡，同时工作人数 8 人；饲料仓库，地上 3 层，建筑高度 20m，每层建筑面积 300 平方米，同时工作人数 3 人。对该工厂的安全疏散设施进行防火检查，下列检查结果中，不符合现行国家标准要求的是（）",[71,73,75,77],{"key":20,"text":72,"correct":26},"饲料仓库室外疏散楼梯周围 1.50m 处的外墙面上设置一个通风高窗",{"key":24,"text":74,"correct":22},"饲料加工车间疏散楼梯采用封闭楼梯间",{"key":28,"text":76,"correct":22},"饲料仓库仅设置一部室外疏散楼梯",{"key":31,"text":78,"correct":22},"饲料加工车间疏散楼梯净宽度为 1.10m",{"id":80,"libraryId":5,"type":15,"typeLabel":16,"stem":81,"options":82,"answer":93,"analysis":37},934829,"(2018年真题) 下列安全出口和疏散门的防火检查结果中，不符合现行国家标准要求的有（ ）",[83,85,87,89,91],{"key":20,"text":84,"correct":22},"单层的谷物仓库在外墙上设置净宽为5m的金属推拉门作为疏散门",{"key":24,"text":86,"correct":26},"多层老年人照料设施中位于走道尽端的康复用房，建筑面积45㎡，设置一个疏散门",{"key":28,"text":88,"correct":22},"多层办公楼封闭楼梯间的门采用双向弹簧门",{"key":31,"text":90,"correct":26},"防烟楼梯间首层直接对外的门采用与楼梯段等宽的向外开启的安全玻璃门",{"key":34,"text":92,"correct":26},"多层建筑内建筑面积300㎡的歌舞厅室内最远点至疏散门距离为12m","BDE",{"id":95,"libraryId":5,"type":40,"typeLabel":41,"stem":96,"options":97,"answer":28,"analysis":37},934830,"(2016年真题)对某33层住宅建筑的消防电梯进行防火检查，下列检查内容中，不属于防火检查内容的是（??）",[98,100,102,104],{"key":20,"text":99,"correct":22},"电梯的载重量",{"key":24,"text":101,"correct":22},"首层设置的消防员专用操作按钮",{"key":28,"text":103,"correct":26},"消防电梯内的安装摄像头",{"key":31,"text":105,"correct":22},"消防电梯从首层到达顶层的时间",{"id":107,"libraryId":5,"type":40,"typeLabel":41,"stem":108,"options":109,"answer":28,"analysis":37},934831,"(2016年真题)对防火门进行检查时，应注意检查防火门的门扇与下框或地面的活动间隙，根据现行国家消防技术标准的规定，该间隙不应大于（??）mm",[110,112,114,116],{"key":20,"text":111,"correct":22},"3",{"key":24,"text":113,"correct":22},"6",{"key":28,"text":115,"correct":26},"9",{"key":31,"text":117,"correct":22},"12",{"id":119,"libraryId":5,"type":40,"typeLabel":41,"stem":120,"options":121,"answer":24,"analysis":37},934832,"(2016年真题) 对建筑进行防火检查时，应注意检查建筑的疏散楼梯的形式，下列建筑中，应彩用防烟楼梯间的是（??）",[122,124,126,128],{"key":20,"text":123,"correct":22},"建筑高度为32M的高层丙类仓库",{"key":24,"text":125,"correct":26},"建筑高度为36M的住宅建筑",{"key":28,"text":127,"correct":22},"建筑高度为10M的医院建筑",{"key":31,"text":129,"correct":22},"建筑高度为30M的学校办公楼",{"id":131,"libraryId":5,"type":40,"typeLabel":41,"stem":132,"options":133,"answer":31,"analysis":37},934833,"(2016年真题) 某大型人防工程内的避难走道，与4个防火分区相连，每个防火分区的建筑面积均为2000m2。对该避难走道进行防火检查，下列检查结果中，不符台现行国家消防技术标准的是（??）。",[134,136,138,140],{"key":20,"text":135,"correct":22},"避难走道的两端各设置了1个直通地面的安全出口",{"key":24,"text":137,"correct":22},"每个防火分区至避难走道入口处设置了防烟前室，其使用面积为6m2",{"key":28,"text":139,"correct":22},"避难走道自都采用轻钢龙骨石膏板做吊顶",{"key":31,"text":141,"correct":26},"其中一个防火分区通向避难走道的门至该避难走道最近直通地面的出口的距离为65m",{"id":143,"libraryId":5,"type":15,"typeLabel":16,"stem":144,"options":145,"answer":156,"analysis":37},934834,"(2016年真题) 对建筑的疏散楼梯进行工程验收时，下列关于疏散楼梯间检查的做法中，正确的有（??）",[146,148,150,152,154],{"key":20,"text":147,"correct":26},"检查疏散楼梯间在各层的位置是否改变",{"key":24,"text":149,"correct":22},"检测疏散楼梯的净宽度，每部楼梯的测量点不少于3处",{"key":28,"text":151,"correct":26},"检查地下与地上共用的楼梯间在首层地下层的出入口处是否设置防火隔墙和乙级防火门完全隔开",{"key":31,"text":153,"correct":26},"测量疏散楼梯间的门完全开启时楼梯平台的有效宽度",{"key":34,"text":155,"correct":26},"检查通向建筑屋面的疏散楼梯间的门的开启方向是否正确","ACDE",{"id":158,"libraryId":5,"type":15,"typeLabel":16,"stem":159,"options":160,"answer":171,"analysis":37},934835,"(2016年真题) 安全疏散距离是安全疏散设计的一项重要内容，关于安全疏散距离的设置，下列说法中，符合现行国家消防技术标准要求的有（??）。",[161,163,165,167,169],{"key":20,"text":162,"correct":22},"商场营业厅内任意点至疏散门的距离不应大于30m",{"key":24,"text":164,"correct":22},"设置自动喷水系统的场所，室内任意点至安全出口的安全疏散距离可在规范规定值的基础上增加25%",{"key":28,"text":166,"correct":22},"高层建筑在首层未采用防烟楼梯间前室时，可将直通室外的门设置在离楼梯间不大于15m处",{"key":31,"text":168,"correct":26},"采用敞开式外廊的建筑，安全疏散距离可在规范规定值的基础上增加5m",{"key":34,"text":170,"correct":26},"位于二级耐火等级建筑内的卡拉OK厅，厅内任一点至直通疏散走道的疏散门的直线距离不应大于9m","DE",{"id":173,"libraryId":5,"type":40,"typeLabel":41,"stem":174,"options":175,"answer":28,"analysis":37},934836,"(2017年真题)关于高层办公楼疏散楼梯设置的说法中，错误的是（??）",[176,178,180,182],{"key":20,"text":177,"correct":22},"疏散楼梯间内不得设置烧水间、可燃材料储存室、垃圾道",{"key":24,"text":179,"correct":22},"疏散楼梯间不得设置影响疏散的凸出物或其他障碍物",{"key":28,"text":181,"correct":26},"疏散楼梯间必须靠外墙设置并开设外窗",{"key":31,"text":183,"correct":22},"公共建筑的疏散楼梯间不得敷设可燃气体管道",{"id":185,"libraryId":5,"type":40,"typeLabel":41,"stem":186,"options":187,"answer":31,"analysis":37},934837,"(2017年真题)下列避难走道的防火检查结果中，不符合现行国家消防技术标准的是（??）",[188,190,192,194],{"key":20,"text":189,"correct":22},"避难走道采用耐火极限3.00h的防火墙和耐火极限2.50h的楼板与其他区域进行分隔",{"key":24,"text":191,"correct":22},"最远防火分区通向避难走道的门至该避难走道最近直通地面的出口的距离为39m",{"key":28,"text":193,"correct":22},"使用人数最多的防火分区通向与其连接的避难走道的2个门净宽度均为1.6m，避难走道的净宽度为3.50m",{"key":31,"text":195,"correct":26},"防火分区开向避难走道前室的门采用乙级防火门，前室开向避难走道的门采用甲级防火门",{"id":197,"libraryId":5,"type":40,"typeLabel":41,"stem":198,"options":199,"answer":31,"analysis":37},934838,"(2017年真题)对某医院的高层病房楼进行防火检查时，发现下列关于避难间的做法中，错误的是（??）",[200,202,204,206],{"key":20,"text":201,"correct":22},"在二层及以上的病房楼层设置避难间",{"key":24,"text":203,"correct":22},"避难间靠近楼梯间设置，采用耐火极限为2.50h的防火隔墙和甲级防火门与其他部位隔开",{"key":28,"text":205,"correct":22},"每个避难间为2个护理单元服务",{"key":31,"text":207,"correct":26},"每个避难间的建筑面积为25m2",{"id":209,"libraryId":5,"type":40,"typeLabel":41,"stem":210,"options":211,"answer":20,"analysis":37},934839,"(2017年真题)下列疏散出口的检查结果中，不符合现行国家消防技术标准的是（??）",[212,214,216,218],{"key":20,"text":213,"correct":26},"容纳200人的观众厅，其2个外开疏散门的净宽度均为1.20m",{"key":24,"text":215,"correct":22},"教学楼内位于两个安全出口之间的建筑面积55㎡，使用人数45人的教室设有1个净宽1.00m的外开门",{"key":28,"text":217,"correct":22},"单层的棉花储备仓库在外墙上设置净宽4.00m的金属卷帘门作为疏散门",{"key":31,"text":219,"correct":22},"建筑面积为200㎡的房间，其相邻2个疏散门洞净宽为1.5m，疏散门中心线之间的距离为6.5m",{"id":221,"libraryId":5,"type":15,"typeLabel":16,"stem":222,"options":223,"answer":234,"analysis":37},934840,"(2017年真题)下列安全出口的检查结果中， 符合现行国家消防技术标准的有( )。",[224,226,228,230,232],{"key":20,"text":225,"correct":22},"防烟楼梯间在首层直接对外的出口门采用向外开启的玻璃门",{"key":24,"text":227,"correct":22},"服装厂房设置的封闭楼梯间， 各层均采用常 闭式乙级防火门，并向楼梯间开启",{"key":28,"text":229,"correct":26},"多层办公楼封闭楼梯间的入口门，采用常开的乙级防火门，并有自行关闭和信号反馈功能",{"key":31,"text":231,"correct":26},"室外 地坪标高 - 0.15m， 室内地坪标高 -10.00的地下2层建筑， 其疏散楼梯采用封闭楼梯间",{"key":34,"text":233,"correct":26},"高层宾馆中连续 “一” 字形内走廊的 2个防烟楼梯间的入口中心线之间的距离为60m","CDE",{"id":236,"libraryId":5,"type":15,"typeLabel":16,"stem":237,"options":238,"answer":249,"analysis":37},934841,"(2017年真题)对某一类高层宾馆进行防火检查，查阅资料得知，该宾馆每层划分为2个防火分区，符合规范要求， 下列检查结果中， 不符合现行国家消防技术标准的有（??）。",[239,241,243,245,247],{"key":20,"text":240,"correct":26},"消防电梯前室的建筑面积为6.0m2， 与防烟楼梯间合用前室的建筑面积为10m2",{"key":24,"text":242,"correct":26},"兼做客梯用的消防电梯，其前室门采用耐火极限满足耐火完整性和耐火隔热性判定的防火卷帘",{"key":28,"text":244,"correct":22},"设有3台消防电梯， 一个防火分区有2台， 另 一个防火分区有l台",{"key":31,"text":246,"correct":22},"消防电梯能够停靠每个楼层",{"key":34,"text":248,"correct":22},"消防电梯从首层到顶层的运行时间为 59s","AB",{"id":251,"libraryId":5,"type":40,"typeLabel":41,"stem":252,"options":253,"answer":20,"analysis":37},934842,"(2018年真题)对大型地下商业建筑进行防火检查，根据现行国家标准《建筑设计防火规范》（GB50016），（）不属于下沉式广场检查的内容。",[254,256,258,260],{"key":20,"text":255,"correct":26},"下沉式广场的自动扶梯的宽度",{"key":24,"text":257,"correct":22},"下沉式广场的实际用途",{"key":28,"text":259,"correct":22},"下沉式广场防风雨棚的开口面积",{"key":31,"text":261,"correct":22},"下沉式广场直通地面疏散楼梯的数量和宽度",{"id":263,"libraryId":5,"type":40,"typeLabel":41,"stem":264,"options":265,"answer":24,"analysis":37},934843,"(2018年真题)对某商业建筑进行防火检查，下列避难走道的检查结果中，符合现行国家标准要求的是( )",[266,268,270,272],{"key":20,"text":267,"correct":22},"防火分区通向避难走道的门至避难走道直通地面的出口的距离最远为65m",{"key":24,"text":269,"correct":26},"避难走道仅与一个防火区相通，该防火分区设有2个直通室外的安全出口，避难走道设置1个直通地面的出口",{"key":28,"text":271,"correct":22},"避难走道采用耐火极限3.00h的防火墙和耐火极限1.0h的楼板与其他区域进行分隔",{"key":31,"text":273,"correct":22},"防火分区至避难走道入口处设置防烟前室，每个前室的建筑面积为6.0㎡",{"id":275,"libraryId":5,"type":40,"typeLabel":41,"stem":276,"options":277,"answer":28,"analysis":37},934844,"(2018年真题)某 6 层建筑，建筑高度 23m，每层建筑面积 1100 ㎡，一、二层为商业店面，三层至五层为老年人照料设施，其中三层设有与疏散楼梯间直接连接的开敞式外廊，六层为办公区，对该建筑的避难间进行防火检查，下列检查结果中，不符合现行国家标准要求的是（）",[278,280,282,284],{"key":20,"text":279,"correct":22},"避难间仅设于四、五层每座疏散楼梯间的相邻部位",{"key":24,"text":281,"correct":22},"避难间可供避难的净面积为 12 ㎡",{"key":28,"text":283,"correct":26},"避难间内共设有消防应急广播、灭火器 2 种消防设施和器材",{"key":31,"text":285,"correct":22},"避难间采用耐火极限2.00h的防火隔墙和甲级防火门与其他部位分隔",{"id":287,"libraryId":5,"type":40,"typeLabel":41,"stem":288,"options":289,"answer":20,"analysis":37},934845,"(2018年真题)某7层病房大楼，建筑高度27m，每层划分2个防火分区，走道两侧双面布房，每层设计容纳人数为110人。下列对该病房大楼安全疏散设施的防火检查结果中，不符合现行国家标准要求的是()",[290,292,294,296],{"key":20,"text":291,"correct":26},"疏散走道与合用前室之间设置耐火极限3.00h且具有停止功能的防火卷帘",{"key":24,"text":293,"correct":22},"楼层水平疏散走道的净宽度为1.60m",{"key":28,"text":295,"correct":22},"疏散楼梯及首层疏散外门的净宽度均为1.30m",{"key":31,"text":297,"correct":22},"疏散走道在防火分区处设置具有自行关闭和信号反馈功能的常开甲级防火门",{"id":299,"libraryId":5,"type":15,"typeLabel":16,"stem":300,"options":301,"answer":312,"analysis":37},934846,"(2018年真题)某老年人照料设施，地上10层，建筑高度为33m，设有2部防烟楼梯间，1部消防电梯及1部客梯，防烟楼梯间前室和消防电梯前室分开设置。标准层面积为1200㎡，中间设有疏散走道，走道两侧双面布房。对该老年人照料设施进行火检查，下列检查结果中，符合现行国家标准《建筑设计防火规范》(GB50016)的有( )。",[302,304,306,308,310],{"key":20,"text":303,"correct":26},"在建筑首层设置了厨房和餐厅",{"key":24,"text":305,"correct":26},"房间疏散门的净宽度为0.90m",{"key":28,"text":307,"correct":26},"疏散走道的净宽度为1.4m",{"key":31,"text":309,"correct":26},"第四层设有建筑面积为150㎡的阅览室，最大容纳人数为20人",{"key":34,"text":311,"correct":22},"每层利用消防电梯的前室作为避难间，前室的建筑面积为12㎡","ABCD",{"id":314,"libraryId":5,"type":15,"typeLabel":16,"stem":315,"options":316,"answer":327,"analysis":37},934847,"(2018年真题)某住宅小区，均为10层住宅楼，建筑高度31m。每栋设有两个单元，每个单元标准层建筑面积为600㎡，户门均釆用乙级防火门且至最近安全出口的最大距离为12m。下列防火检查结果中，符合现行国家标准要求的有( )。",[317,319,321,323,325],{"key":20,"text":318,"correct":26},"抽查一层住宅的外窗，与楼梯间外墙上的窗口最近边缘的水平距离为1.5m",{"key":24,"text":320,"correct":26},"疏散楼梯采用敞开楼梯间",{"key":28,"text":322,"correct":26},"敞开楼梯间内局部敷设的天然气管道采用钢套管保护并设量切断气源的装置",{"key":31,"text":324,"correct":22},"每栋楼每个单元设一部疏散楼梯，单元之间的疏散楼梯可通过屋面连通",{"key":34,"text":326,"correct":22},"敞开楼梯间内设置垃圾道，垃圾道开口采用甲级防火门进行防火分隔","ABC",{"id":329,"libraryId":5,"type":40,"typeLabel":41,"stem":330,"options":331,"answer":31,"analysis":37},934848,"(2016年真题)对高层医院病房楼进行防火检查时，应注意检查避难间的设置情况。下列对某医院病房楼避难间的检查结果中，符合现行国家消防技术标准的是（??）",[332,334,336,338],{"key":20,"text":333,"correct":22},"每个避难间为3个护理单元服务",{"key":24,"text":335,"correct":22},"利用防烟楼梯间和消防电梯合用前室做避难间",{"key":28,"text":337,"correct":22},"避难间采用耐火极限不低于2.0H的防火隔墙和乙级防火门与其他部位分隔",{"key":31,"text":339,"correct":26},"在二层及以上的每个病房楼层设置避难间",{"id":341,"libraryId":5,"type":40,"typeLabel":41,"stem":342,"options":343,"answer":31,"analysis":37},934849,"(2016年真题)对某建筑高度为140m的住宅建筑进行防火检查。下列关于避难的检查结果中，不符合现行国家消防技术标准的是（??）",[344,346,348,350],{"key":20,"text":345,"correct":22},"设置了可直接对外开启的乙级防火窗",{"key":24,"text":347,"correct":22},"在避难层设置消防电梯出口",{"key":28,"text":349,"correct":22},"在避难层设置的设备用房与避难区采用防火墙分隔",{"key":31,"text":351,"correct":26},"在避难层设置消火栓，机械排烟系统和消防专用电话",{"id":353,"libraryId":5,"type":40,"typeLabel":41,"stem":354,"options":355,"answer":20,"analysis":37},934850,"（2020年真题）某建筑高度为30m的8层电信楼主楼2~8层,层高均为3.6m,每层建筑面积为2000㎡,裙房地上二层,建筑面积共1500㎡,使用功能为附属办公,办公室双面布房,与高层建筑主体之间采用防火墙分隔。下列防火检查结果中,符合现行国家标准要求的是（ ）。",[356,358,360,362],{"key":20,"text":357,"correct":26},"裙房疏散楼梯间为敞开楼梯间",{"key":24,"text":359,"correct":22},"主楼疏散楼梯间为封闭楼梯间",{"key":28,"text":361,"correct":22},"裙房内位于袋形走道尽端的房间门至最近安全出口的直线距离为35m",{"key":31,"text":363,"correct":22},"主楼内位于袋形走道尽端的房间门至最近安全出口的直线距离为26m",{"id":365,"libraryId":5,"type":40,"typeLabel":41,"stem":366,"options":367,"answer":20,"analysis":37},934851,"（2020年真题）某二级耐火等级的卷烟包装厂房，地上2层，地下1层，各层层高均为6m。地下一层采用防火墙划分为2个防火分区，每个防火分区各有1个直通室外的独立安全出口。下列防火检查结果中，不符合国家现行标准要求的是（ ）。",[368,370,372,374],{"key":20,"text":369,"correct":26},"地下—层的某点至最近安全出口的距离为40m",{"key":24,"text":371,"correct":22},"首层任—点到安全出口的最远距离为60m",{"key":28,"text":373,"correct":22},"地下—层防火分区间的防火墙上设2樘甲级防火门",{"key":31,"text":375,"correct":22},"疏散楼梯采用封闭楼梯间",{"id":377,"libraryId":5,"type":40,"typeLabel":41,"stem":378,"options":379,"answer":31,"analysis":37},934852,"（2020年真题）某小区住宅楼，1号楼建筑高度为18m，2号楼建筑高度为30m，3号楼建筑高度为90m。下列防火检查结果中，不符合现行国家标准要求的是（ ）。",[380,382,384,386],{"key":20,"text":381,"correct":22},"1号楼疏散楼梯与电梯井相邻，采用封闭楼梯间",{"key":24,"text":383,"correct":22},"2号楼有2隔单元，均采用敞开楼梯间，户门采用乙级防火门",{"key":28,"text":385,"correct":22},"3号楼有4隔单元，均采用剪刀楼梯间，户门到安全出口最远距离为10m",{"key":31,"text":387,"correct":26},"3号楼首层疏散外门的净宽度均为0.90m",{"id":389,"libraryId":5,"type":40,"typeLabel":41,"stem":390,"options":391,"answer":31,"analysis":37},934853,"（2020年真题）某多层办公楼,每层有2部散楼梯。下列防火检查结果中,不符合现行国家标准的是（ ）",[392,394,396,398],{"key":20,"text":393,"correct":22},"甲房间位于袋形走道的一侧，建筑面积60㎡，1个净宽为1.0m的疏散门",{"key":24,"text":395,"correct":22},"乙房间位于2个安全出口之间,建筑面积80㎡，设1个净宽为0.9m的疏散门",{"key":28,"text":397,"correct":22},"丙房间位于袋形走道尽端,建筑面积120㎡,房间内任一点至疏散门的最远距离为12m,设1个净宽为1.4m的疏散门",{"key":31,"text":399,"correct":26},"丁房间位于袋形走道尽端,建筑面积80㎡，设1个净宽为0.9m的疏散门",{"id":401,"libraryId":5,"type":40,"typeLabel":41,"stem":402,"options":403,"answer":20,"analysis":37},934854,"（2020年真题）对某地下商场进行防火检查时，发现有两个防火分区与避难走道连通，其中防火分区一设置两个净宽为1.4m的门通向该避难走道防烟前室。防火分区二设置一个净宽为1.40m的门通向该避难走道防烟前室，下列防火检查中符合现行国家标准的是（ ）。",[404,406,408,410],{"key":20,"text":405,"correct":26},"避难走道的净宽度为3.00m",{"key":24,"text":407,"correct":22},"避难走道入口处前室的建筑面积为6.0m2",{"key":28,"text":409,"correct":22},"商场开向避难走到前室的门为乙级防火门",{"key":31,"text":411,"correct":22},"避难走道顶棚装修材料为珍珠岩吸声板",{"id":413,"libraryId":5,"type":40,"typeLabel":41,"stem":414,"options":415,"answer":28,"analysis":37},934855,"（2020年真题）某二级耐火等级的多层综合楼，一层为商店，二层为餐厅，三层为影院，四层为宾馆。二层最大使用人数为240人。三四层每层最大使用人数均为200人。该建筑设有三部疏散楼梯，其中一部为电影院独立使用的室外疏散楼梯，下列防火检查结果中不符合现行国家标准要求的是（ ）.",[416,418,420,422],{"key":20,"text":417,"correct":22},"室内疏散楼梯梯段净宽度均为1.10m，室外疏散楼梯梯段净宽为0.90m",{"key":24,"text":419,"correct":22},"4层宾馆双面布防疏散走道径宽为1.40m",{"key":28,"text":421,"correct":26},"3层电影院1号观众厅设有100个座位，厅内边走道净宽为0.8m",{"key":31,"text":423,"correct":22},"室外疏散通道的净宽为4.00m，并直接通向广场",{"id":425,"libraryId":5,"type":40,"typeLabel":41,"stem":426,"options":427,"answer":28,"analysis":37},934856,"（2019年真题）对某乙炔站的供配电系统进行防火检查，下列检査结果中，不符合现行国家标准要求的是（）。",[428,430,432,434],{"key":20,"text":429,"correct":22},"导线选用了截面积为2m㎡的铜芯绝缘导线",{"key":24,"text":431,"correct":22},"电气线路采用电缆桥架架空敷设",{"key":28,"text":433,"correct":26},"绝缘导线的允许载流量是熔断器额定电流的1.2倍",{"key":31,"text":435,"correct":22},"电缆内部的导线为绞线，终端采用定型端子连接",{"id":437,"libraryId":5,"type":40,"typeLabel":41,"stem":438,"options":439,"answer":28,"analysis":37},934857,"（2019年真题）对某服装厂的仓库进行电气防火检查，下列检查结果中，符合现行国家标准《建筑设计防火规范》(GB50016)要求的是（）。",[440,442,444,446],{"key":20,"text":441,"correct":22},"仓库采用卤钨灯照明",{"key":24,"text":443,"correct":22},"额定功率为10w的照明灯的引入线采用阻燃材料做隔热保护",{"key":28,"text":445,"correct":26},"照明配电箱设置在仓库门口外墙上",{"key":31,"text":447,"correct":22},"仓库门口内墙上设置照明开关",{"id":449,"libraryId":5,"type":40,"typeLabel":41,"stem":450,"options":451,"answer":24,"analysis":37},934858,"（2019年真题）对某植物油加工厂房的浸出车间进行防火检查，下列对通风系统检查的结果中，不符合现行国家标准要求的是（）。",[452,454,456,458],{"key":20,"text":453,"correct":22},"送风机采用普通型的通风设备，布置在单独分隔的通风机房内，送风干管上设置了防止回流设施",{"key":24,"text":455,"correct":26},"排风管道穿过防火墙时两侧均设置防火阀",{"key":28,"text":457,"correct":22},"排风系统采用了导除静电的接地装置",{"key":31,"text":459,"correct":22},"排风机采用防爆型设备",{"id":461,"libraryId":5,"type":15,"typeLabel":16,"stem":462,"options":463,"answer":474,"analysis":37},934859,"（2019年真题）对某活性炭制造厂房进行防火防爆检查，下列检查结果中，符合现行国家标准要求的有（）",[464,466,468,470,472],{"key":20,"text":465,"correct":26},"厂房采用水泥地面",{"key":24,"text":467,"correct":22},"地沟中积聚的粉尘未清理",{"key":28,"text":469,"correct":26},"在厂房内设置的排污地沟，盖板严密",{"key":31,"text":471,"correct":22},"采暖设施采用肋片式散热器",{"key":34,"text":473,"correct":26},"墙面采取了防静电措施","ACE",{"id":476,"libraryId":5,"type":15,"typeLabel":16,"stem":477,"options":478,"answer":312,"analysis":37},934860,"(2017年真题) 某设计院对有爆炸危险的甲类厂房进行设计，下列防爆设计方案中，符合现行国家标准《建筑设计防火规范》(GB50016-2014)的有（??）。",[479,481,483,485,487],{"key":20,"text":480,"correct":26},"厂房承重结构采用钢筋混凝土结构",{"key":24,"text":482,"correct":26},"厂房的总控制室独立设置",{"key":28,"text":484,"correct":26},"厂房的地面采用不发火花地面",{"key":31,"text":486,"correct":26},"厂房的分控制室贴邻厂房外墙设置，并采用耐火极限不低于3.00h的防火隔墙与其他部位分离",{"key":34,"text":488,"correct":22},"厂房利用门窗作为泄压设施，窗玻璃采用普通玻璃",{"id":490,"libraryId":5,"type":40,"typeLabel":41,"stem":491,"options":492,"answer":31,"analysis":37},934861,"(2018年真题) 对某煤粉生产车间进行防火防爆检查，下列检查结果中，不符合现行国家标准要求的是( )。",[493,495,497,499],{"key":20,"text":494,"correct":22},"车间排风系统设置了导除静电的接地装置",{"key":24,"text":496,"correct":22},"排风管采用明敷的金属管道，并直接通向室外安全地点",{"key":28,"text":498,"correct":22},"送风系统采用了防爆型的通风设备",{"key":31,"text":500,"correct":26},"净化粉尘的干式除尘器和过滤器布置在系统的正压段上，且设置了泄压装置",{"id":502,"libraryId":5,"type":15,"typeLabel":16,"stem":503,"options":504,"answer":515,"analysis":37},934862,"(2018年真题) 对某桶装煤油仓库开展防火检查，查阅资料得知，该仓库屋面板设计为泄压面。下列检查结果中，符合现行国家标准要求的有( )",[505,507,509,511,513],{"key":20,"text":506,"correct":26},"在仓库门洞处修筑了高为200mm的漫坡",{"key":24,"text":508,"correct":22},"仓库照明设备采用了普通LED灯",{"key":28,"text":510,"correct":26},"采用55kg\u002F㎡的材料作为屋面板",{"key":31,"text":512,"correct":26},"屋面板采取了防冰雪积聚措施",{"key":34,"text":514,"correct":22},"外墙窗户采用钢化玻璃","ACD",{"id":517,"libraryId":5,"type":40,"typeLabel":41,"stem":518,"options":519,"answer":28,"analysis":37},934863,"(2018年真题) 根据《爆炸危险环境电力装置设计规范》(GB50058)，某面粉加工厂选择面粉碾磨车间的电气设备时，不需要考虑的因素是()。",[520,522,524,526],{"key":20,"text":521,"correct":22},"爆炸危险区域的分区",{"key":24,"text":523,"correct":22},"可燃性物质和可燃性粉尘的分级",{"key":28,"text":525,"correct":26},"可燃性物质和可燃性粉尘的物质总量",{"key":31,"text":527,"correct":22},"可燃性粉尘云、可燃性粉尘层的最低引燃温度",{"id":529,"libraryId":5,"type":40,"typeLabel":41,"stem":530,"options":531,"answer":20,"analysis":37},934864,"(2016年真题) 有爆炸危险区域内的楼梯间、室外楼梯或有爆炸危险的区域与相邻区域连通处，应设置门斗等防护措施。下列门斗的做法中，符合现行国家消防技术标准规定的是（??）。",[532,534,536,538],{"key":20,"text":533,"correct":26},"门斗隔墙的耐火极限为2.0h，门采用甲级防火门且与楼梯间门错位",{"key":24,"text":535,"correct":22},"门斗隔墙的耐火极限为1.5h，门采用甲级防火门且与楼梯间门正对",{"key":28,"text":537,"correct":22},"门斗隔墙的耐火极限为2.0h，门采用乙级防火门且与楼梯间门正对",{"key":31,"text":539,"correct":22},"门斗隔墙的耐火极限为2.5h，门采用乙级防火门且与楼梯间门错位",{"id":541,"libraryId":5,"type":40,"typeLabel":41,"stem":542,"options":543,"answer":31,"analysis":37},934865,"(2016年真题) 根据现行国家消防技术标准，下列净化或输送有爆炸危险粉尘和碎屑的设施上，不需要设置泄 压装置的是（??）。",[544,546,548,550],{"key":20,"text":545,"correct":22},"除尘器",{"key":24,"text":547,"correct":22},"过滤器",{"key":28,"text":549,"correct":22},"管道",{"key":31,"text":551,"correct":26},"风机",{"id":553,"libraryId":5,"type":15,"typeLabel":16,"stem":554,"options":555,"answer":515,"analysis":37},934866,"(2016年真题)在对易燃易爆危险环境进行防火检查时，应注意检查电气设备和电缆电线的选型及其安装情况，下列做法中，符合现行国家消防技术标准要求的有（??）",[556,558,560,562,564],{"key":20,"text":557,"correct":26},"在爆炸性气体混合物级别为IIA级的爆炸性气体环境，选用IIB级别的防爆电器设备",{"key":24,"text":559,"correct":22},"在爆炸危险区域为I区的爆炸性环境采用截面积为20m㎡的铜芯照明电缆",{"key":28,"text":561,"correct":26},"安装的正压型电器设备与通风系统连锁",{"key":31,"text":563,"correct":26},"电气设备房间与爆炸性环境想通，采取对爆炸性环境保持相对正压的措施",{"key":34,"text":565,"correct":22},"在爆炸危险区域不同的方向，接地干线有1处于接地体连接",{"id":567,"libraryId":5,"type":40,"typeLabel":41,"stem":568,"options":569,"answer":28,"analysis":37},934867,"(2017年真题)某氯酸钾厂房通风、空调系统的下列做法中，不符合现行国家消防技术标准的是（ ）",[570,572,574,576],{"key":20,"text":571,"correct":22},"通风设施设置导除静电的接地装置",{"key":24,"text":573,"correct":22},"排风系统采用防爆型通风设备",{"key":28,"text":575,"correct":26},"厂房内的空气在循环使用前经过净化处理，并使空气中的含尘浓度低于其爆炸下限的25%",{"key":31,"text":577,"correct":22},"厂房内选用不产生火花的除尘器",{"id":579,"libraryId":5,"type":40,"typeLabel":41,"stem":580,"options":581,"answer":24,"analysis":37},934868,"(2017年真题)下列甲醇生产车间内电缆、导线的选型及敷设的做法中，不符合现行国家消防技术标准要求的是（??）",[582,584,586,588],{"key":20,"text":583,"correct":22},"低压电力线路绝缘导线的额定电压等于工作电压",{"key":24,"text":585,"correct":26},"在1区内的供电线路采用铝芯电缆",{"key":28,"text":587,"correct":22},"接线箱内的供配电线路采用无护套的电线",{"key":31,"text":589,"correct":22},"电气线路在较高处敷设",{"id":591,"libraryId":5,"type":40,"typeLabel":41,"stem":592,"options":593,"answer":31,"analysis":37},934869,"(2017年真题)某金属元件抛光车间的下列做法中， 不符合规范要求的是（??）",[594,596,598,600],{"key":20,"text":595,"correct":22},"采用铜芯绝缘导线做配线",{"key":24,"text":597,"correct":22},"导线的连接采用压接方式",{"key":28,"text":599,"correct":22},"带电部件的接地干线有两处与接地体相连",{"key":31,"text":601,"correct":26},"电气设备按潮湿环境选用",{"id":603,"libraryId":5,"type":40,"typeLabel":41,"stem":604,"options":605,"answer":24,"analysis":37},934870,"（2019年真题）某建为26m的商业综合体,设有火灾自动报警系统和自动喷水灭火系统。对位于地上三层的卡OK厅的室内装修工程进行验收,下列验收检查结果中,不符合现行国家标准要求的是（）",[606,608,610,612],{"key":20,"text":607,"correct":22},"采用金属复合板",{"key":24,"text":609,"correct":26},"沙发采用实木布艺材料制",{"key":28,"text":611,"correct":22},"墙面采用珍珠岩装饰吸声板",{"key":31,"text":613,"correct":22},"地面采用氯丁橡胶地板",{"id":615,"libraryId":5,"type":40,"typeLabel":41,"stem":616,"options":617,"answer":24,"analysis":37},934871,"（2019年真题）对某28层酒店的消防控制室的室内装修工程进行防火检查。下列检查结果中，不符合现行国家标准要求的是（）",[618,620,622,624],{"key":20,"text":619,"correct":22},"顶棚采用硅酸钙板",{"key":24,"text":621,"correct":26},"墙面采用矿棉板",{"key":28,"text":623,"correct":22},"地面采用水泥刨花板",{"key":31,"text":625,"correct":22},"窗帘采用未经阻燃处理的难燃织物",{"id":627,"libraryId":5,"type":40,"typeLabel":41,"stem":628,"options":629,"answer":31,"analysis":37},934872,"（2019年真题）某3层养老院，设有自动喷水灭火系统和火灾自动报警系统，对其内装修工程进行验收，下列验收检查结果中，不符合现行国家标准要求的是（）。",[630,632,634,636],{"key":20,"text":631,"correct":22},"顶棚采用轻钢龙骨纸面石膏板",{"key":24,"text":633,"correct":22},"地面采用PVC卷材地板",{"key":28,"text":635,"correct":22},"窗帘采用纯棉装饰布",{"key":31,"text":637,"correct":26},"墙面采用印刷木纹人造板",{"id":639,"libraryId":5,"type":40,"typeLabel":41,"stem":640,"options":641,"answer":31,"analysis":37},934873,"（2019年真题）对某24层住宅建筑进行屋面和外墙外保温系统施工，保温材料均采用B1级材料，该建筑外墙外保温的防火措施中，不符合现行国家标准要求的是（）。",[642,644,646,648],{"key":20,"text":643,"correct":22},"在外墙外保温系统中每层采用不燃材料设置高度为300m的水平防火隔离带",{"key":24,"text":645,"correct":22},"建筑外墙上窗的耐火完整性为0.50h",{"key":28,"text":647,"correct":22},"外墙外保温系统首层采用厚度为15mm的不燃材料作为防火层",{"key":31,"text":649,"correct":26},"屋面与外墙之间采用不燃材料设置宽度为300mm的防火隔离带",{"id":651,"libraryId":5,"type":15,"typeLabel":16,"stem":652,"options":653,"answer":93,"analysis":37},934874,"（2019年真题）某大型地下商场内装修工程进行工程验收，该商场设有自动喷水灭火系统和火灾自动报警系统。下列验收检查结果中，符合现行国家标准要求的有（）",[654,656,658,660,662],{"key":20,"text":655,"correct":22},"疏散楼梯间前室墙面设置灯箱广告",{"key":24,"text":657,"correct":26},"疏散走道的地面采用仿古瓷砖",{"key":28,"text":659,"correct":22},"营业厅地面采用水泥木丝板",{"key":31,"text":661,"correct":26},"疏散楼梯间的地面采用水磨石",{"key":34,"text":663,"correct":26},"消防水泵房、空调机房地面采用水泥地面",[665,668,671,674,677,680],{"id":40,"name":666,"category":7,"favorite":667},"领导干部任职前廉政法规知识测试题",92,{"id":669,"name":670,"category":7,"favorite":40},595,"建筑结构与设备",{"id":672,"name":673,"category":7,"favorite":40},715,"招标采购专业知识与法律法规",{"id":675,"name":676,"category":7,"favorite":40},848,"市政方向-通用基础",{"id":678,"name":679,"category":7,"favorite":8},534,"BIM工程师",{"id":681,"name":679,"category":7,"favorite":8},535]