[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-605-34":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":621},{"id":5,"name":6,"category":7,"favorite":8},605,"消防技术综合能力(一级、二级)","建筑工程",0,34,50,2974,[13,34,46,58,70,82,94,105,117,129,147,162,173,185,197,209,221,231,243,255,267,279,291,300,315,329,340,352,364,376,387,397,405,414,426,438,450,462,474,489,501,513,525,540,552,561,573,585,597,609],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":30,"analysis":33},936342,1,"单选题","某消防技术服务机构对某商场内的消防供配电系统进行检查，发现下列情况，其中不符合消防技术标准的是（ ）。",[19,23,26,29],{"key":20,"text":21,"correct":22},"A","建筑物内设有变电所，消防配电系统在变电所处开始自成系统",false,{"key":24,"text":25,"correct":22},"B","在防烟和排烟风机配电线路的最末一级配电箱处设置自动切换装置",{"key":27,"text":28,"correct":22},"C","采用柴油发电机组作为备用电源，柴油发电机组设置自动和手动启动装置",{"key":30,"text":31,"correct":32},"D","消防配电线路采用有机绝缘耐火电缆，在电气竖井内与非消防配电线路同束敷设",true,"",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":24,"analysis":33},936343,"下列关于供配电系统设置的要求描述中,不正确的是（ ）。",[38,40,42,44],{"key":20,"text":39,"correct":22},"消防用电设备的供配电系统应作为独立系统进行设置",{"key":24,"text":41,"correct":32},"消防用电设备配电装置不应设置在建筑物的电源进线处或配变电所处",{"key":27,"text":43,"correct":22},"消防负荷按一、二级负荷供电的建筑,自备发电设备作为备用电源时,应设置自动和手动启动装置。当采用自动启动方式时,应能保证在 30s 内供电",{"key":30,"text":45,"correct":22},"消防控制室、消防水泵房、防烟和排烟风的用电设备及消防电梯等的供电设备,应在其配电线路的最末一级配电箱处设置自动切换装置",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":20,"analysis":33},936344,"消防用电设备的供电线路采用不同的电线电缆时，供电线路的敷设方式也不同，当敷设方式采用直接明敷时，应优先选用的电缆是（ ）。",[50,52,54,56],{"key":20,"text":51,"correct":32},"矿物绝缘电缆",{"key":24,"text":53,"correct":22},"难燃性电缆",{"key":27,"text":55,"correct":22},"有机绝缘耐火电缆",{"key":30,"text":57,"correct":22},"阻燃电线电缆",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":20,"analysis":33},936345,"某办公大楼建筑高度69m，大楼采用柴油发电机作为备用电源，市政供电中断时柴油发电机自动启动。当市政供电中断时，自备发电机的启动时间不符合规范要求的是（ ）。",[62,64,66,68],{"key":20,"text":63,"correct":32},"35s",{"key":24,"text":65,"correct":22},"15s",{"key":27,"text":67,"correct":22},"20s",{"key":30,"text":69,"correct":22},"25s",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":27,"analysis":33},936346,"室外变、配电装置距液化石油气罐不应小于（ ）m。",[74,76,78,80],{"key":20,"text":75,"correct":22},"10",{"key":24,"text":77,"correct":22},"25",{"key":27,"text":79,"correct":32},"35",{"key":30,"text":81,"correct":22},"40",{"id":83,"libraryId":5,"type":15,"typeLabel":16,"stem":84,"options":85,"answer":24,"analysis":33},936347,"电动机应安装在牢固的机座上，机座周围应有适当的通道，与其它低压带电体、可燃物之间的距离不应小于（ ）m。",[86,88,90,92],{"key":20,"text":87,"correct":22},"0．5",{"key":24,"text":89,"correct":32},"1．0",{"key":27,"text":91,"correct":22},"1．5",{"key":30,"text":93,"correct":22},"2．0",{"id":95,"libraryId":5,"type":15,"typeLabel":16,"stem":96,"options":97,"answer":20,"analysis":33},936348,"消防用电设备供配电系统启动装置要求，当消防用电负荷为一级时，应在主电源断电后（ ）s内供电。",[98,100,101,103],{"key":20,"text":99,"correct":32},"30",{"key":24,"text":81,"correct":22},{"key":27,"text":102,"correct":22},"50",{"key":30,"text":104,"correct":22},"60",{"id":106,"libraryId":5,"type":15,"typeLabel":16,"stem":107,"options":108,"answer":30,"analysis":33},936349,"下列关于插座安装的说法，正确的是（ ）。",[109,111,113,115],{"key":20,"text":110,"correct":22},"单相两孔插座，面对插座的上孔与零线连接",{"key":24,"text":112,"correct":22},"单相两孔插座，面对插座的左孔与相线连接",{"key":27,"text":114,"correct":22},"三孔插座，面对插座的右孔与零线连接",{"key":30,"text":116,"correct":32},"单相两孔插座，面对插座的下孔与零线连接",{"id":118,"libraryId":5,"type":15,"typeLabel":16,"stem":119,"options":120,"answer":27,"analysis":33},936350,"下列关于消防用电设备供电线路敷设要求的说法中，错误的是（ ）。",[121,123,125,127],{"key":20,"text":122,"correct":22},"采用矿物绝缘电缆时，可直接采用明敷设或在吊顶内敷设",{"key":24,"text":124,"correct":22},"采用难燃性电缆时，在电缆沟内敷设可不穿导管保护，应采取与非消防用电缆隔离的措施",{"key":27,"text":126,"correct":32},"采用有机绝缘耐火电缆时，在电气竖井内敷设必须穿导管保护",{"key":30,"text":128,"correct":22},"线路暗敷设时，要敷设在不燃烧结构内，保护层厚度应不小于30mm",{"id":130,"libraryId":5,"type":131,"typeLabel":132,"stem":133,"options":134,"answer":146,"analysis":33},936351,2,"多选题","嵌入式灯具采用卤钨灯时，下列关于引入线的做法符合规定的是（ ）。",[135,137,139,141,143],{"key":20,"text":136,"correct":32},"采用耐150℃高温的绝缘电线",{"key":24,"text":138,"correct":32},"引入线采用瓷管作隔热保护",{"key":27,"text":140,"correct":32},"引入线采用石棉作隔热保护",{"key":30,"text":142,"correct":22},"采用耐100℃高温的绝缘电线",{"key":144,"text":145,"correct":32},"E","采用耐120℃高温的绝缘电线","ABCE",{"id":148,"libraryId":5,"type":131,"typeLabel":132,"stem":149,"options":150,"answer":161,"analysis":33},936352,"下列灯具中，不应安装在可燃材料或可燃构件上的是（ ）。",[151,153,155,157,159],{"key":20,"text":152,"correct":32},"1kW的卤素灯",{"key":24,"text":154,"correct":32},"300W的荧光高压汞灯",{"key":27,"text":156,"correct":22},"50W的白炽灯",{"key":30,"text":158,"correct":32},"100W的白炽灯",{"key":144,"text":160,"correct":22},"60W的白炽灯","ABD",{"id":163,"libraryId":5,"type":15,"typeLabel":16,"stem":164,"options":165,"answer":24,"analysis":33},936353,"在潮湿场所应采用密封型并带保护地线触头的保护型插座，安装高度不低于（ ）m。",[166,168,169,171],{"key":20,"text":167,"correct":22},"1．6",{"key":24,"text":91,"correct":32},{"key":27,"text":170,"correct":22},"1．4",{"key":30,"text":172,"correct":22},"1．3",{"id":174,"libraryId":5,"type":15,"typeLabel":16,"stem":175,"options":176,"answer":24,"analysis":33},936354,"对建筑物进行防火检查时，应注意检查建筑物的消防用电负荷设置的合理性。下列建筑中，消防用电可按二级负荷供电的是（）。",[177,179,181,183],{"key":20,"text":178,"correct":22},"建筑高度36m的省级广播电视中心",{"key":24,"text":180,"correct":32},"粮食仓库及粮食筒仓",{"key":27,"text":182,"correct":22},"建筑高度54m的乙、丙类厂房",{"key":30,"text":184,"correct":22},"建筑高度30m的住院楼",{"id":186,"libraryId":5,"type":15,"typeLabel":16,"stem":187,"options":188,"answer":20,"analysis":33},936355,"根据爆炸危险环境电缆的配线技术要求，爆炸性气体环境为1级区域的场所内控制导线应采用铜芯电缆，其最小截面不应小于（ ）mm2。",[189,191,193,195],{"key":20,"text":190,"correct":32},"1.0",{"key":24,"text":192,"correct":22},"1.5",{"key":27,"text":194,"correct":22},"2.0",{"key":30,"text":196,"correct":22},"2.5",{"id":198,"libraryId":5,"type":15,"typeLabel":16,"stem":199,"options":200,"answer":30,"analysis":33},936356,"某综合楼，建筑高度为58m，设有室内消火栓，自动喷水灭火系统，防烟排烟系统、火灾自动报警系统。建筑内采用一路市政电源供电，柴油发电设备作为备用电源，下列关于各消防用电设备电源自动切换装置的做法中，不合理的是（ ）。",[201,203,205,207],{"key":20,"text":202,"correct":22},"消防水泵的电源自动切换装置设在消防水泵房配电箱内",{"key":24,"text":204,"correct":22},"排烟风机的电源自动切换装置设在排烟风机机房的风机配电箱内",{"key":27,"text":206,"correct":22},"防烟风机的电源自动切换装置设在其配电线路的最末一级配电箱处",{"key":30,"text":208,"correct":32},"消防电梯的电源自动切换装置设在消防控制室内",{"id":210,"libraryId":5,"type":15,"typeLabel":16,"stem":211,"options":212,"answer":27,"analysis":33},936357,"消防电源在火灾时要持续为消防设备供电，为防止火灾通过消防用电设备供电线路蔓延，应对消防用电设备供电线路采取防火封堵措施。在对防火封堵部位进行检查时，下列情况，不需要采取防火封堵措施的是（ ）。",[213,215,217,219],{"key":20,"text":214,"correct":22},"穿越不同的防火分区处",{"key":24,"text":216,"correct":22},"沿竖井垂直敷设穿越楼板处",{"key":27,"text":218,"correct":32},"电缆桥架转弯处",{"key":30,"text":220,"correct":22},"穿越建筑物的外墙处",{"id":222,"libraryId":5,"type":15,"typeLabel":16,"stem":223,"options":224,"answer":30,"analysis":33},936358,"消防配电线路应满足火灾时连续供电的需要，暗敷时，应穿管并应敷设在不燃性结构内且保护层厚度不应小于（ ）mm。",[225,227,228,230],{"key":20,"text":226,"correct":22},"5",{"key":24,"text":75,"correct":22},{"key":27,"text":229,"correct":22},"20",{"key":30,"text":99,"correct":32},{"id":232,"libraryId":5,"type":15,"typeLabel":16,"stem":233,"options":234,"answer":27,"analysis":33},936359,"下列关于电热器防火措施的说法中，错误的是（ ）。",[235,237,239,241],{"key":20,"text":236,"correct":22},"超过3kW的固定式电热器具应采用单独回路供电，电源线应装设短路、过载及接地故障保护电器",{"key":24,"text":238,"correct":22},"低于3kW以下可移动式电热器应放在不燃材料制作的工作台上，与周围可燃物应保持0．3m以上的距离",{"key":27,"text":240,"correct":32},"5kW的固定式电热器具周围0．3m以内不应放置可燃物",{"key":30,"text":242,"correct":22},"低于3kW以下可移动式电热器引出线应采用石棉、瓷管等耐高温绝缘套管保护",{"id":244,"libraryId":5,"type":15,"typeLabel":16,"stem":245,"options":246,"answer":24,"analysis":33},936360,"某消防检测机构检查物业公司的临时高压消防给水系统维护管理记录时，发现有一条维护管理记录如下：自动和手动启动消防水泵时，水泵无法实现运转，按下控制柜的机械应急启动操作杆时，水泵能正常运转。下列关于系统故障原因的分析中，正确的是（ ）。",[247,249,251,253],{"key":20,"text":248,"correct":22},"自动巡检变频器故障",{"key":24,"text":250,"correct":32},"控制电器元件故障",{"key":27,"text":252,"correct":22},"电机供电回路故障",{"key":30,"text":254,"correct":22},"供电电压不足",{"id":256,"libraryId":5,"type":15,"typeLabel":16,"stem":257,"options":258,"answer":30,"analysis":33},936361,"变、配电站（室）是工业企业的动力枢纽，电气设备较多，而且有些设备工作时会产生火花和高温，下列关于某化工厂变、配电站的布置的检查结果，符合规范的是（ ）。",[259,261,263,265],{"key":20,"text":260,"correct":22},"室外变、配电装置距甲醇液体储罐20m",{"key":24,"text":262,"correct":22},"室外变、配电装置距油布仓库20m",{"key":27,"text":264,"correct":22},"室外变、配电装置距硝化棉厂房20m",{"key":30,"text":266,"correct":32},"室外变、配电装置距液化石油气储罐40m",{"id":268,"libraryId":5,"type":15,"typeLabel":16,"stem":269,"options":270,"answer":27,"analysis":33},936362,"用电设施安装不规范是引发电器火灾的重要因素之一。下列用电设施的安装方案中，错误的是（ ）。",[271,273,275,277],{"key":20,"text":272,"correct":22},"单相两孔插座，面对插座的右孔或上孔与相线连接",{"key":24,"text":274,"correct":22},"空调器具安装在不燃结构上，与周围可燃物的距离大于0．3m",{"key":27,"text":276,"correct":32},"彩灯连接线路采用截面积为2mm2的绝缘铜导线",{"key":30,"text":278,"correct":22},"嵌入顶棚内的卤钨灯的绝缘电线采用瓷管作隔热保护",{"id":280,"libraryId":5,"type":15,"typeLabel":16,"stem":281,"options":282,"answer":27,"analysis":33},936363,"电气线路一旦长时间过负荷使用会发热，从而增加发生电气火灾的风险。以下不属于预防电气线路过负荷措施的是（ ）。",[283,285,287,289],{"key":20,"text":284,"correct":22},"严禁滥用铜丝、铁丝代替熔断器的熔丝",{"key":24,"text":286,"correct":22},"根据负载情况，选择合适的电线",{"key":27,"text":288,"correct":32},"铜线接头处搪锡",{"key":30,"text":290,"correct":22},"根据生产需要，错峰启动用电设备",{"id":292,"libraryId":5,"type":15,"typeLabel":16,"stem":293,"options":294,"answer":30,"analysis":33},936364,"当消防配电线路暗敷设时，要穿金属导管或难燃性刚性塑料导管进行保护，并要敷设在不燃烧结构内，保护层厚度应不小于（ ）mm。",[295,296,298,299],{"key":20,"text":75,"correct":22},{"key":24,"text":297,"correct":22},"15",{"key":27,"text":229,"correct":22},{"key":30,"text":99,"correct":32},{"id":301,"libraryId":5,"type":131,"typeLabel":132,"stem":302,"options":303,"answer":314,"analysis":33},936365,"节日彩灯的检查应符合（ ）的规定。",[304,306,308,310,312],{"key":20,"text":305,"correct":32},"建筑物顶部彩灯采用有防雨性能的专用灯具，灯罩要拧紧",{"key":24,"text":307,"correct":22},"彩灯连接线路应采用绝缘铜导线，导线截面面积应满足载流量要求，且不应小于3．5mm2，灯头线不应小于1．0mm",{"key":27,"text":309,"correct":32},"悬挂式彩灯应采用防水吊线灯头，灯头线与干线的连接应牢固并绝缘包扎紧密",{"key":30,"text":311,"correct":22},"彩灯供电线路应采用橡胶多股铜芯软导线，截面面积不应小于5．0mm2，垂直敷设时，对地面的距离不小于4．0m",{"key":144,"text":313,"correct":32},"彩灯的电源除统一控制外，每个支路应有单独控制开关和熔断器保护，导线的支持物应安装牢固","ACE",{"id":316,"libraryId":5,"type":131,"typeLabel":132,"stem":317,"options":318,"answer":328,"analysis":33},936366,"消防用电设备供电线路在电缆隧道、电缆桥架、电缆竖井、封闭式母线、线槽安装等处时，在下列情况下应采取防火封堵措施（ ）。",[319,321,323,324,326],{"key":20,"text":320,"correct":22},"穿越建筑物的内墙处",{"key":24,"text":322,"correct":32},"穿越不同的防火分区",{"key":27,"text":216,"correct":32},{"key":30,"text":325,"correct":32},"管线进出竖井处",{"key":144,"text":327,"correct":32},"电缆隧道、电缆沟、电缆间的隔墙处","BCDE",{"id":330,"libraryId":5,"type":15,"typeLabel":16,"stem":331,"options":332,"answer":27,"analysis":33},936367,"集中电源、应急照明配电箱配接的所有非持续型照明灯的光源应应急点亮，持续型灯具的光源应由节电点亮模式转入应急点亮模式;灯具持续应急点亮时间应符合设计文件的规定，且不应大于（ ）h。",[333,335,337,339],{"key":20,"text":334,"correct":22},"1",{"key":24,"text":336,"correct":22},"2",{"key":27,"text":338,"correct":32},"0.5",{"key":30,"text":192,"correct":22},{"id":341,"libraryId":5,"type":15,"typeLabel":16,"stem":342,"options":343,"answer":24,"analysis":33},936368,"在安装消防应急照明和疏散指示系统时，电线电缆选择和线路敷设安装不正确的是（ ）。",[344,346,348,350],{"key":20,"text":345,"correct":22},"潮湿场所安装时，灯具的供电线路和控制线路，均应选择耐腐蚀的橡胶电缆，接线处应有防腐蚀和防潮处理",{"key":24,"text":347,"correct":32},"应急照明分配电装置的输出线路和集中控制型系统的控制线路选择燃烧性能等级为B1级的电线电缆时，不能敷设在燃烧性能为同级别的电缆桥架或线槽中。",{"key":27,"text":349,"correct":22},"应急照明分配电装置的输出线路和集中控制型系统的控制线路选择燃烧性能等级为A级的电线电缆时，可明敷",{"key":30,"text":351,"correct":22},"系统的配电支线应采用铜芯导线，控制线路应采用多股铜芯导线",{"id":353,"libraryId":5,"type":15,"typeLabel":16,"stem":354,"options":355,"answer":30,"analysis":33},936369,"关于某场所设置的应急照明配电箱检查结果中，不符合规范要求的是（ ）。",[356,358,360,362],{"key":20,"text":357,"correct":22},"宜设置在值班室、设备机房、配电间或电气竖井内",{"key":24,"text":359,"correct":22},"人员密集场所，每个防火分区应设置独立的应急照明配电箱",{"key":27,"text":361,"correct":22},"A型应急照明配电箱的输出回路不应超过8路",{"key":30,"text":363,"correct":32},"B型应急照明配电箱的输出回路不应超过60路。",{"id":365,"libraryId":5,"type":15,"typeLabel":16,"stem":366,"options":367,"answer":20,"analysis":33},936370,"某消防应急照明灯具上的红色指示灯亮起，表示灯具处于（ ）状态。",[368,370,372,374],{"key":20,"text":369,"correct":32},"充电",{"key":24,"text":371,"correct":22},"故障",{"key":27,"text":373,"correct":22},"主电",{"key":30,"text":375,"correct":22},"自检",{"id":377,"libraryId":5,"type":15,"typeLabel":16,"stem":378,"options":379,"answer":30,"analysis":33},936371,"应急照明配电箱及应急照明分配电装置的输出回路不应超过（ ）路。",[380,381,383,385],{"key":20,"text":226,"correct":22},{"key":24,"text":382,"correct":22},"6",{"key":27,"text":384,"correct":22},"7",{"key":30,"text":386,"correct":32},"8",{"id":388,"libraryId":5,"type":15,"typeLabel":16,"stem":389,"options":390,"answer":24,"analysis":33},936372,"在对消防应急照明和疏散指示标志进行调试时，逐个切断各区域应急照明配电箱或应急照明集中电源的分配电装置，该配电箱或分配电装置供电的消防应急灯具应在（ ）s内转入应急工作状态。",[391,393,394,396],{"key":20,"text":392,"correct":22},"0．25",{"key":24,"text":226,"correct":32},{"key":27,"text":395,"correct":22},"3",{"key":30,"text":75,"correct":22},{"id":398,"libraryId":5,"type":15,"typeLabel":16,"stem":399,"options":400,"answer":27,"analysis":33},936373,"对应急照明控制器进行检测时，应急照明控制器应有主、备用电源的工作状态指示，并能实现主、备用电源的自动转换。且备用电源应能保证应急照明控制器正常工作（ ）h。",[401,402,403,404],{"key":20,"text":334,"correct":22},{"key":24,"text":226,"correct":22},{"key":27,"text":395,"correct":32},{"key":30,"text":382,"correct":22},{"id":406,"libraryId":5,"type":15,"typeLabel":16,"stem":407,"options":408,"answer":20,"analysis":33},936374,"某自带电源型应急照明灯具的绿色指示灯亮起，代表该应急照明灯具处于（ ）状态。",[409,410,411,412],{"key":20,"text":373,"correct":32},{"key":24,"text":371,"correct":22},{"key":27,"text":369,"correct":22},{"key":30,"text":413,"correct":22},"应急",{"id":415,"libraryId":5,"type":15,"typeLabel":16,"stem":416,"options":417,"answer":30,"analysis":33},936375,"由应急照明控制器、应急照明集中电源、应急照明分配电装置和消防应急灯具组成的系统称为（ ）。",[418,420,422,424],{"key":20,"text":419,"correct":22},"自带电源非集中控制型系统",{"key":24,"text":421,"correct":22},"自带电源集中控制型系统",{"key":27,"text":423,"correct":22},"集中电源非集中控制型系统",{"key":30,"text":425,"correct":32},"集中电源集中控制型系统",{"id":427,"libraryId":5,"type":15,"typeLabel":16,"stem":428,"options":429,"answer":24,"analysis":33},936376,"消防应急照明和疏散指示系统是用于建筑内人员安全疏散、逃生、避难和消防作业等应急行动的重要消防设施。下列不属于自带电源集中控制型系统组件的是（ ）。",[430,432,434,436],{"key":20,"text":431,"correct":22},"应急照明控制器",{"key":24,"text":433,"correct":32},"应急照明分配电装置",{"key":27,"text":435,"correct":22},"应急照明配电箱",{"key":30,"text":437,"correct":22},"消防应急灯具",{"id":439,"libraryId":5,"type":15,"typeLabel":16,"stem":440,"options":441,"answer":27,"analysis":33},936377,"下列关于消防应急灯具安装的说法中，错误的是（ ）。",[442,444,446,448],{"key":20,"text":443,"correct":22},"消防应急灯具吊装时宜使用金属吊管，吊管上端应固定在建筑物实体或构件上",{"key":24,"text":445,"correct":22},"消防应急灯具宜安装在不燃烧墙体和不燃烧装修材料上",{"key":27,"text":447,"correct":32},"消防应急灯具与供电线路之间必要时可以使用插头连接",{"key":30,"text":449,"correct":22},"消防应急照明灯具安装时，在正面迎向人员疏散方向，应有防止造成眩光的措施",{"id":451,"libraryId":5,"type":15,"typeLabel":16,"stem":452,"options":453,"answer":24,"analysis":33},936378,"消防应急标志灯具在顶部安装时，尽量不要贴顶安装，灯具上边与顶棚距离宜大于（ ）mm。",[454,456,458,460],{"key":20,"text":455,"correct":22},"100",{"key":24,"text":457,"correct":32},"200",{"key":27,"text":459,"correct":22},"300",{"key":30,"text":461,"correct":22},"400",{"id":463,"libraryId":5,"type":15,"typeLabel":16,"stem":464,"options":465,"answer":27,"analysis":33},936379,"消防配电线路应满足火灾时连续供电的需要，下列关于其敷设的说法中，错误的是（ ）。",[466,468,470,472],{"key":20,"text":467,"correct":22},"明敷时，应穿金属导管或采用封闭式金属槽盒保护",{"key":24,"text":469,"correct":22},"当采用阻燃或耐火电缆并敷设在电缆井、沟内时，可不穿金属导管或采用封闭式金属槽盒保护",{"key":27,"text":471,"correct":32},"暗敷时，应穿管并应敷设在不燃性结构内且保护层厚度不应小于25mm",{"key":30,"text":473,"correct":22},"消防配电线路宜与其他配电线路分开敷设在不同的电缆井、沟内",{"id":475,"libraryId":5,"type":131,"typeLabel":132,"stem":476,"options":477,"answer":488,"analysis":33},936380,"下列关于应急照明控制器安装的做法，正确的是（ ）。",[478,480,482,484,486],{"key":20,"text":479,"correct":32},"安装在墙上的应急照明控制器高度为1．4m",{"key":24,"text":481,"correct":32},"安装在墙上的应急照明控制器正面操作距离为1．3m",{"key":27,"text":483,"correct":32},"应急照明控制器的主电源有明显标志",{"key":30,"text":485,"correct":32},"应急照明控制器与其外接备用电源之间直接连接",{"key":144,"text":487,"correct":22},"应急照明控制器的导线，留有100mm的余量","ABCD",{"id":490,"libraryId":5,"type":15,"typeLabel":16,"stem":491,"options":492,"answer":24,"analysis":33},936381,"下列关于消防应急照明灯具与疏散指示标志灯具安装的做法，不符合消防技术标准的是（ ）。",[493,495,497,499],{"key":20,"text":494,"correct":22},"消防应急照明灯具安装在顶棚上",{"key":24,"text":496,"correct":32},"消防应急照明灯具与主电源间的连线采用插头连接",{"key":27,"text":498,"correct":22},"疏散走道上标志灯具的安装间距为9m",{"key":30,"text":500,"correct":22},"消防应急照明灯具采用金属杆吊装在建筑结构件上",{"id":502,"libraryId":5,"type":15,"typeLabel":16,"stem":503,"options":504,"answer":30,"analysis":33},936382,"下列关于消防应急照明控制器调式，不包括（ ）。",[505,507,509,511],{"key":20,"text":506,"correct":22},"自检功能",{"key":24,"text":508,"correct":22},"操作级别",{"key":27,"text":510,"correct":22},"主、备电源的自动转换功能",{"key":30,"text":512,"correct":32},"电源分配输出功能",{"id":514,"libraryId":5,"type":15,"typeLabel":16,"stem":515,"options":516,"answer":27,"analysis":33},936383,"下列关于消防应急照明和疏散指示系统的检查结果，符合规范要求的是（ ）。",[517,519,521,523],{"key":20,"text":518,"correct":22},"消防应急灯具连接在专门用于该系统的插座上",{"key":24,"text":520,"correct":22},"安装在侧墙上消防应急灯具其底部距地面1．5m",{"key":27,"text":522,"correct":32},"应急照明分配电装置的输出线路可以选择燃烧性能为B1级的电线电缆",{"key":30,"text":524,"correct":22},"地面安装灯具的供电线路选择耐腐蚀的橡胶电缆，控制线路可选择普通的阻燃耐火电缆",{"id":526,"libraryId":5,"type":131,"typeLabel":132,"stem":527,"options":528,"answer":539,"analysis":33},936384,"火灾自动报警系统管路超过下列长度时，应在便于接线处装设接线盒（ ）。",[529,531,533,535,537],{"key":20,"text":530,"correct":32},"管子长度每超过30m，无弯曲时",{"key":24,"text":532,"correct":22},"管子长度每超过10m，有1个弯曲时",{"key":27,"text":534,"correct":32},"管子长度每超过10m，有2个弯曲时",{"key":30,"text":536,"correct":32},"管子长度每超过8m，有3个弯曲时",{"key":144,"text":538,"correct":22},"管子长度每超过8m，有4个弯曲时","ACD",{"id":541,"libraryId":5,"type":15,"typeLabel":16,"stem":542,"options":543,"answer":30,"analysis":33},936385,"下列关于消防应急标志灯具的安装说法中，错误的是（ ）。",[544,546,548,550],{"key":20,"text":545,"correct":22},"安装在地面上时，灯具的所有金属构件应采用耐腐蚀构件或做防腐处理",{"key":24,"text":547,"correct":22},"吊装时，应采用金属吊杆或吊链，吊杆或吊链上端应固定在建筑结构件上",{"key":27,"text":549,"correct":22},"低位安装在疏散走道及其转角处时，标志灯具表面应与墙面平行",{"key":30,"text":551,"correct":32},"安装在地面上时，与地面高度差不宜大于5mm",{"id":553,"libraryId":5,"type":15,"typeLabel":16,"stem":554,"options":555,"answer":30,"analysis":33},936386,"消防应急照明灯具在侧面墙上顶部安装时，其底部距地面距离不得低于（ ）m。",[556,557,558,560],{"key":20,"text":334,"correct":22},{"key":24,"text":91,"correct":22},{"key":27,"text":559,"correct":22},"1．8",{"key":30,"text":336,"correct":32},{"id":562,"libraryId":5,"type":15,"typeLabel":16,"stem":563,"options":564,"answer":24,"analysis":33},936387,"下列关于应急照明集中电源的安装说法中，错误的是（ ）。",[565,567,569,571],{"key":20,"text":566,"correct":22},"安装场所应无腐蚀性气体、蒸汽、易燃物及尘土",{"key":24,"text":568,"correct":32},"电池应安放在密封环境中",{"key":27,"text":570,"correct":22},"电源落地安装时，宜高出地面150mm以上",{"key":30,"text":572,"correct":22},"屏前和屏后的通道应能够满足更换电池的需求",{"id":574,"libraryId":5,"type":15,"typeLabel":16,"stem":575,"options":576,"answer":20,"analysis":33},936388,"某单位委托具备相应资质的消防技术服务机构对建筑内消防应急照明和疏散指示标志进行调试，下列关于应急照明控制器调试的说法中，错误的是（ ）。",[577,579,581,583],{"key":20,"text":578,"correct":32},"关闭应急照明控制器的主程序，系统内的消防应急灯具应能处于原有状态，等待主程序重新启动",{"key":24,"text":580,"correct":22},"断开任一消防应急灯具与应急照明控制器间连线，应急照明控制器应发出声、光故障信号，并显示故障部位",{"key":27,"text":582,"correct":22},"应急照明控制器应能控制任何消防应急灯具从主电工作状态转入应急工作状态",{"key":30,"text":584,"correct":22},"断开应急照明控制器的主电源，使应急照明控制器由备电工作，应急照明控制器在备电工作时各种控制功能应不受影响",{"id":586,"libraryId":5,"type":15,"typeLabel":16,"stem":587,"options":588,"answer":27,"analysis":33},936389,"应急照明配电箱装置落地安装时宜高出地面（ ）mm。",[589,591,593,595],{"key":20,"text":590,"correct":22},"20-100",{"key":24,"text":592,"correct":22},"30-100",{"key":27,"text":594,"correct":32},"100-200",{"key":30,"text":596,"correct":22},"150-200",{"id":598,"libraryId":5,"type":15,"typeLabel":16,"stem":599,"options":600,"answer":27,"analysis":33},936390,"消防检测人员在对某建筑内的消防应急照明灯具检查时，发现有一个灯具的状态指示灯为亮红色，这表明该应急照明灯具处于（ ）状态。",[601,603,605,607],{"key":20,"text":602,"correct":22},"主电工作状态",{"key":24,"text":604,"correct":22},"备电工作状态",{"key":27,"text":606,"correct":32},"充电状态",{"key":30,"text":608,"correct":22},"故障状态",{"id":610,"libraryId":5,"type":15,"typeLabel":16,"stem":611,"options":612,"answer":30,"analysis":33},936391,"根据《消防应急照明和疏散指示系统》GB 17945—2010，关于应急照明配电箱应具备的性能要求，说法错误的是（ ）。",[613,615,617,619],{"key":20,"text":614,"correct":22},"双路输入型应急照明配电箱应设有手动试验转换装置，手动试验转换完毕后应能自动恢复到正常供电电源供电",{"key":24,"text":616,"correct":22},"应急照明配电箱应能接收应急转换联动控制信号，切断供电电源，使连接的灯具转入应急状态",{"key":27,"text":618,"correct":22},"应急照明配电箱的每路电源均应设有绿色电源状态指示灯，指示正常供电电源和备用供电电源的供电状态",{"key":30,"text":620,"correct":32},"应急照明配电箱在应急转换时，应保证灯具在5s内转入应急工作状态，高危险区域的应急转换时间不大于1．5s",[622,625,628,631,634,637],{"id":15,"name":623,"category":7,"favorite":624},"领导干部任职前廉政法规知识测试题",92,{"id":626,"name":627,"category":7,"favorite":15},595,"建筑结构与设备",{"id":629,"name":630,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":632,"name":633,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":635,"name":636,"category":7,"favorite":8},534,"BIM工程师",{"id":638,"name":636,"category":7,"favorite":8},535]