[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-605-31":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":628},{"id":5,"name":6,"category":7,"favorite":8},605,"消防技术综合能力(一级、二级)","建筑工程",0,31,50,2974,[13,34,46,58,70,81,93,111,126,138,150,162,174,186,198,210,222,234,246,258,270,282,294,306,318,329,343,356,371,383,395,410,420,435,447,459,469,478,486,497,509,521,533,545,555,568,580,592,604,616],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":20,"analysis":33},936188,1,"单选题","施工单位承接某企业泡沫灭火系统安装工程，系统泡沫混合液管道设置在地上，在安装控制阀时，宜使其高度保持在（ ）m。",[19,23,27,30],{"key":20,"text":21,"correct":22},"A","1.1～1.5",true,{"key":24,"text":25,"correct":26},"B","1.3～1.5",false,{"key":28,"text":29,"correct":26},"C","1.3～1.7",{"key":31,"text":32,"correct":26},"D","1.5～1.7","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":28,"analysis":33},936189,"某储罐区采用低倍数泡沫灭火系统。根据现行国家标准《泡沫灭火系统及验收规范》GB50281，下列检查项目中，属于每月检查一次的项目是（ ）。",[38,40,42,44],{"key":20,"text":39,"correct":26},"管道过滤器滤网进行清洗",{"key":24,"text":41,"correct":26},"检测消防水泵的流量和压力",{"key":28,"text":43,"correct":22},"平时充有泡沫液的管道应进行渗漏检查",{"key":31,"text":45,"correct":26},"金属软管进行外观检查",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":20,"analysis":33},936190,"整体平衡式比例混合装置是由平衡压力流量控制阀和比例混合器两大部分装在一起的,产品出厂前己进行了（ ）和混合比的标定,故安装时需整体竖直安装在压力水的水平管道上。",[50,52,54,56],{"key":20,"text":51,"correct":22},"强度试验",{"key":24,"text":53,"correct":26},"发泡倍数",{"key":28,"text":55,"correct":26},"压力试验",{"key":31,"text":57,"correct":26},"流量标定",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":28,"analysis":33},936191,"泡沫灭火系统的使用或管理单位要由经过专门培训的人员负责系统的管理操作和维护,维护管理人员需要熟悉泡沫灭火系统的原理、性能和操作维护规程。下列关于泡沫灭火系统的维护管理,说法不正确的 有（ ）。",[62,64,66,68],{"key":20,"text":63,"correct":26},"每周需要对消防泵和备用动力以手动或自动控制的方式进行一次启动试验",{"key":24,"text":65,"correct":26},"每月对遥控功能或自动控制设施及操纵机构进行检查",{"key":28,"text":67,"correct":22},"每半年对高倍数泡沫产生器进口端控制阀后的管道进行冲洗,清除锈渣",{"key":31,"text":69,"correct":26},"每两年对低倍数泡沫灭火系统进行喷泡沬试验",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":31,"analysis":33},936192,"泡沫液进场后,需要现场取样留存,以待日后需要时送检。对于需要送检的泡沫液,检测内容不包括（ ）",[74,75,77,79],{"key":20,"text":53,"correct":26},{"key":24,"text":76,"correct":26},"析液时间",{"key":28,"text":78,"correct":26},"抗烧时间",{"key":31,"text":80,"correct":22},"喷射时间",{"id":82,"libraryId":5,"type":15,"typeLabel":16,"stem":83,"options":84,"answer":24,"analysis":33},936193,"在泡沫灭火系统管道的水压试验时，试验压力应为设计压力的（ ）倍。",[85,87,89,91],{"key":20,"text":86,"correct":26},"1",{"key":24,"text":88,"correct":22},"1．5",{"key":28,"text":90,"correct":26},"2",{"key":31,"text":92,"correct":26},"2．5",{"id":94,"libraryId":5,"type":95,"typeLabel":96,"stem":97,"options":98,"answer":110,"analysis":33},936194,2,"多选题","某施工单位对泡沫液储罐进行进场检查，下列属于外观检查项目的是（ ）。",[99,101,103,105,107],{"key":20,"text":100,"correct":22},"机械损伤",{"key":24,"text":102,"correct":22},"表面涂层",{"key":28,"text":104,"correct":26},"产品材质",{"key":31,"text":106,"correct":22},"铭牌标记",{"key":108,"text":109,"correct":26},"E","产品说明","ABD",{"id":112,"libraryId":5,"type":95,"typeLabel":96,"stem":113,"options":114,"answer":125,"analysis":33},936195,"某1NG项目采用了高倍数泡沫灭火系统，因为价格优惠，一次性购买蛋白泡沫灭火剂2t，下列关于该项目的施工检查中，符合规范要求的是（ ）。",[115,117,119,121,123],{"key":20,"text":116,"correct":22},"需要对泡沫灭火剂取样送至具备相应资质的检测单位进行检测",{"key":24,"text":118,"correct":22},"用手持折射仪测量泡沫液的混合比",{"key":28,"text":120,"correct":26},"当对泡沫比例混合装置的质量有疑义时，要现场进行抽样测试",{"key":31,"text":122,"correct":22},"检查施工记录时发现，泡沫管道的水压试验是以1．5倍设计压力作为实验压力进行",{"key":108,"text":124,"correct":22},"距高倍数泡沫产生器的进气端0．5m处有遮挡物","ABDE",{"id":127,"libraryId":5,"type":15,"typeLabel":16,"stem":128,"options":129,"answer":28,"analysis":33},936196,"下列关于干粉灭火系统选择阀安装的说法中，错误的是（ ）。",[130,132,134,136],{"key":20,"text":131,"correct":26},"选择阀采用螺纹连接时，其与管网连接处采用法兰连接或活接",{"key":24,"text":133,"correct":26},"选择阀上须设置标明防护区或保护对象名称（编号）的永久性标志牌",{"key":28,"text":135,"correct":22},"在操作面一侧安装选择阀操作手柄，当安装高度超过1．5m时，要采取便于操作的措施",{"key":31,"text":137,"correct":26},"选择阀的流向指示箭头与介质流动方向一致",{"id":139,"libraryId":5,"type":15,"typeLabel":16,"stem":140,"options":141,"answer":24,"analysis":33},936197,"某单位一封闭防护区采用两套预制干粉灭火系统进行全淹没保护，消防设施检测机构对该系统进行检测，结果如下，其中不符合现行国家消防技术标准要求的是（ ）。",[142,144,146,148],{"key":20,"text":143,"correct":26},"装置管道长度为15m",{"key":24,"text":145,"correct":22},"喷放灭火剂时，不能自动关闭的开口设置在防护区底部",{"key":28,"text":147,"correct":26},"预制灭火装置未设机械应急操作启动方式",{"key":31,"text":149,"correct":26},"两套装置响应时间差为1s",{"id":151,"libraryId":5,"type":15,"typeLabel":16,"stem":152,"options":153,"answer":20,"analysis":33},936198,"消防设施检测机构对某单位内设置的全淹没干粉系统进行检测，关于防护区及系统功能检查的结果中，不符合现行国家消防技术标准要求的是（ ）。",[154,156,158,160],{"key":20,"text":155,"correct":22},"干粉喷射时间为50s",{"key":24,"text":157,"correct":26},"灭火剂设计浓度为0．7kg／m3",{"key":28,"text":159,"correct":26},"防护区吊顶的耐火极限为0．5h",{"key":31,"text":161,"correct":26},"防护区的围护结构及门、窗的耐火极限为1．00h",{"id":163,"libraryId":5,"type":15,"typeLabel":16,"stem":164,"options":165,"answer":28,"analysis":33},936199,"某单位内经常有人停留的防护区设置局部应用干粉灭火系统进行保护，在对该系统进行设计时，下列可不设置的启动方式是（ ）。",[166,168,170,172],{"key":20,"text":167,"correct":26},"机械应急操作",{"key":24,"text":169,"correct":26},"手动控制",{"key":28,"text":171,"correct":22},"自动控制",{"key":31,"text":173,"correct":26},"传动管控制",{"id":175,"libraryId":5,"type":15,"typeLabel":16,"stem":176,"options":177,"answer":20,"analysis":33},936200,"关于干粉灭火系统的日常维护管理,下列说法正确的是（ ）。",[178,180,182,184],{"key":20,"text":179,"correct":22},"每日应检查一次启动气体储瓶和驱动气体储瓶的压力",{"key":24,"text":181,"correct":26},"每周应检查一次驱动气体储瓶的充装量",{"key":28,"text":183,"correct":26},"每月应检查一次防护区及干粉存储装置间",{"key":31,"text":185,"correct":26},"每年应检查一次干粉储存装置部件",{"id":187,"libraryId":5,"type":15,"typeLabel":16,"stem":188,"options":189,"answer":31,"analysis":33},936201,"下列有关模拟喷放试验的试验要求说法,不正确的是（ ）。",[190,192,194,196],{"key":20,"text":191,"correct":26},"采用干粉灭火剂和自动启动方式,干粉用量不少于设计用量的 30%",{"key":24,"text":193,"correct":26},"当现场条件不允许喷放干粉灭火剂时,可采用惰性气体",{"key":28,"text":195,"correct":26},"试验时应保证出口压力不低于设计压力",{"key":31,"text":197,"correct":22},"采用的试验气瓶需与干粉灭火系统驱动气体储瓶的型号规格、阀门结构、充装压力、连接与控制方式类似",{"id":199,"libraryId":5,"type":15,"typeLabel":16,"stem":200,"options":201,"answer":24,"analysis":33},936202,"按照系统应用方式的不同，干粉灭火系统可分为（ ）。",[202,204,206,208],{"key":20,"text":203,"correct":26},"固定式干粉灭火系统和半固定式干粉灭火系统",{"key":24,"text":205,"correct":22},"全淹没灭火系统和局部应用系统",{"key":28,"text":207,"correct":26},"储气瓶型干粉灭火系统和储压型干粉灭火系统",{"key":31,"text":209,"correct":26},"管网干粉灭火系统、预制干粉灭火系统和干粉炮灭火系统",{"id":211,"libraryId":5,"type":15,"typeLabel":16,"stem":212,"options":213,"answer":24,"analysis":33},936203,"干粉灭火系统组件安装中，对于储压型系统，当采用全淹没灭火系统时，喷头的最大安装高度不大于（ ）。",[214,216,218,220],{"key":20,"text":215,"correct":26},"5m",{"key":24,"text":217,"correct":22},"7m",{"key":28,"text":219,"correct":26},"9m",{"key":31,"text":221,"correct":26},"10m",{"id":223,"libraryId":5,"type":15,"typeLabel":16,"stem":224,"options":225,"answer":28,"analysis":33},936204,"某施工单位对干粉灭火系统的驱动气体储瓶进行安装检查时，按规定，同一规格的驱动气体储瓶高度差不超过（ ）mm。",[226,228,230,232],{"key":20,"text":227,"correct":26},"10",{"key":24,"text":229,"correct":26},"15",{"key":28,"text":231,"correct":22},"20",{"key":31,"text":233,"correct":26},"25",{"id":235,"libraryId":5,"type":15,"typeLabel":16,"stem":236,"options":237,"answer":24,"analysis":33},936205,"在干粉灭火系统分类中，局部应用系统是按照（ ）分类。",[238,240,242,244],{"key":20,"text":239,"correct":26},"系统结构",{"key":24,"text":241,"correct":22},"应用方式",{"key":28,"text":243,"correct":26},"安装方式",{"key":31,"text":245,"correct":26},"储存方式",{"id":247,"libraryId":5,"type":15,"typeLabel":16,"stem":248,"options":249,"answer":31,"analysis":33},936206,"干粉灭火系统中启动气体储瓶内压力不低于设计压力，且不超过设计压力的（ ）。",[250,252,254,256],{"key":20,"text":251,"correct":26},"2％",{"key":24,"text":253,"correct":26},"3％",{"key":28,"text":255,"correct":26},"4％",{"key":31,"text":257,"correct":22},"5％",{"id":259,"libraryId":5,"type":15,"typeLabel":16,"stem":260,"options":261,"answer":24,"analysis":33},936207,"干粉输送管道末端采用防晃支架固定，支架与末端喷头间的距离不大于（ ）mm。",[262,264,266,268],{"key":20,"text":263,"correct":26},"300",{"key":24,"text":265,"correct":22},"500",{"key":28,"text":267,"correct":26},"600",{"key":31,"text":269,"correct":26},"800",{"id":271,"libraryId":5,"type":15,"typeLabel":16,"stem":272,"options":273,"answer":20,"analysis":33},936208,"干粉灭火系统进行气密性试验时，达到试验压力，关断试验气源3min内压力降不超过试验压力的（ ）为合格。",[274,276,278,280],{"key":20,"text":275,"correct":22},"10％",{"key":24,"text":277,"correct":26},"20％",{"key":28,"text":279,"correct":26},"30％",{"key":31,"text":281,"correct":26},"40％",{"id":283,"libraryId":5,"type":15,"typeLabel":16,"stem":284,"options":285,"answer":24,"analysis":33},936209,"对于储气瓶型干粉灭火系统，当采用全淹没灭火系统时，喷头的最大安装高度不大于（ ）m，当采用局部应用系统时，喷头最大安装高度不大于（ ）m。",[286,288,290,292],{"key":20,"text":287,"correct":26},"7，6",{"key":24,"text":289,"correct":22},"8，7",{"key":28,"text":291,"correct":26},"8，6",{"key":31,"text":293,"correct":26},"7，5",{"id":295,"libraryId":5,"type":15,"typeLabel":16,"stem":296,"options":297,"answer":20,"analysis":33},936210,"关于干粉灭火系统的日常维护管理，不属于每日检查的项目是（ ）。",[298,300,302,304],{"key":20,"text":299,"correct":22},"驱动气体储瓶充装量",{"key":24,"text":301,"correct":26},"干粉储存装置外观",{"key":28,"text":303,"correct":26},"灭火控制器运行情况",{"key":31,"text":305,"correct":26},"启动气体储瓶和驱动气体储瓶压力",{"id":307,"libraryId":5,"type":15,"typeLabel":16,"stem":308,"options":309,"answer":31,"analysis":33},936211,"干粉灭火系统组件安装完毕后需要进行调试，其中模拟喷放试验应采用干粉灭火剂和自动启动方式，干粉用量不少于设计用量的（ ）。",[310,312,314,316],{"key":20,"text":311,"correct":26},"10%",{"key":24,"text":313,"correct":26},"15%",{"key":28,"text":315,"correct":26},"20%",{"key":31,"text":317,"correct":22},"30%",{"id":319,"libraryId":5,"type":15,"typeLabel":16,"stem":320,"options":321,"answer":20,"analysis":33},936212,"某干粉灭火系统施工现场，施工单位组织对干粉灭火容器进行现场检查，充装量检查要求实际充装量不得小于设计充装量，也不得超过设计充装量的（ ）。",[322,324,326,328],{"key":20,"text":323,"correct":22},"3%",{"key":24,"text":325,"correct":26},"5%",{"key":28,"text":327,"correct":26},"7%",{"key":31,"text":311,"correct":26},{"id":330,"libraryId":5,"type":95,"typeLabel":96,"stem":331,"options":332,"answer":342,"analysis":33},936213,"某施工单位对干粉灭火系统进行进场检测，对干粉储存容器检查时，下列属于应检查的项目是（ ）。",[333,335,337,339,341],{"key":20,"text":334,"correct":22},"外观质量",{"key":24,"text":336,"correct":26},"气密性试验",{"key":28,"text":338,"correct":22},"密封面",{"key":31,"text":340,"correct":22},"充装量",{"key":108,"text":51,"correct":26},"ACD",{"id":344,"libraryId":5,"type":95,"typeLabel":96,"stem":345,"options":346,"answer":355,"analysis":33},936214,"对干粉灭火系统进行维护管理时，下列属于月度检查项目的是（ ）。",[347,348,350,351,353],{"key":20,"text":305,"correct":26},{"key":24,"text":349,"correct":22},"干粉储存装置部件",{"key":28,"text":299,"correct":22},{"key":31,"text":352,"correct":26},"模拟启动检查",{"key":108,"text":354,"correct":26},"备用瓶组切换功能检测","BC",{"id":357,"libraryId":5,"type":95,"typeLabel":96,"stem":358,"options":359,"answer":370,"analysis":33},936215,"在干粉灭火系统的日常维护管理过程中，检查频次正确的做法包括（ ）。",[360,362,364,366,368],{"key":20,"text":361,"correct":22},"每日检查干粉储存装置外观",{"key":24,"text":363,"correct":22},"每日检查灭火控制器运行情况",{"key":28,"text":365,"correct":22},"每月检查驱动气体储瓶充装量",{"key":31,"text":367,"correct":26},"每月检查启动气体储瓶和驱动气体储瓶压力",{"key":108,"text":369,"correct":22},"每年模拟启动检查","ABCE",{"id":372,"libraryId":5,"type":15,"typeLabel":16,"stem":373,"options":374,"answer":24,"analysis":33},936216,"下列关于干粉灭火系统的维护管理，不正确的是（）。",[375,377,379,381],{"key":20,"text":376,"correct":26},"启动气体储瓶和驱动气体储瓶压力至少每日检查1次",{"key":24,"text":378,"correct":22},"灭火控制器运行情况至少每月检查1次",{"key":28,"text":380,"correct":26},"驱动气体储瓶充装量至少每月检查1次",{"key":31,"text":382,"correct":26},"防护区及干粉储存装置间每年检查1次",{"id":384,"libraryId":5,"type":15,"typeLabel":16,"stem":385,"options":386,"answer":28,"analysis":33},936217,"某消防设施检测机构对一单位设置的局部应用干粉灭火系统进行检测。关于系统保护对象环境及系统功能检查的下列结果中，不符合现行国家消防技术标准要求的是（）。",[387,389,391,393],{"key":20,"text":388,"correct":26},"喷射的干粉覆盖保护对象垂直投影面积的120％",{"key":24,"text":390,"correct":26},"可燃液体液面至容器缘口的距离为155mm",{"key":28,"text":392,"correct":22},"保护对象周围的空气流动速度最大为3m／s",{"key":31,"text":394,"correct":26},"干粉喷射时间为60s",{"id":396,"libraryId":5,"type":95,"typeLabel":96,"stem":397,"options":398,"answer":409,"analysis":33},936218,"干粉灭火系统系统试压试验和管网吹扫在管网安装完毕后进行，下列规定试压、吹扫条件符合要求的是（）。",[399,401,403,405,407],{"key":20,"text":400,"correct":22},"经复查，埋地管道的位置及管道基础、支墩等符合设计文件要求",{"key":24,"text":402,"correct":26},"准备不少于2只的试压用压力表，精度不低于2．0级，量程为试验压力值的1．5～2．0倍",{"key":28,"text":404,"correct":22},"加设的1临时盲板具有突出于法兰的边耳，且有明显标志，并对临时盲板数量、位置进行记录",{"key":31,"text":406,"correct":22},"隔离或者拆除不能参与试压的设备、仪表、阀门及附件",{"key":108,"text":408,"correct":22},"采用生活用水进行水压试验和管网冲洗，不得使用海水或者含有腐蚀性化学物质的水进行试压试验、管网冲洗","ACDE",{"id":411,"libraryId":5,"type":15,"typeLabel":16,"stem":412,"options":413,"answer":20,"analysis":33},936219,"干粉灭火系统检查中，下列属于月检的是（ ）。",[414,415,417,419],{"key":20,"text":349,"correct":22},{"key":24,"text":416,"correct":26},"防护区及干粉储存装置间",{"key":28,"text":418,"correct":26},"管网、支架及喷放组件",{"key":31,"text":301,"correct":26},{"id":421,"libraryId":5,"type":95,"typeLabel":96,"stem":422,"options":423,"answer":434,"analysis":33},936220,"干粉灭火系统的模拟喷放试验判定标准有（ ）。",[424,426,428,430,432],{"key":20,"text":425,"correct":22},"延时启动时符合设定时间",{"key":24,"text":427,"correct":22},"有关声光报警信号正确",{"key":28,"text":429,"correct":22},"信号反馈装置动作正常",{"key":31,"text":431,"correct":22},"干粉输送管无明显晃动和机械性损坏",{"key":108,"text":433,"correct":26},"干粉或气体能喷入被试防护区内或保护对象上","ABCD",{"id":436,"libraryId":5,"type":15,"typeLabel":16,"stem":437,"options":438,"answer":24,"analysis":33},936221,"（）是按一定的应用条件，将干粉储存装置和喷头等部件预先组装起来的成套灭火装置。预制干粉灭火装置主要由柜体、干粉储存容器、驱动气体储瓶、输粉管路和干粉喷头以及与之配套的火灾探测器、火灾报警控制器等组成，主要用来保护特定的小型设备或者小空间，既可用于局部保护方式，也可用于全淹没保护方式。",[439,441,443,445],{"key":20,"text":440,"correct":26},"干粉炮灭火系统",{"key":24,"text":442,"correct":22},"预制干粉灭火装置",{"key":28,"text":444,"correct":26},"储气型干粉灭火系统",{"key":31,"text":446,"correct":26},"储压型干粉灭火系统",{"id":448,"libraryId":5,"type":15,"typeLabel":16,"stem":449,"options":450,"answer":28,"analysis":33},936222,"干粉灭火系统管网试压和吹扫中，当水压强度试验条件不具备时，可采用气压强度试验代替。气压强度试验压力取（）倍系统最大工作压力。",[451,453,455,457],{"key":20,"text":452,"correct":26},"1．05",{"key":24,"text":454,"correct":26},"1．10",{"key":28,"text":456,"correct":22},"1．15",{"key":31,"text":458,"correct":26},"1．20",{"id":460,"libraryId":5,"type":15,"typeLabel":16,"stem":461,"options":462,"answer":24,"analysis":33},936223,"对干粉储存容器现场检查时，要求实际充装量不得小于设计充装量，也不得超过设计充装量的（ ）。",[463,465,466,467],{"key":20,"text":464,"correct":26},"1％",{"key":24,"text":253,"correct":22},{"key":28,"text":257,"correct":26},{"key":31,"text":468,"correct":26},"6％",{"id":470,"libraryId":5,"type":15,"typeLabel":16,"stem":471,"options":472,"answer":31,"analysis":33},936224,"干粉灭火系统管网吹扫采用压缩空气时，管道末端的气体流速不小于（ ）m／s。",[473,475,476,477],{"key":20,"text":474,"correct":26},"5",{"key":24,"text":227,"correct":26},{"key":28,"text":229,"correct":26},{"key":31,"text":231,"correct":22},{"id":479,"libraryId":5,"type":15,"typeLabel":16,"stem":480,"options":481,"answer":20,"analysis":33},936225,"干粉灭火系统启动气体储瓶内压力不低于设计压力，且不超过设计压力的（ ）％，设置在启动气体管道的单向阀启闭灵活，无卡阻现象。",[482,483,484,485],{"key":20,"text":474,"correct":22},{"key":24,"text":227,"correct":26},{"key":28,"text":229,"correct":26},{"key":31,"text":231,"correct":26},{"id":487,"libraryId":5,"type":15,"typeLabel":16,"stem":488,"options":489,"answer":24,"analysis":33},936226,"对干粉灭火系统进行周期性检查维护管理，下列检查项目中，不属于年度功能检查项目的是（ ）。",[490,491,493,495],{"key":20,"text":352,"correct":26},{"key":24,"text":492,"correct":22},"气瓶和干粉储罐充装量",{"key":28,"text":494,"correct":26},"模拟备用瓶组功能试验",{"key":31,"text":496,"correct":26},"模拟紧急启停功能",{"id":498,"libraryId":5,"type":15,"typeLabel":16,"stem":499,"options":500,"answer":24,"analysis":33},936227,"下列关于干粉灭火系统的操作控制的说法中，不符合规范要求的是（ ）。",[501,503,505,507],{"key":20,"text":502,"correct":26},"当局部应用灭火系统用于经常有人的保护场所时，可不设自动控制启动方式",{"key":24,"text":504,"correct":22},"火灾自动报警系统自动控制时，要设置不小于30s的延迟",{"key":28,"text":506,"correct":26},"预制灭火装置可不设机械应急操作启动方式",{"key":31,"text":508,"correct":26},"手动紧急停止装置应确保灭火系统能在启动后和喷放灭火剂前的延迟阶段中止，在使用手动紧急停止装置后手动启动装置可以再次启动",{"id":510,"libraryId":5,"type":15,"typeLabel":16,"stem":511,"options":512,"answer":20,"analysis":33},936228,"对某单位的干粉灭火系统组件进行检测，下列关于系统组件的检测结果，不符合规范要求的是（ ）。",[513,515,517,519],{"key":20,"text":514,"correct":22},"干粉储存容器灭火剂的装量系数为0．9，增压时间为25s",{"key":24,"text":516,"correct":26},"驱动气体储瓶及其充装系数符合国家现行标准《气瓶安全监察规程》的规定",{"key":28,"text":518,"correct":26},"驱动气体选用氮气",{"key":31,"text":520,"correct":26},"驱动压力小于干粉储存容器的最高工作压力",{"id":522,"libraryId":5,"type":15,"typeLabel":16,"stem":523,"options":524,"answer":28,"analysis":33},936229,"对设置组合分配式干粉的防护区或保护对象进行检查和检测，应注意组件的设置情况，下列关于组件的选择和安装说法，错误的是（ ）。",[525,527,529,531],{"key":20,"text":526,"correct":26},"在组合分配系统中，每个防护区或保护对象应设一个选择阀",{"key":24,"text":528,"correct":26},"选择阀可采用电动、气动或液动驱动方式，并应有机械应急操作方式",{"key":28,"text":530,"correct":22},"喷头的单孔直径不得小于5mm",{"key":31,"text":532,"correct":26},"系统启动时，选择阀应在输出容器阀动作之前打开",{"id":534,"libraryId":5,"type":15,"typeLabel":16,"stem":535,"options":536,"answer":24,"analysis":33},936230,"干粉储存容器在现场检查中， 其充装量（ ）。",[537,539,541,543],{"key":20,"text":538,"correct":26},"不得小于设计充装量， 也不得超过设计充装量的 1%",{"key":24,"text":540,"correct":22},"不得小于设计充装量， 也不得超过设计充装量的 3%",{"key":28,"text":542,"correct":26},"不得小于设计充装量， 也不得超过设计充装量的 5%",{"key":31,"text":544,"correct":26},"不得小于设计充装量， 也不得超过设计充装量的 15%",{"id":546,"libraryId":5,"type":95,"typeLabel":96,"stem":547,"options":548,"answer":554,"analysis":33},936231,"干粉灭火系统中，（ ）项目每年检查1次。",[549,550,551,552,553],{"key":20,"text":416,"correct":22},{"key":24,"text":418,"correct":22},{"key":28,"text":352,"correct":22},{"key":31,"text":349,"correct":26},{"key":108,"text":299,"correct":26},"ABC",{"id":556,"libraryId":5,"type":95,"typeLabel":96,"stem":557,"options":558,"answer":125,"analysis":33},936232,"下列属于干粉灭火系统年度功能检测内容的是（ ）。",[559,561,563,565,567],{"key":20,"text":560,"correct":22},"模拟干粉喷放功能检测",{"key":24,"text":562,"correct":22},"模拟自动启动功能检测",{"key":28,"text":564,"correct":26},"模拟紧急机械启动功能检测",{"key":31,"text":566,"correct":22},"模拟手动启动／紧急停止功能检测",{"key":108,"text":354,"correct":22},{"id":569,"libraryId":5,"type":15,"typeLabel":16,"stem":570,"options":571,"answer":20,"analysis":33},936234,"下列检查项目中，不属于推车式干粉灭火器进厂检查项目的是（ ）。",[572,574,576,578],{"key":20,"text":573,"correct":22},"间歇喷射机构",{"key":24,"text":575,"correct":26},"筒体",{"key":28,"text":577,"correct":26},"灭火器结构",{"key":31,"text":579,"correct":26},"行驶机构",{"id":581,"libraryId":5,"type":15,"typeLabel":16,"stem":582,"options":583,"answer":20,"analysis":33},936235,"下列关于建筑灭火器维修、报废的说法，不正确的是（ ）。",[584,586,588,590],{"key":20,"text":585,"correct":22},"水基型灭火器出厂满5年后应进行报废处理",{"key":24,"text":587,"correct":26},"被火烧过的灭火器应进行报废处理",{"key":28,"text":589,"correct":26},"铭牌脱落的灭火器应进行报废处理",{"key":31,"text":591,"correct":26},"倒置使用型灭火器应进行报废处理",{"id":593,"libraryId":5,"type":15,"typeLabel":16,"stem":594,"options":595,"answer":31,"analysis":33},936236,"灭火器维修后出厂前应逐具进行检验，下列不属于维修出厂检验项目的是（ ）。",[596,598,600,602],{"key":20,"text":597,"correct":26},"灭火器外观、外部结构及总质量检查",{"key":24,"text":599,"correct":26},"灭火器气密性试验",{"key":28,"text":601,"correct":26},"灭火剂充装量检查",{"key":31,"text":603,"correct":22},"灭火器质量检查",{"id":605,"libraryId":5,"type":15,"typeLabel":16,"stem":606,"options":607,"answer":24,"analysis":33},936237,"某工程新到一批翻盖式灭火器箱，现场检查情况如下，其中不符合国家消防技术标准的是（ ）。",[608,610,612,614],{"key":20,"text":609,"correct":26},"用直尺测量箱体正面标注的字体尺寸，宽高为30×60mm",{"key":24,"text":611,"correct":22},"用测力计检查箱盖开启力为60N",{"key":28,"text":613,"correct":26},"在翻盖上标注有开启方向的标识",{"key":31,"text":615,"correct":26},"箱盖开启角度为100。",{"id":617,"libraryId":5,"type":15,"typeLabel":16,"stem":618,"options":619,"answer":20,"analysis":33},936238,"对某写字楼的灭火器进行检查时发现部分灭火器指针处于红色区域，表示灭火器（ ）。",[620,622,624,626],{"key":20,"text":621,"correct":22},"压力不足",{"key":24,"text":623,"correct":26},"压力过高",{"key":28,"text":625,"correct":26},"压力正常",{"key":31,"text":627,"correct":26},"压力表损坏",[629,632,635,638,641,644],{"id":15,"name":630,"category":7,"favorite":631},"领导干部任职前廉政法规知识测试题",92,{"id":633,"name":634,"category":7,"favorite":15},595,"建筑结构与设备",{"id":636,"name":637,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":639,"name":640,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":642,"name":643,"category":7,"favorite":8},534,"BIM工程师",{"id":645,"name":643,"category":7,"favorite":8},535]