[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-605-17":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":658},{"id":5,"name":6,"category":7,"favorite":8},605,"消防技术综合能力(一级、二级)","建筑工程",0,17,50,2974,[13,38,53,67,82,97,109,121,133,145,157,169,178,188,200,212,222,234,246,258,270,278,290,302,314,326,338,350,362,374,386,398,410,422,434,446,458,470,482,496,511,525,539,554,569,584,599,613,628,643],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":36,"analysis":37},935483,2,"多选题","为满足厂房日常管理的需要，在厂房内可以设置一些管理、控制或调度生产的办公用房以及工人的临时休息室。关于此类办公用房和临时休息室的叙述，正确的是（）。",[19,23,26,30,33],{"key":20,"text":21,"correct":22},"A","甲、乙类厂房必须设置办公室、休息室等时，只能与厂房贴邻建造，且耐火等级不低于二级",true,{"key":24,"text":25,"correct":22},"B","甲、乙类厂房与办公室、休息室贴邻建造时，采用耐火极限不低于3．00h的不燃体防爆墙隔开和设置独立的安全出口",{"key":27,"text":28,"correct":29},"C","丙类厂房，厂房内可设置为厂房服务的办公室、休息室，采用耐火极限不低于2．50h的不燃体隔墙和1．50h的楼板与厂房隔开，并至少设置2个独立的安全出口",false,{"key":31,"text":32,"correct":22},"D","丙类厂房，如隔墙上需开设相互连通的门时，需为乙级防火门",{"key":34,"text":35,"correct":29},"E","丙类厂房，厂房内不可设置为厂房服务的办公室、休息室","ABD","",{"id":39,"libraryId":5,"type":15,"typeLabel":16,"stem":40,"options":41,"answer":52,"analysis":37},935484,"某综合楼，共40层，每层4m，消防技术服务机构对该建筑进行防火检查时，存在下列情况。其中符合规范要求的是（ ）。",[42,44,46,48,50],{"key":20,"text":43,"correct":29},"移动营业厅设置在地下三层",{"key":24,"text":45,"correct":22},"消防控制室设置在建筑的地下一层",{"key":27,"text":47,"correct":29},"消防控制室采用耐火极限不低于2．00h的防火隔墙和耐火极限不低于1．50h的楼板与其他部位分隔",{"key":31,"text":49,"correct":22},"消防水泵房设置在地下二层",{"key":34,"text":51,"correct":29},"建筑内的防烟、排烟风机设置在一个房间内","BD",{"id":54,"libraryId":5,"type":55,"typeLabel":56,"stem":57,"options":58,"answer":24,"analysis":37},935485,1,"单选题","某建筑单位承建了本市某一疗养院中的住院部，该建筑耐火等级为三级时，其建筑层数不超过（ ）层。",[59,61,63,65],{"key":20,"text":60,"correct":29},"1",{"key":24,"text":62,"correct":22},"2",{"key":27,"text":64,"correct":29},"3",{"key":31,"text":66,"correct":29},"4",{"id":68,"libraryId":5,"type":15,"typeLabel":16,"stem":69,"options":70,"answer":81,"analysis":37},935486,"在人防工程中，不允许设置的场所或设施包括（ ）。",[71,73,75,77,79],{"key":20,"text":72,"correct":22},"哺乳室、幼儿园、托儿所、游乐厅等儿童活动场所和残疾人员活动场所",{"key":24,"text":74,"correct":22},"使用、储存液化石油气、相对密度（与空气密度比值）大于或等于0．75的可燃气体和闪点小于60℃的液体作燃料的场所",{"key":27,"text":76,"correct":22},"油浸电力变压器",{"key":31,"text":78,"correct":29},"地下商店",{"key":34,"text":80,"correct":29},"歌舞娱乐放映游艺场所","ABC",{"id":83,"libraryId":5,"type":15,"typeLabel":16,"stem":84,"options":85,"answer":96,"analysis":37},935487,"当防火间距不足时，可采取的措施有（ ）。",[86,88,90,92,94],{"key":20,"text":87,"correct":29},"改变房屋结构的耐火性能，提高建筑物的耐火等级",{"key":24,"text":89,"correct":22},"调整生产厂房的部分工艺流程和库房的储存物品的数量",{"key":27,"text":91,"correct":22},"将建筑物的普通外墙改为防火墙",{"key":31,"text":93,"correct":22},"拆除部分耐火等级低、占地面积小、适用性不强且与新建建筑相邻的原有陈旧建筑物",{"key":34,"text":95,"correct":22},"设置独立的防火墙","BCDE",{"id":98,"libraryId":5,"type":55,"typeLabel":56,"stem":99,"options":100,"answer":27,"analysis":37},935488,"对于设有短边长度大于24m的内院或天井的建筑物，宜设置（）的消防车道。",[101,103,105,107],{"key":20,"text":102,"correct":29},"穿过建筑物",{"key":24,"text":104,"correct":29},"尽头式",{"key":27,"text":106,"correct":22},"进入内院或天井",{"key":31,"text":108,"correct":29},"环形",{"id":110,"libraryId":5,"type":55,"typeLabel":56,"stem":111,"options":112,"answer":27,"analysis":37},935489,"消防车通道的最小转弯半径是消防车回转时消防车的前轮外侧循圆曲线行走轨迹的半径：我国普通消防车转弯半径为（）m，登高车的转弯半径为12m，一些特种车辆的转弯半径为16～20m。",[113,115,117,119],{"key":20,"text":114,"correct":29},"5",{"key":24,"text":116,"correct":29},"6",{"key":27,"text":118,"correct":22},"9",{"key":31,"text":120,"correct":29},"10",{"id":122,"libraryId":5,"type":55,"typeLabel":56,"stem":123,"options":124,"answer":31,"analysis":37},935490,"消防车道是指供消防车灭火通行时的道路，下列场所应设置环形车道的是（ ）。",[125,127,129,131],{"key":20,"text":126,"correct":29},"座位数为3000个的单层体育馆",{"key":24,"text":128,"correct":29},"占地面积1500㎡的植物油仓库",{"key":27,"text":130,"correct":29},"占地面积2500㎡的单层植物油精炼厂房",{"key":31,"text":132,"correct":22},"建筑高度为54m的公共建筑",{"id":134,"libraryId":5,"type":55,"typeLabel":56,"stem":135,"options":136,"answer":31,"analysis":37},935491,"某公共建筑，地上5层，地下2层，层高均为5m，室外设计地面标高为±0．00m，地下一层和地上一层为商场，二层至五层为办公楼，下列做法中，符合规范要求的是（ ）。",[137,139,141,143],{"key":20,"text":138,"correct":29},"采用相对密度（与空气密度的比值）为0．65的可燃气体为燃料的锅炉房，设置在地下一层",{"key":24,"text":140,"correct":29},"常（负）压燃油锅炉房设置在地下二层",{"key":27,"text":142,"correct":29},"柴油发电机房设置在地下二层",{"key":31,"text":144,"correct":22},"消防控制室设置在地下一层",{"id":146,"libraryId":5,"type":55,"typeLabel":56,"stem":147,"options":148,"answer":24,"analysis":37},935492,"一级耐火等级的高层金属制品抛光厂房与二级耐火等级的高层民用建筑的防火间距不宜小于（ ）m。",[149,151,153,155],{"key":20,"text":150,"correct":29},"60",{"key":24,"text":152,"correct":22},"50",{"key":27,"text":154,"correct":29},"40",{"key":31,"text":156,"correct":29},"30",{"id":158,"libraryId":5,"type":55,"typeLabel":56,"stem":159,"options":160,"answer":31,"analysis":37},935493,"某一级耐火等级的高层钙镁磷肥厂房与建筑高度为30m的二级耐火等级普通写字楼之间的防火间距不应小于（ ）m。",[161,163,165,167],{"key":20,"text":162,"correct":29},"18",{"key":24,"text":164,"correct":29},"20",{"key":27,"text":166,"correct":29},"15",{"key":31,"text":168,"correct":22},"13",{"id":170,"libraryId":5,"type":55,"typeLabel":56,"stem":171,"options":172,"answer":31,"analysis":37},935494,"某建筑高度为16．5m的多层商场，耐火等级为二级，与建筑高度为55m酒店裙房之间的防火间距不应小于（ ）m。",[173,174,175,177],{"key":20,"text":118,"correct":29},{"key":24,"text":168,"correct":29},{"key":27,"text":176,"correct":29},"7",{"key":31,"text":116,"correct":22},{"id":179,"libraryId":5,"type":55,"typeLabel":56,"stem":180,"options":181,"answer":24,"analysis":37},935495,"某高层办公楼设置进深为4m的裙房，裙房相邻侧为一栋高层住宅，则该裙房与高层住宅之间的防火间距不应小于（ ）m。",[182,183,184,186],{"key":20,"text":168,"correct":29},{"key":24,"text":118,"correct":22},{"key":27,"text":185,"correct":29},"11",{"key":31,"text":187,"correct":29},"14",{"id":189,"libraryId":5,"type":55,"typeLabel":56,"stem":190,"options":191,"answer":31,"analysis":37},935496,"商业广场，地上5层，地下2层，每层建筑面积3200㎡，首层为商场，二层为儿童游乐场、剧场，三层为电影院，四层为餐饮场所，五层为KTV，地下一层为老人年康复中心，受业主委托消防服务机构对该商业建筑进行防火检查，结果如下，其中不符合现行国家技术标准的是（ ）。",[192,194,196,198],{"key":20,"text":193,"correct":29},"KTV采用耐火极限为2．0h的防火隔墙划分多个建筑面积为100㎡的厅、室",{"key":24,"text":195,"correct":29},"老年人康复中心每间用房的建筑面积为200㎡，使用人数为10人",{"key":27,"text":197,"correct":29},"电影院采用耐火极限为2．5h的防火隔墙与其他场所分隔，连通处开设甲级防火门",{"key":31,"text":199,"correct":22},"儿童游乐场采用耐火极限为2．0h的防火隔墙与剧场部位分隔，连通处开设乙级防火门",{"id":201,"libraryId":5,"type":55,"typeLabel":56,"stem":202,"options":203,"answer":31,"analysis":37},935497,"某综合楼，地上10层，地下3层，每层层高3．5m，每层建筑面积3500㎡，地上使用功能为旅馆，办公楼，地下部分使用功能为设备间、汽车库，按照国家规定设置了相应的消防设施，受业主委托消防服务机构对该综合楼进行防火检查，下列结果，符合规范要求的是（ ）。",[204,206,208,210],{"key":20,"text":205,"correct":29},"设置1部消防电梯，从首层到顶层运行时间为60s",{"key":24,"text":207,"correct":29},"常压燃气锅炉房设置在屋顶，与安全出口的距离为3m",{"key":27,"text":209,"correct":29},"地下三层的消防水泵房采用耐火极限为3．0h的防火隔墙与其他部位分隔",{"key":31,"text":211,"correct":22},"地下二层的柴油发电机房采用耐火极限不低于2．00h的防火隔墙和1．50h的不燃性楼板与其他部位分隔，连通处采用甲级防火门",{"id":213,"libraryId":5,"type":55,"typeLabel":56,"stem":214,"options":215,"answer":31,"analysis":37},935498,"某建筑高度为36m的医院病房楼，长55m，宽22m。该建筑周边用地紧张，没有条件连续布置消防车登高操作场地，则每个消防车登高操作场地的最小长度应为（ ）m。",[216,217,219,221],{"key":20,"text":164,"correct":29},{"key":24,"text":218,"correct":29},"55",{"key":27,"text":220,"correct":29},"36",{"key":31,"text":166,"correct":22},{"id":223,"libraryId":5,"type":55,"typeLabel":56,"stem":224,"options":225,"answer":27,"analysis":37},935499,"某老年人照料设施附设在一座一级耐火等级民用建筑下部，建筑层高4m，现计划设置一个老年人公共餐厅，该餐厅建筑面积为200㎡，同一时间就餐人数28人，则该餐厅不可以建造在建筑的（ ）层。",[226,228,230,232],{"key":20,"text":227,"correct":29},"负一",{"key":24,"text":229,"correct":29},"二",{"key":27,"text":231,"correct":22},"十五",{"key":31,"text":233,"correct":29},"四",{"id":235,"libraryId":5,"type":55,"typeLabel":56,"stem":236,"options":237,"answer":31,"analysis":37},935500,"某综合楼，地上11层，地下2层，标准层建筑面积为1200㎡，地上部分使用功能为办公，地下部分为商场，各层层高均为5m。消防机构对该建筑的进行消防安全检查，下列检查结果中符合规范要求的是（ ）。",[238,240,242,244],{"key":20,"text":239,"correct":29},"该建筑设置的环形消防车道有一处与其他车道相通",{"key":24,"text":241,"correct":29},"该建筑的消防车登高操作场地的坡度为8％",{"key":27,"text":243,"correct":29},"该建筑的登高操作场地的长度和宽度分别为15m和10m",{"key":31,"text":245,"correct":22},"登高操作场地范围内的裙房进深为4m",{"id":247,"libraryId":5,"type":55,"typeLabel":56,"stem":248,"options":249,"answer":31,"analysis":37},935501,"建筑之间的防火间距，从相邻建筑（ ）进行测量。",[250,252,254,256],{"key":20,"text":251,"correct":29},"外墙",{"key":24,"text":253,"correct":29},"外墙的最远距离",{"key":27,"text":255,"correct":29},"外墙的最远水平距离",{"key":31,"text":257,"correct":22},"外墙的最近水平距离",{"id":259,"libraryId":5,"type":55,"typeLabel":56,"stem":260,"options":261,"answer":27,"analysis":37},935502,"对设置在建筑内的歌舞娱乐游艺场所进行消防检查，下列结果错误的是（）。",[262,264,266,268],{"key":20,"text":263,"correct":29},"布置在袋形走道两侧或尽端房间疏散门到最近安全出口距离为9m",{"key":24,"text":265,"correct":29},"布置在地下一层且地面与室外出入口地坪高差为6m",{"key":27,"text":267,"correct":22},"布置在四层且每个厅室建筑面积为400m2",{"key":31,"text":269,"correct":29},"厅室之间采用2．00h防火隔墙和1．00h不燃性楼板分隔",{"id":271,"libraryId":5,"type":55,"typeLabel":56,"stem":272,"options":273,"answer":31,"analysis":37},935503,"对一时不能拆除重建的旧城区中严重影响城市消防安全的企业，可划分占地面积不大于2500m2的防火分区，各分区之间留出不小于（）m的防火通道或设置高出建筑屋面不小于50cm的防火墙。",[274,275,276,277],{"key":20,"text":64,"correct":29},{"key":24,"text":66,"correct":29},{"key":27,"text":114,"correct":29},{"key":31,"text":116,"correct":22},{"id":279,"libraryId":5,"type":55,"typeLabel":56,"stem":280,"options":281,"answer":20,"analysis":37},935504,"消防车道常见设置形式有环形消防车道、尽头式消防车道、穿越建筑的消防车道和与环形消防车道相连的中间消防车道等形式。针对高层厂房，占地面积大于3000m2的甲、乙、丙类厂房和占地面积大于1500m2的乙、丙类仓库，消防车道通常应该设置的形式为（ ）。",[282,284,286,288],{"key":20,"text":283,"correct":22},"环形消防车道",{"key":24,"text":285,"correct":29},"尽头式消防车道",{"key":27,"text":287,"correct":29},"穿越建筑的消防车道",{"key":31,"text":289,"correct":29},"与环形消防车道相连的中间消防车道",{"id":291,"libraryId":5,"type":55,"typeLabel":56,"stem":292,"options":293,"answer":27,"analysis":37},935505,"在人防工程中，柴油发电机房储油间采用防火墙和常闭甲级防火门与发电机间隔开，并设置高（）mm的不燃烧、不渗漏的门槛，地面不得设置地漏。",[294,296,298,300],{"key":20,"text":295,"correct":29},"100",{"key":24,"text":297,"correct":29},"120",{"key":27,"text":299,"correct":22},"150",{"key":31,"text":301,"correct":29},"180",{"id":303,"libraryId":5,"type":55,"typeLabel":56,"stem":304,"options":305,"answer":27,"analysis":37},935506,"下列建筑中不设置消防电梯，仍能符合国家工程消防技术标准的是（ ）。",[306,308,310,312],{"key":20,"text":307,"correct":29},"某高度为50m的办公大楼",{"key":24,"text":309,"correct":29},"某住宅建筑12层，层高3 m",{"key":27,"text":311,"correct":22},"埋深为8 m的地下建筑，地下建筑总面积为800 m2",{"key":31,"text":313,"correct":29},"局部建筑高度为33 m，且局部高出部分的每层建筑面积为60 m2的丁类厂房",{"id":315,"libraryId":5,"type":55,"typeLabel":56,"stem":316,"options":317,"answer":27,"analysis":37},935507,"装运液化石油气和其他易燃易爆化学物品的专用码头布置在某港区的独立安全地段。对某装运液化石油气的码头进行检查，此码头最大装运船舶长度为280 m，该码头与装运其他物品的码头之间的距离不小于（ ）m，距主航道的距离不小于（ ）m。",[318,320,322,324],{"key":20,"text":319,"correct":29},"140，280",{"key":24,"text":321,"correct":29},"280，280",{"key":27,"text":323,"correct":22},"560，280",{"key":31,"text":325,"correct":29},"280，560",{"id":327,"libraryId":5,"type":55,"typeLabel":56,"stem":328,"options":329,"answer":27,"analysis":37},935508,"某民用建筑，地下2层，地上8层，该建筑内均设置自动灭火系统，某电影院欲设置在该建筑内，则下列做法错误的是（ ）。",[330,332,334,336],{"key":20,"text":331,"correct":29},"设置在地下一层，一个厅室建筑面积300 m2",{"key":24,"text":333,"correct":29},"设置在地上四层，一个厅室建筑面积200 m2",{"key":27,"text":335,"correct":22},"设置在地下二层，一个厅室建筑面积150 m2，设置一个疏散门",{"key":31,"text":337,"correct":29},"厅室与其他部位之间采用3．00h的防火隔墙与1．50h不燃性楼板分隔",{"id":339,"libraryId":5,"type":55,"typeLabel":56,"stem":340,"options":341,"answer":24,"analysis":37},935509,"消防站的设置位置便于消防车迅速通往工艺装置区和罐区，宜位于化工企业生产区（ ）且避开工厂主要人流道路。",[342,344,346,348],{"key":20,"text":343,"correct":29},"全年最小频率风向的上风侧",{"key":24,"text":345,"correct":22},"全年最小频率风向的下风侧",{"key":27,"text":347,"correct":29},"全年最大频率风向的上风侧",{"key":31,"text":349,"correct":29},"全年最大频率风向的下风侧",{"id":351,"libraryId":5,"type":55,"typeLabel":56,"stem":352,"options":353,"answer":31,"analysis":37},935510,"消防车登高面是消防灭火救援的重要设施。下列关于消防车登高面设置的说法中，错误的是（）。",[354,356,358,360],{"key":20,"text":355,"correct":29},"高层建筑应至少沿一个长边或周边长度的1／4且不小于一个长边长度的底边连续布置消防车登高面",{"key":24,"text":357,"correct":29},"消防车登高面靠建筑外墙一侧的边缘距离建筑外墙不宜小于5m，且不应大于10m",{"key":27,"text":359,"correct":29},"消防车登高面的坡度不宜大于3％",{"key":31,"text":361,"correct":22},"高层建筑的消防车登高面不应布置裙房",{"id":363,"libraryId":5,"type":55,"typeLabel":56,"stem":364,"options":365,"answer":27,"analysis":37},935511,"某旧城区中有一些中严重影响城市消防安全的企业，但是现在由于某些原因不能对其进行拆除，对其的处理是划分合理的防火分区，在各分区之间留出不小于（ ）m的通道或设置高出建筑屋面不小于（ ）cm的防火墙。",[366,368,370,372],{"key":20,"text":367,"correct":29},"4，50",{"key":24,"text":369,"correct":29},"4，100",{"key":27,"text":371,"correct":22},"6，50",{"key":31,"text":373,"correct":29},"6，100",{"id":375,"libraryId":5,"type":55,"typeLabel":56,"stem":376,"options":377,"answer":20,"analysis":37},935512,"某氨压缩机房需要设置一个供本机房专用的10kV配电站，关于该配电站的设置，下列做法中不符合规范要求的是（ ）。",[378,380,382,384],{"key":20,"text":379,"correct":22},"该配电站不得贴邻厂房",{"key":24,"text":381,"correct":29},"如果生产上确实有需要，当采用无门、窗、洞口的防火墙分隔时，可一面贴邻",{"key":27,"text":383,"correct":29},"厂房与配电站的分隔采用无门、窗、洞口的防火墙",{"key":31,"text":385,"correct":29},"为观察设备，可在该配电站的防火墙上设置甲级防火窗",{"id":387,"libraryId":5,"type":55,"typeLabel":56,"stem":388,"options":389,"answer":20,"analysis":37},935513,"下列关于消防电梯前室设置的说法中，错误的是（ ）。",[390,392,394,396],{"key":20,"text":391,"correct":22},"住宅建筑单独设置的消防电梯前室，使用面积不应小于4.5m2",{"key":24,"text":393,"correct":29},"设置在仓库连廊的消防电梯外可不设置前室",{"key":27,"text":395,"correct":29},"消防电梯前室或合用前室的门应采用乙级防火门，不应设置卷帘",{"key":31,"text":397,"correct":29},"消防电梯前室应在首层直通室外或经过长度不大于30m的通道通向室外",{"id":399,"libraryId":5,"type":55,"typeLabel":56,"stem":400,"options":401,"answer":24,"analysis":37},935514,"某单层乙类厂房，采用预应力钢筋混凝土楼板，耐火极限为0．80h；屋顶承重构件采用不燃材料制作，耐火极限为1．00h；吊顶采用轻钢龙骨石膏板，耐火极限为0．20h；柱采用不燃材料制作，耐火极限为2．00h；厂房内设有自动喷水灭火系统全保护，该厂房的下列结构中，满足一级耐火等级建筑要求的是（ ）。",[402,404,406,408],{"key":20,"text":403,"correct":29},"预应力混凝土楼板",{"key":24,"text":405,"correct":22},"不燃性承重构件",{"key":27,"text":407,"correct":29},"轻钢龙骨石膏板吊顶",{"key":31,"text":409,"correct":29},"不燃性柱",{"id":411,"libraryId":5,"type":55,"typeLabel":56,"stem":412,"options":413,"answer":20,"analysis":37},935515,"对民用建筑内设备用房进行防火检查，下列检查结果中，不符合规定的是（ ）。",[414,416,418,420],{"key":20,"text":415,"correct":22},"首层的锅炉房靠外墙设置，采用耐火极限为2．00h的防火隔墙与其他部分分隔，在隔墙开设乙级防火门",{"key":24,"text":417,"correct":29},"设置在地下二层的柴油发电机房，设有总储存量为1m3的储油间",{"key":27,"text":419,"correct":29},"设置在地下一层的变压器室靠外墙设置，疏散门直通安全出口",{"key":31,"text":421,"correct":29},"设置在首层的消防控制室靠外墙设置，疏散门直通室外",{"id":423,"libraryId":5,"type":55,"typeLabel":56,"stem":424,"options":425,"answer":24,"analysis":37},935516,"对某橡胶制品厂的涂胶车间进行防火检查，查阅资料得知，该车间地上2层，耐火等级为一级，防火分区划分符合规范要求。该车间的下列做法中，符合现行国家消防技术标准要求的有（ ）。",[426,428,430,432],{"key":20,"text":427,"correct":29},"首层因生产需要，部分防火分区之间采用耐火极限为4．00h的防火卷帘分隔",{"key":24,"text":429,"correct":22},"为车间服务的10KV专用配电站贴邻车间建造，采用无门、窗、洞口的防火墙与车间分隔",{"key":27,"text":431,"correct":29},"设在一层的车间办公室采用耐火极限3．00h的防火墙与厂房分隔，并设有独立的安全出口",{"key":31,"text":433,"correct":29},"车间二层的防火分区之间采用耐火极限为3．00h的防火墙分隔",{"id":435,"libraryId":5,"type":55,"typeLabel":56,"stem":436,"options":437,"answer":27,"analysis":37},935517,"对某高层民用建筑进行防火检查时，下列检查结果中，不符合现行国家消防技术标准的是（ ）。",[438,440,442,444],{"key":20,"text":439,"correct":29},"该建筑消防车登高操作场地的长度大于建筑周边长度的1／4且大于建筑的一个长边（长边长度为20m），该范围内的裙房进深为4m",{"key":24,"text":441,"correct":29},"每个防火分区设置有一台消防电梯",{"key":27,"text":443,"correct":22},"消防电梯井与相邻电梯井之间采用2．00h的防火隔墙分隔，隔墙上开乙级防火门",{"key":31,"text":445,"correct":29},"消防车登高操作场地的坡度为2％",{"id":447,"libraryId":5,"type":55,"typeLabel":56,"stem":448,"options":449,"answer":31,"analysis":37},935518,"某 KTV 设置在建筑高度为 55m 的综合楼建筑的第 4 层,现公安机关消防机构对其进行防火检查,下列检查结果不符合相应规范要求的是（ ）。",[450,452,454,456],{"key":20,"text":451,"correct":29},"房间的建筑面积都没有超过 200m2",{"key":24,"text":453,"correct":29},"房间和房间之间采用了耐火极限为 2.00h 的防火隔墙分隔",{"key":27,"text":455,"correct":29},"位于两个安全出口之间的房间门至最近安全出口的距离为 20m",{"key":31,"text":457,"correct":22},"房间内设置了自喷和火灾报警系统,顶棚装修材料的燃烧性能等级为 B1 级的装修材料",{"id":459,"libraryId":5,"type":55,"typeLabel":56,"stem":460,"options":461,"answer":27,"analysis":37},935519,"人防工程中，地下商店营业厅不得设置在地下（ ）及以下。",[462,464,466,468],{"key":20,"text":463,"correct":29},"一层",{"key":24,"text":465,"correct":29},"二层",{"key":27,"text":467,"correct":22},"三层",{"key":31,"text":469,"correct":29},"四层",{"id":471,"libraryId":5,"type":55,"typeLabel":56,"stem":472,"options":473,"answer":27,"analysis":37},935520,"某铝合金冷加工厂房，地上2层，建筑高度12m。下列关于该厂房的平面布置，存在火灾隐患的是（ ）。",[474,476,478,480],{"key":20,"text":475,"correct":29},"在一层设置一间工人休息室，采用耐火极限为2．00h的防火隔墙与其他部位分隔",{"key":24,"text":477,"correct":29},"在二层中间设置一间铝合金条中间仓库，采用耐火极限2．00h的防火隔墙和1．50h的楼板与生产部位分隔",{"key":27,"text":479,"correct":22},"在二层设置一个容量为3m2的润滑油储罐，采用耐火极限2．50h的防火隔墙和甲级防火门与生产部位分隔",{"key":31,"text":481,"correct":29},"设置在厂房内的通风机房，采用耐火极限1．00h的防火隔墙和0．50h的楼板与其他部位分隔",{"id":483,"libraryId":5,"type":15,"typeLabel":16,"stem":484,"options":485,"answer":495,"analysis":37},935521,"下列属于人防工程中不允许设置的场所或设施的是（ ）",[486,488,490,492,493],{"key":20,"text":487,"correct":22},"哺乳室",{"key":24,"text":489,"correct":22},"托儿所",{"key":27,"text":491,"correct":22},"使用、储存液化石油气场所",{"key":31,"text":76,"correct":22},{"key":34,"text":494,"correct":29},"医院病房","ABCD",{"id":497,"libraryId":5,"type":15,"typeLabel":16,"stem":498,"options":499,"answer":510,"analysis":37},935522,"在人防工程中，对歌舞娱乐放映游艺场所进行消防安全检查的内容包括（ ）。",[500,502,504,506,508],{"key":20,"text":501,"correct":29},"采用耐火极限不低于2．00h的不燃体墙和耐火极限不低于1．00h的楼板与其他场所隔开，墙上必须开设的门为乙级防火门",{"key":24,"text":503,"correct":22},"布置在袋形走道的两侧或尽端时，最远房间的疏散门至最近安全出口的距离不大于9m",{"key":27,"text":505,"correct":22},"歌舞娱乐放映游艺场所不得布置在地下二层及二层以下",{"key":31,"text":507,"correct":29},"当布置在地下一层时，地下一层地面与室外出入口地坪的高差不大于8m",{"key":34,"text":509,"correct":29},"一个厅、室的建筑面积不大于100㎡","BC",{"id":512,"libraryId":5,"type":15,"typeLabel":16,"stem":513,"options":514,"answer":495,"analysis":37},935523,"某食用油加工厂，拟新建一座2层大豆油浸出车间，其耐火等级为二级，车间需设置与生产配套的浸出溶剂中间仓库、分控制室、办公室和专用10KV变电所。对该厂房进行总平面布局和平面布置时，不正确的有（ ）。",[515,517,519,521,523],{"key":20,"text":516,"correct":22},"办公室设置在厂房内，并与其他区域之间采用防火墙分隔",{"key":24,"text":518,"correct":22},"中间仓库在厂房内靠外墙布置，并采用防火墙和耐火极限不低于1．00h的不燃性楼板与其他部位分隔",{"key":27,"text":520,"correct":22},"容积15m3的丙类液体储罐设置在专用房间内，采用耐火极限3．00h的防火隔墙和1．50h的楼板与其他部位分隔，房间门采用乙级防火门",{"key":31,"text":522,"correct":22},"车间专用10KV变电所贴邻厂房建造，并采用防火墙与厂房分隔，防火墙上设置了耐火极限1．50h的观察窗",{"key":34,"text":524,"correct":29},"分控制室贴邻厂房外墙设置，并采用耐火极限为4．00h的防火墙与厂房分隔",{"id":526,"libraryId":5,"type":15,"typeLabel":16,"stem":527,"options":528,"answer":495,"analysis":37},935524,"在某次消防安全检查中，检查人员对以下场所进行了各项检查，下列选项中不符合规范要求的有（ ）。",[529,531,533,535,537],{"key":20,"text":530,"correct":22},"某氯酸钾生产厂房贴邻建造了办公室和休息室，办公室和休息室的建筑耐火等级经测定为二级，采用了耐火极限为3．00h的防火墙与厂房分隔，并设置的独立的安全出口",{"key":24,"text":532,"correct":22},"某服装加工厂房内部设置工人休息室，休息室采用耐火极限为2．00h的防火隔墙和耐火极限为1．00h的楼板与其他部位隔开，并采用乙级防火门与厂房连通",{"key":27,"text":534,"correct":22},"某储存乙醇的仓库，为了方便工人午间休息，贴邻建造了一个休息室，采用耐火极限为3．00h的防爆墙与仓库分隔",{"key":31,"text":536,"correct":22},"某谷物储存仓库，办公管理用房采用耐火极限为2．00h的防火隔墙和耐火极限为1．00h的楼板与其他部位分隔并设置了1个独立的安全出口，另一出口采用甲级防火门与仓库连通",{"key":34,"text":538,"correct":29},"某高锰酸钾厂房的专用10KV配电站与厂房贴邻设置，并采用无门、窗、洞口的防火墙 与厂房分隔",{"id":540,"libraryId":5,"type":15,"typeLabel":16,"stem":541,"options":542,"answer":553,"analysis":37},935525,"某单层厂房用于生产乙醇（总建筑面积6000㎡），下列关于其防火设计的描述中，正确的是（ ）。",[543,545,547,549,551],{"key":20,"text":544,"correct":29},"该厂房内采用耐火极限为3．00h的防火墙划分防火分区",{"key":24,"text":546,"correct":22},"与该厂房贴邻布置的办公室采用二级耐火等级且设有独立安全出口，两者之间采用耐火极限为3．00h的防爆墙分隔",{"key":27,"text":548,"correct":29},"为满足24小时值班需求，在该厂房内靠外墙侧设置一间有独立安全出口且仅住宿两人的宿舍",{"key":31,"text":550,"correct":29},"该厂房的10KV的专用变配电室设在厂房内靠外墙一角",{"key":34,"text":552,"correct":22},"该厂房外贴临设置一间一级耐火等级有独立安全出口的值班室，值班室与该厂房采用3．00h的防爆墙分隔","BE",{"id":555,"libraryId":5,"type":15,"typeLabel":16,"stem":556,"options":557,"answer":568,"analysis":37},935526,"下列有关厂房内防火分隔的描述中，表述正确的是（ ）。",[558,560,562,564,566],{"key":20,"text":559,"correct":22},"集成电路工厂内用于储存清洗零部件的化学溶剂中间仓库（使用闪点小于28℃的液体），采用4．00h的防火墙和耐火极限不低于1．50h的不燃性楼板与其他部位分隔",{"key":24,"text":561,"correct":29},"面粉厂碾磨车间内设置丙类中间仓库时应采用耐火极限不低于2．00h的防火隔墙与其他部位分隔，墙上的门、窗应采用乙级防火门、窗，确有困难时，可采用防火卷帘",{"key":27,"text":563,"correct":22},"木材加工厂房内的丙类中间仓库应采用防火墙和耐火极限不低于1．50h的不燃性楼板与其他部位分隔",{"key":31,"text":565,"correct":29},"蒸汽机车库内的丙类中间仓库应采用耐火极限不低于2．00h的防火隔墙与其他部位分隔，墙上的门、窗应采用乙级防火门、窗，确有困难时，可采用防火卷帘",{"key":34,"text":567,"correct":22},"甲类生产部位与丙类液体部位采用2．00h防火隔墙与其他部位隔开","ACE",{"id":570,"libraryId":5,"type":15,"typeLabel":16,"stem":571,"options":572,"answer":583,"analysis":37},935527,"关于附设在民用建筑内燃油、燃气锅炉房的平面布置，下列说法不正确的是（ ）。",[573,575,577,579,581],{"key":20,"text":574,"correct":29},"不应设置在人员密集场所的上一层、下一层或贴邻",{"key":24,"text":576,"correct":29},"应设置在首层或地下一层靠外墙部位",{"key":27,"text":578,"correct":22},"设在屋顶的常（负）压燃油锅炉与屋顶安全出口的距离应不大于6m",{"key":31,"text":580,"correct":29},"采用相对密度≥0．75的可燃气体的常（负）压燃气锅炉不得设置在地下、半地下",{"key":34,"text":582,"correct":22},"布置在首层时，疏散门应直通室外或疏散走道","CE",{"id":585,"libraryId":5,"type":15,"typeLabel":16,"stem":586,"options":587,"answer":598,"analysis":37},935528,"下列场所附设在民用建筑内时，应靠建筑外墙布置的有（ ）。",[588,590,592,594,596],{"key":20,"text":589,"correct":22},"变压器室",{"key":24,"text":591,"correct":29},"封闭楼梯间",{"key":27,"text":593,"correct":29},"歌舞娱乐场所",{"key":31,"text":595,"correct":29},"消防控制室",{"key":34,"text":597,"correct":22},"燃油锅炉房","AE",{"id":600,"libraryId":5,"type":15,"typeLabel":16,"stem":601,"options":602,"answer":612,"analysis":37},935529,"对民用建筑实施防火检查时，检查人员应注意查看特殊功能场所，下列不能设在地下的场所有（ ）。",[603,605,606,608,610],{"key":20,"text":604,"correct":22},"医院的住院部分",{"key":24,"text":593,"correct":29},{"key":27,"text":607,"correct":22},"儿童游乐场",{"key":31,"text":609,"correct":29},"消防水泵房",{"key":34,"text":611,"correct":29},"会议厅、多功能厅","AC",{"id":614,"libraryId":5,"type":15,"typeLabel":16,"stem":615,"options":616,"answer":627,"analysis":37},935530,"下列场所有关防火分隔的做法中，正确的有（ ）。",[617,619,621,623,625],{"key":20,"text":618,"correct":29},"某多层民用建筑，住宅部分与商业部分之间采用耐火极限为2．00h的防火隔墙和1．50h的不燃性楼板分隔，隔墙上开设的门为甲级防火门",{"key":24,"text":620,"correct":29},"某二类高层住宅建筑，一、二层为商业服务网点，其居住部分与商业服务网点之间采用耐火极限为2．00h且无门、窗、洞口的防火隔墙和1．00h的不燃性楼板分隔",{"key":27,"text":622,"correct":22},"某幼儿园设置在高层综合楼的首层至三层，幼儿园与其他部分之间采用耐火极限为2．00h的防火隔墙和1．00h的楼板分隔，墙上设置的门、窗采用乙级防火门、窗",{"key":31,"text":624,"correct":22},"附设在民用建筑内首层的消防控制室采用耐火极限2．00h的防火隔墙和1．5h的楼板与其他部位分隔",{"key":34,"text":626,"correct":22},"设置在某建筑首层的网吧，厅、室之间及与建筑的其他部位之间，采用耐火极限2．00h的防火隔墙和1．00h的不燃性楼板分隔","CDE",{"id":629,"libraryId":5,"type":15,"typeLabel":16,"stem":630,"options":631,"answer":642,"analysis":37},935531,"下列关于建筑防火分隔的做法中，不符合规范要求的是（ ）。",[632,634,636,638,640],{"key":20,"text":633,"correct":22},"某KTV各厅、室之间采用耐火极限为2．00h的防火隔墙和1．50h的不燃性楼板进行分隔，隔墙上开设乙级防火门",{"key":24,"text":635,"correct":22},"某民用建筑内柴油发电机房的储油间（柴油储量为0．8m3）采用耐火极限为2．50h的防火隔墙和1．5h的不燃性楼板及甲级防火门与其他部位分隔",{"key":27,"text":637,"correct":22},"某高层住宅建筑底部设置商业服务网点，与住宅部分之间采用耐火极限为2．50h且无门、窗、洞口的防火隔墙和1．00h的不燃性楼板与其他部位分隔",{"key":31,"text":639,"correct":29},"某医院病房楼内相邻护理单元之间采用耐火极限为2．00h的防火隔墙和乙级防火门分隔",{"key":34,"text":641,"correct":22},"某高层建筑下部为商场，上部为住宅，商场采用防火墙和耐火极限为2．00h的不燃性楼板与上部住宅进行防火分隔，商场与住宅之间采用甲级防火门相连通","ABCE",{"id":644,"libraryId":5,"type":15,"typeLabel":16,"stem":645,"options":646,"answer":657,"analysis":37},935532,"对某厂的谷物碾磨车间进行防火检查，查阅资料得知，该车间耐火等级为一级防火分区划分，符合规范要求。该车间的下列做法中，符合现行国家消防技术标准要求的有（ ）。",[647,649,651,653,655],{"key":20,"text":648,"correct":29},"配电站设于厂内的一层，采用防火墙和耐火极限为1．50 h的楼板与其他区域分隔墙上的门为甲级防火门",{"key":24,"text":650,"correct":29},"位于厂房三层的运行调度监控室采用防火墙和耐火极限为1．50 h的楼板与其他部分分隔，且设有独立使用的防烟楼梯间",{"key":27,"text":652,"correct":29},"车间办公室贴邻厂房外墙设置，采用耐火极限为4．00 h的防火墙与厂房分隔，并设有独立的安全出口",{"key":31,"text":654,"correct":22},"设置在一层的产品临时存放仓库单独划分防火分区",{"key":34,"text":656,"correct":22},"位于二层的饲料添加剂仓库（丙类）采用防火墙和耐火极限为1．50 h的楼板与其他部位分隔，墙上的门为甲级防火门","DE",[659,662,665,668,671,674],{"id":55,"name":660,"category":7,"favorite":661},"领导干部任职前廉政法规知识测试题",92,{"id":663,"name":664,"category":7,"favorite":55},595,"建筑结构与设备",{"id":666,"name":667,"category":7,"favorite":55},715,"招标采购专业知识与法律法规",{"id":669,"name":670,"category":7,"favorite":55},848,"市政方向-通用基础",{"id":672,"name":673,"category":7,"favorite":8},534,"BIM工程师",{"id":675,"name":673,"category":7,"favorite":8},535]