[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-605-15":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":653},{"id":5,"name":6,"category":7,"favorite":8},605,"消防技术综合能力(一级、二级)","建筑工程",0,15,50,2974,[13,34,46,58,70,82,94,106,118,130,142,154,172,187,202,217,229,241,252,264,276,286,298,310,322,332,344,356,368,380,392,404,416,428,440,452,464,476,486,498,510,522,537,552,567,582,596,610,625,639],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":24,"analysis":33},935383,1,"单选题","某独立建造且建筑总面积为300㎡的地上2层氧气站，其耐火等级最低可采用（ ）。",[19,23,27,30],{"key":20,"text":21,"correct":22},"A","一级",false,{"key":24,"text":25,"correct":26},"B","二级",true,{"key":28,"text":29,"correct":22},"C","三级",{"key":31,"text":32,"correct":22},"D","四级","",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":31,"analysis":33},935384,"某高锰酸钾厂房的耐火等级为二级，则其建筑层数不应大于（ ）层。",[38,40,42,44],{"key":20,"text":39,"correct":22},"3",{"key":24,"text":41,"correct":22},"4",{"key":28,"text":43,"correct":22},"5",{"key":31,"text":45,"correct":26},"6",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":31,"analysis":33},935385,"下列关于厚型钢结构防火涂料的检查说法中，错误的是（ ）。",[50,52,54,56],{"key":20,"text":51,"correct":22},"现场选取至少五个不同的涂层部位，用测厚仪分别测量其厚度",{"key":24,"text":53,"correct":22},"涂层厚度应为测点厚度的平均值",{"key":28,"text":55,"correct":22},"目测涂层无开裂、脱落，则涂层外观合格",{"key":31,"text":57,"correct":26},"现场已施工的涂层厚度不应大于型式检验报告描述的厚度",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":28,"analysis":33},935386,"一建筑物室外地面至顶部屋面高度为23m，顶部屋面面积为200m2，有局部突出屋顶的若干辅助用房，该辅助用房高度为2m，面积为60m2，按照国家消防工程技术标准规定，该建筑物的高度为（ ）。",[62,64,66,68],{"key":20,"text":63,"correct":22},"23",{"key":24,"text":65,"correct":22},"24",{"key":28,"text":67,"correct":26},"25",{"key":31,"text":69,"correct":22},"26",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":31,"analysis":33},935387,"建筑主要构件的燃烧性能和耐火极限不得低于建筑相应耐火等级的要求。下列关于建筑耐火等级检查要求的说法，错误的是（ ）。",[74,76,78,80],{"key":20,"text":75,"correct":22},"一级耐火等级建筑的主要构件都是不燃烧体",{"key":24,"text":77,"correct":22},"二级耐火等级建筑的主要构件，除吊顶为难燃体外，其余构件都是不燃体",{"key":28,"text":79,"correct":22},"三级耐火等级建筑的主要构件，除吊顶和隔墙体为难燃体外，民用建筑的屋顶承重构件还可以采用可燃体",{"key":31,"text":81,"correct":26},"四级耐火等级建筑的主要构件，全部构件可采用难燃体或可燃体",{"id":83,"libraryId":5,"type":15,"typeLabel":16,"stem":84,"options":85,"answer":31,"analysis":33},935388,"机械修配厂或修理车间，使用少量的汽油等甲类溶剂清洗零件，该厂房的火灾危险性按（ ）类考虑。",[86,88,90,92],{"key":20,"text":87,"correct":22},"乙",{"key":24,"text":89,"correct":22},"丙",{"key":28,"text":91,"correct":22},"丁",{"key":31,"text":93,"correct":26},"戊",{"id":95,"libraryId":5,"type":15,"typeLabel":16,"stem":96,"options":97,"answer":31,"analysis":33},935389,"某18层商住楼，一二层为商业服务网点；三到十八层为单元式住宅，住宅为平屋面。室外设计地面至屋面面层的高度为54．5m，首层室内标高为+0．00m，室外标高为-0．6m，则该建筑的建筑类别为（ ）。",[98,100,102,104],{"key":20,"text":99,"correct":22},"二类高层公共建筑",{"key":24,"text":101,"correct":22},"单、多层民用建筑",{"key":28,"text":103,"correct":22},"一类高层住宅建筑",{"key":31,"text":105,"correct":26},"二类高层住宅建筑",{"id":107,"libraryId":5,"type":15,"typeLabel":16,"stem":108,"options":109,"answer":24,"analysis":33},935390,"厂房的火灾危险性类别是以生产过程中使用和产出物质的火灾危险性类别确定的，对生产场所进行防火检查时，发现的下列做法中，不符合现行国家消防技术标准的是（ ）。",[110,112,114,116],{"key":20,"text":111,"correct":22},"一般情况下，同一座厂房或同一个防火分区内的生产火灾危险性类别应按火灾危险性较大的部分确定",{"key":24,"text":113,"correct":26},"木器加工厂房内油漆工段占本层或本防火分区比例为8％，且发生火灾事故时不足以蔓延至其他部位或火灾危险性较大的生产部分采取了有效的防火措施，厂房的火灾危险性可以确定为丙类",{"key":28,"text":115,"correct":22},"陶瓷制品厂房内火灾危险性较大的生产部分占本层或本防火分区建筑面积的比例为3％，厂房的火灾危险性为丁类",{"key":31,"text":117,"correct":22},"仪表加工厂房内的油漆工段占所在防火分区建筑面积的比例为15％，采用封闭喷漆工艺，封闭喷漆空间内保持负压、油漆工段设置可燃气体探测报警系统时，该厂房的火灾危险性为戊类",{"id":119,"libraryId":5,"type":15,"typeLabel":16,"stem":120,"options":121,"answer":24,"analysis":33},935391,"某百货仓库，同时储存有蜡烛、白糖、白兰地酒、漂白粉、及棉麻针织物，分别占该仓库建筑面积的20％。对该仓库进行防火检查时，该仓库的火灾危险性应确定为（ ）。",[122,124,126,128],{"key":20,"text":123,"correct":22},"甲类",{"key":24,"text":125,"correct":26},"乙类",{"key":28,"text":127,"correct":22},"丙类",{"key":31,"text":129,"correct":22},"丁类",{"id":131,"libraryId":5,"type":15,"typeLabel":16,"stem":132,"options":133,"answer":28,"analysis":33},935392,"消防检测机构在对某建筑物的耐火等级、主要建筑构件的燃烧性能和耐火极限开展现场检查,下列关于钢结构防火涂料检查结果,不符合要求的是（ ）。",[134,136,138,140],{"key":20,"text":135,"correct":22},"耐火等级为二级的多层厂房,屋顶承重为钢结构,选用薄涂型钢结构防火涂料",{"key":24,"text":137,"correct":22},"薄涂型钢结构防火涂层表面有个别裂缝,其宽度 0.3mm",{"key":28,"text":139,"correct":26},"厚涂型钢结构防火涂层最薄处厚度不低于为设计要求的 85%",{"key":31,"text":141,"correct":22},"薄型（膨胀型）钢结构防火涂料的膨胀倍数为 5",{"id":143,"libraryId":5,"type":15,"typeLabel":16,"stem":144,"options":145,"answer":24,"analysis":33},935393,"（ ）级耐火等级建筑的主要构件，除吊顶为难燃烧体外，其余构件都是不燃烧体。",[146,148,150,152],{"key":20,"text":147,"correct":22},"一",{"key":24,"text":149,"correct":26},"二",{"key":28,"text":151,"correct":22},"三",{"key":31,"text":153,"correct":22},"四",{"id":155,"libraryId":5,"type":156,"typeLabel":157,"stem":158,"options":159,"answer":171,"analysis":33},935394,2,"多选题","对钢结构防火涂料进行检查时，主要进行（）操作。",[160,162,164,166,168],{"key":20,"text":161,"correct":22},"检查涂料防水性能",{"key":24,"text":163,"correct":26},"检查涂层外观",{"key":28,"text":165,"correct":26},"检查膨胀倍数",{"key":31,"text":167,"correct":26},"检查涂层厚度",{"key":169,"text":170,"correct":22},"E","检查表面裂纹","BCD",{"id":173,"libraryId":5,"type":156,"typeLabel":157,"stem":174,"options":175,"answer":186,"analysis":33},935395,"下列关于建筑分类的描述中，表述正确的是（ ）。",[176,178,180,182,184],{"key":20,"text":177,"correct":22},"建筑高度28m的医疗建筑,每层建筑面积均不大于1000㎡，属于二类高层公共建筑",{"key":24,"text":179,"correct":26},"某建筑地上10层，首层分隔为多个建筑面积不超过300㎡的商业性服务用房，其他楼层的使用功能为住宅，其建筑类别为住宅建筑",{"key":28,"text":181,"correct":22},"某民用建筑首层设置多个营业性用房，分别为理发店（280㎡），小商店（150㎡），邮政所（310㎡），该建筑为住宅建筑",{"key":31,"text":183,"correct":22},"与某高层建筑主体相连的附属建筑，建筑高度为25m，该附属建筑为其裙房",{"key":169,"text":185,"correct":26},"某综合楼，建筑高度35m，层高5m，标准层建筑面积为1100㎡，该建筑为一类高层公共建筑","BE",{"id":188,"libraryId":5,"type":156,"typeLabel":157,"stem":189,"options":190,"answer":201,"analysis":33},935396,"某单层空分厂房，平屋面可上人，设计图纸上显示耐火等级为一级，消防机构对该厂房构件的耐火性能进行检查，结果如下：厂房柱的耐火极限为2．50h，屋面板采用预应力钢筋混凝土，耐火极限0．75h，钢结构屋顶承重构件采用防火涂料涂刷，耐火极限为1．00h，吊顶采用轻钢龙骨石膏板，耐火极限0．15h，防火墙的耐火极限为3．00h，厂房内设有自动喷水灭火系统全保护，则该厂房的下列建筑构件中，不满足该厂房耐火等级要求的是（ ）。",[191,193,195,197,199],{"key":20,"text":192,"correct":26},"预应力混凝土屋面板",{"key":24,"text":194,"correct":22},"柱",{"key":28,"text":196,"correct":22},"钢结构屋顶承重构件",{"key":31,"text":198,"correct":26},"轻钢龙骨石膏板吊顶",{"key":169,"text":200,"correct":26},"防火墙","ADE",{"id":203,"libraryId":5,"type":156,"typeLabel":157,"stem":204,"options":205,"answer":216,"analysis":33},935397,"在建筑物和构筑物钢结构构件表面涂刷钢结构防火涂料，形成耐火隔热保护层，以提高钢结构耐火极限。在对钢结构防火涂料进行检查时，符合规范要求的情况包括（ ）。",[206,208,210,212,214],{"key":20,"text":207,"correct":26},"设计耐火极限为1．00h时，选用薄涂型钢结构防火涂料",{"key":24,"text":209,"correct":26},"设计耐火极限为2.00 h的室内隐蔽钢结构，选用厚涂型钢结构防火涂料",{"key":28,"text":211,"correct":22},"厚涂型钢结构防火涂层最薄处厚度为设计要求的80％，厚度不足部位的连续面积的长度为1 m，并在5 m范围内未出现类似情况",{"key":31,"text":213,"correct":26},"薄涂型钢结构防火涂层表面有少量裂缝，其最大宽度为0．4 mm",{"key":169,"text":215,"correct":22},"通过汽油喷灯测试，测得超薄型钢结构防火涂料的膨胀倍数为8倍","ABD",{"id":218,"libraryId":5,"type":15,"typeLabel":16,"stem":219,"options":220,"answer":20,"analysis":33},935398,"下列场所应设置环形消防车道的是（ ）。",[221,223,225,227],{"key":20,"text":222,"correct":26},"建筑高度28m的住宅建筑",{"key":24,"text":224,"correct":22},"占地面积为3000㎡的多层商店建筑",{"key":28,"text":226,"correct":22},"占地面积为3500㎡的多层氟利昂厂房",{"key":31,"text":228,"correct":22},"占地面积为1500㎡的白兰地成品仓库",{"id":230,"libraryId":5,"type":15,"typeLabel":16,"stem":231,"options":232,"answer":20,"analysis":33},935399,"下列关于消防车登高操作场地和救援窗的说法中，正确的是（ ）。",[233,235,237,239],{"key":20,"text":234,"correct":26},"高层建筑至少沿一个长边或周边长度的1／4且不小于一个长边长度的底边连续布置消防车登高操作场地，该范围内裙房的进深不应大于4m",{"key":24,"text":236,"correct":22},"场地的坡度不宜大于8％，场地靠建筑外墙一侧的边缘距离建筑外墙不宜小于5m，且不应大于10m",{"key":28,"text":238,"correct":22},"消防登高操作场地的长度和宽度分别不小于15m和10m，对于建筑高度大于50m的建筑，场地的长度和宽度分别不应小于20m和15m",{"key":31,"text":240,"correct":22},"供消防救援人员进入的窗口的净高度和净宽度均不应小于1．2m，下沿距室内地面不宜大于1．0m，间距不宜大于20m且每个防火分区不应少于2个",{"id":242,"libraryId":5,"type":15,"typeLabel":16,"stem":243,"options":244,"answer":20,"analysis":33},935400,"某一级耐火等级的52度白酒灌装车间与三级耐火等级多层民用建筑的防火间距不应小于（ ）m。",[245,246,248,250],{"key":20,"text":67,"correct":26},{"key":24,"text":247,"correct":22},"16",{"key":28,"text":249,"correct":22},"30",{"key":31,"text":251,"correct":22},"20",{"id":253,"libraryId":5,"type":15,"typeLabel":16,"stem":254,"options":255,"answer":28,"analysis":33},935401,"在建筑高度为100m的综合楼北侧有一栋高度为24m的办公楼，综合楼北面的外墙为防火墙，其防火间距（ ）。",[256,258,260,262],{"key":20,"text":257,"correct":22},"大于等于9m",{"key":24,"text":259,"correct":22},"大于等于4m",{"key":28,"text":261,"correct":26},"不限",{"key":31,"text":263,"correct":22},"大于等于3．5m",{"id":265,"libraryId":5,"type":15,"typeLabel":16,"stem":266,"options":267,"answer":31,"analysis":33},935402,"某汽车加工厂房，地上5层，首层为汽车组装车间，二层为汽车电子加工车间，三层为汽车座椅加工车间，四层至五层为汽车零部件加工车间，设有环形消防车道，消防服务机构对该厂房进行防火检查，结果如下，其中不符合现行国家技术标准的是（ ）。",[268,270,272,274],{"key":20,"text":269,"correct":22},"首层靠外墙部分设置办公室、员工休息室，采用耐火极限为3．0h的防火隔墙与1．5h的不燃性楼板其他部位分隔",{"key":24,"text":271,"correct":22},"顶层靠外墙部位设丙类液体中间储罐，储存容量为4m3，采用3．0h的防火分隔与1．5h的不燃性楼板其他部位分隔，连通处开始甲级防火门",{"key":28,"text":273,"correct":22},"消防车道的净宽和净高均为5m，距建筑外墙的距离为12m",{"key":31,"text":275,"correct":26},"消防救援场地距建筑距离为8m，坡度为5％",{"id":277,"libraryId":5,"type":15,"typeLabel":16,"stem":278,"options":279,"answer":24,"analysis":33},935403,"某居民小区，由于周边市政配套设施不齐全，该小区采用瓶装液化石油气瓶组供气。小区外建造有单独的瓶组间，气瓶的总容积为3m3，则该瓶组间与小区锅炉房的防火间距应不小于（ ）m。",[280,281,282,284],{"key":20,"text":67,"correct":22},{"key":24,"text":249,"correct":26},{"key":28,"text":283,"correct":22},"50",{"key":31,"text":285,"correct":22},"10",{"id":287,"libraryId":5,"type":15,"typeLabel":16,"stem":288,"options":289,"answer":31,"analysis":33},935404,"某综合楼，地上6层，地下2层，标准层建筑面积为3000㎡，层高均为6米，地上每层划分为一个防火分区。消防机构对该综合楼进行消防安全检查，下列检查结果中不符合规范要求的是（ ）。",[290,292,294,296],{"key":20,"text":291,"correct":22},"地下一层为商场，最大一个防火分区的面积为1000㎡",{"key":24,"text":293,"correct":22},"地上三层为KTV，包间面积为300㎡",{"key":28,"text":295,"correct":22},"地下二层为电影院，设置了一个独立的安全出口",{"key":31,"text":297,"correct":26},"地上二层为儿童游乐场，设置了一个独立的安全出口",{"id":299,"libraryId":5,"type":15,"typeLabel":16,"stem":300,"options":301,"answer":28,"analysis":33},935405,"消防机构对下列场所进行消防安全检查，检查结果中不符合规范要求的（ ）。",[302,304,306,308],{"key":20,"text":303,"correct":22},"某电影院采用耐火极限为2．00h的防火隔墙和甲级防火门与其他区域分隔",{"key":24,"text":305,"correct":22},"某民用建筑内的锅炉房与其他部位之间采用耐火极限为2．00h的防火隔墙和1．50h的不燃性楼板分隔",{"key":28,"text":307,"correct":26},"某柴油发电机房内的储油间采用耐火极限为2．00h的防火隔墙和1．50h的不燃性楼板与发电机间分隔",{"key":31,"text":309,"correct":22},"变压器室与配电室之间，采用耐火极限不低于2．00h的防火隔墙分隔",{"id":311,"libraryId":5,"type":15,"typeLabel":16,"stem":312,"options":313,"answer":20,"analysis":33},935406,"某综合楼，地上5层，地下2层，标准层建筑面积为2600㎡，层高均为6m。消防机构对该综合楼进行消防检查，下列检查结果中符合规范要求的是（ ）。",[314,316,318,320],{"key":20,"text":315,"correct":26},"地上四层为会议厅，最大一个房间的面积为260㎡",{"key":24,"text":317,"correct":22},"地下二层设置有歌舞娱乐场所",{"key":28,"text":319,"correct":22},"地下二层设置有消防水泵房",{"key":31,"text":321,"correct":22},"地上一层为老年人活动场所，设置了一个独立的安全出口",{"id":323,"libraryId":5,"type":15,"typeLabel":16,"stem":324,"options":325,"answer":24,"analysis":33},935407,"某钢铁冶金企业，建筑防火要求露天布置的可燃气体与不可燃气体固定容积储罐之间的净距不得小于（ ）m。",[326,328,330,331],{"key":20,"text":327,"correct":22},"1",{"key":24,"text":329,"correct":26},"2",{"key":28,"text":43,"correct":22},{"key":31,"text":45,"correct":22},{"id":333,"libraryId":5,"type":15,"typeLabel":16,"stem":334,"options":335,"answer":28,"analysis":33},935408,"某L形沿街建筑，其沿街道部分的长度为200m，该建筑的消防车道为（ ）。",[336,338,340,342],{"key":20,"text":337,"correct":22},"尽头式消防车道",{"key":24,"text":339,"correct":22},"环形消防车道",{"key":28,"text":341,"correct":26},"穿越建筑的消防车道",{"key":31,"text":343,"correct":22},"与环形消防车道相连的中间消防车道",{"id":345,"libraryId":5,"type":15,"typeLabel":16,"stem":346,"options":347,"answer":24,"analysis":33},935409,"城市消防站的布置应结合城市交通状况和各区域的火灾危险性进行合理布局；街区道路布置和市政消火栓的布局应能满足灭火救援的需要，街区道路中心线间距离一般在（ ）m以内，市政消火栓沿可通行消防车的街区道路布置，间距不得大于（ ）m。",[348,350,352,354],{"key":20,"text":349,"correct":22},"150，110",{"key":24,"text":351,"correct":26},"160，120",{"key":28,"text":353,"correct":22},"150，120",{"key":31,"text":355,"correct":22},"160，110",{"id":357,"libraryId":5,"type":15,"typeLabel":16,"stem":358,"options":359,"answer":24,"analysis":33},935410,"在对某化工厂的电解食盐车间进行防火检查时，查阅资料得知，该车间耐火等级为一级。该车间的下列做法中，不符合现行国家消防技术标准的是（ ）。",[360,362,364,366],{"key":20,"text":361,"correct":22},"丙类中间仓库设置在该车间的地上二层",{"key":24,"text":363,"correct":26},"该车间生产线贯通地下一层到地上三层",{"key":28,"text":365,"correct":22},"丙类中间仓库与其他部位的分隔墙为耐火极限4．00 h的防火墙",{"key":31,"text":367,"correct":22},"丙类中间仓库无独立的安全出口",{"id":369,"libraryId":5,"type":15,"typeLabel":16,"stem":370,"options":371,"answer":31,"analysis":33},935411,"在检查消防车道设置的过程中，不符合规范要求的做法是（ ）。",[372,374,376,378],{"key":20,"text":373,"correct":22},"河道边临空建造的高层民用建筑，消防车道沿建筑的一个长边设置，且该长边所在建筑立面为消防车登高操作面",{"key":24,"text":375,"correct":22},"消防车道的净宽度和净空高度均为4．5m",{"key":28,"text":377,"correct":22},"消防车道的坡度为7％",{"key":31,"text":379,"correct":26},"高层民用建筑尽头式消防车道的回车场面积为12m×12m",{"id":381,"libraryId":5,"type":15,"typeLabel":16,"stem":382,"options":383,"answer":24,"analysis":33},935412,"对某高层建筑供消防救援人员进入的窗口进行防火检查，下列检查结果中，不符合规范要求的是（ ）。",[384,386,388,390],{"key":20,"text":385,"correct":22},"设置位置与消防车登高操作场地相对应",{"key":24,"text":387,"correct":26},"每个防火分区设有3个入口，间距为25m",{"key":28,"text":389,"correct":22},"入口的净宽和净高均为1．2m",{"key":31,"text":391,"correct":22},"入口下沿距室内高度为1．0m",{"id":393,"libraryId":5,"type":15,"typeLabel":16,"stem":394,"options":395,"answer":31,"analysis":33},935413,"对厂房进行防火检查时，应核查厂房的平面布置情况，某针织品厂的印染厂房下列做法中，符合规范要求的是（ ）。",[396,398,400,402],{"key":20,"text":397,"correct":22},"厂房内设置休息室，采用耐火极限为2．00h的防火隔墙和1．5h的不燃性楼板与生产车间分隔，并设置独立出口",{"key":24,"text":399,"correct":22},"厂房内设置丙类液体中间储罐的房间，并采用耐火极限为3．00h的防火隔墙与生产车间分隔，连通生产车间的门采用乙级防火门",{"key":28,"text":401,"correct":22},"厂房内设置办公室，采用耐火极限为2．50h的防火隔墙和1．5h的不燃性楼板与生产车间分隔，并通过车间疏散通道进行安全疏散",{"key":31,"text":403,"correct":26},"靠外墙设置存放丙类原料的中间仓库，储量为2昼夜的量，采用防火墙与生产区分隔",{"id":405,"libraryId":5,"type":15,"typeLabel":16,"stem":406,"options":407,"answer":28,"analysis":33},935414,"对某服装加工厂房进行防火检查时，通过查阅资料得知，该建筑的耐火等级为二级，地上6层，地下1层，层高5m，每层建筑面积6000m2，按照相关规定设置了相应的消防设施。下列做法中，不符合现行国家消防技术标准的是（ ）。",[408,410,412,414],{"key":20,"text":409,"correct":22},"设在二层的车间，划分为2个防火分区",{"key":24,"text":411,"correct":22},"设在地下的车间防火分区之间采用3．00h的防火墙",{"key":28,"text":413,"correct":26},"设在地上三层为厂房服务的丙类中间仓库，采用耐火极限为3．00h的防火隔墙和1．5h的不燃性楼板与其他部位分隔",{"key":31,"text":415,"correct":22},"设在首层的车间防火分区之间部分采用3．00h的防火卷帘分隔",{"id":417,"libraryId":5,"type":15,"typeLabel":16,"stem":418,"options":419,"answer":28,"analysis":33},935415,"某地上5层商业建筑，层高4m，耐火等级为一级，使用性质为商场、游艺厅、电影院儿童游乐场、餐饮场所等，对该商业建筑进行防火检查时，检查结果如下，其中不符合规定的是（ ）。",[420,422,424,426],{"key":20,"text":421,"correct":22},"位于地上二层的电影院观众厅建筑面积分别为120-430m2不等，采用耐火极限为2．00h的防火隔墙分隔",{"key":24,"text":423,"correct":22},"位于地上四层的游艺厅采用耐火极限为2．00h的防火隔墙和1．50h的不燃性楼板分隔，设置在厅、室墙上的门采用乙级防火门",{"key":28,"text":425,"correct":26},"位于地上五层的餐厅（含具有卡拉OK功能）采用耐火极限为2．00h的防火隔墙分隔为多个建筑面积为60-240m2的房间",{"key":31,"text":427,"correct":22},"位于地上三层的儿童游乐场采用耐火极限为2．00h的防火隔墙与其他场所或部位分隔，墙上开设乙级防火门",{"id":429,"libraryId":5,"type":15,"typeLabel":16,"stem":430,"options":431,"answer":31,"analysis":33},935416,"对某高层办公建筑设置的环形消防车道进行检查时，下列结果，不符合规范要求的是（ ）。",[432,434,436,438],{"key":20,"text":433,"correct":22},"该消防车道的坡度为5％",{"key":24,"text":435,"correct":22},"距建筑外墙的距离为12m",{"key":28,"text":437,"correct":22},"该车道的净空高和净宽分别均为4．2m",{"key":31,"text":439,"correct":26},"该消防车道有一处与其他车道连通",{"id":441,"libraryId":5,"type":15,"typeLabel":16,"stem":442,"options":443,"answer":31,"analysis":33},935417,"对民用建筑的设备用房进行防火检查，下列检查结果不符合现行国家消防技术标准的是（ ）。",[444,446,448,450],{"key":20,"text":445,"correct":22},"设置在地下二层的柴油发电机房设有储油间 ，采用耐火极限为3．00h的防火隔墙与发电机间分隔",{"key":24,"text":447,"correct":22},"设置在地下一层的变压器室与配电室之间，采用耐火极限为2．00h的防火隔墙",{"key":28,"text":449,"correct":22},"设置在地下二层的消防水泵房疏散门直通安全出口",{"key":31,"text":451,"correct":26},"设置在地下二层的燃气锅炉房，采用相对密度（与空气密度的比值）为0．75的可燃气体为燃料，设有直通室外的安全出口",{"id":453,"libraryId":5,"type":15,"typeLabel":16,"stem":454,"options":455,"answer":31,"analysis":33},935418,"对仓库进行防火检查时，应检查仓库的占地面积和防火分区面积。下列说法中，错误的是（ ）。",[456,458,460,462],{"key":20,"text":457,"correct":22},"除冷库外，当仓库内设置自动灭火系统时，每座仓库的最大允许占地面积可按规定值增加 1.0 倍",{"key":24,"text":459,"correct":22},"除冷库外，当仓库内设置自动灭火系统时，每座仓库的每个防火分区最大允许建筑面积可按规定值增加1.0 倍",{"key":28,"text":461,"correct":22},"地下或半地下仓库的最大允许占地面积，不应大于相应类别地上仓库的最大允许占地面积",{"key":31,"text":463,"correct":26},"当仓库划分多个防火分区时，每座仓库的总建筑面积不应大于该仓库最大允许占地面积的规定值",{"id":465,"libraryId":5,"type":15,"typeLabel":16,"stem":466,"options":467,"answer":28,"analysis":33},935419,"下列关于厂房内中间仓库平面布置的做法中，错误的是（ ）。",[468,470,472,474],{"key":20,"text":469,"correct":22},"某甲类中间仓库靠外墙布置，其储量为 1 昼夜的需要量",{"key":24,"text":471,"correct":22},"某乙类中间仓库采用防火墙和耐火极限为 1.50h 的不燃性楼板与其他部位分隔",{"key":28,"text":473,"correct":26},"某丙类中间仓库应采用耐火极限为 3.00h 的防火隔墙和 1.00h 的不燃性楼板与其他部位分隔",{"key":31,"text":475,"correct":22},"某丁类中间仓库采用耐火极限为 2.00h 的防火隔墙和 1.00h 的楼板与其他部位分隔",{"id":477,"libraryId":5,"type":15,"typeLabel":16,"stem":478,"options":479,"answer":31,"analysis":33},935420,"当一座设置有自动喷水灭火系统的单层二级耐火等级 U 形沥青加工厂房的占地面积15000 ㎡时，厂房中相邻两翼之间的防火间距可为（ ）m。",[480,481,483,485],{"key":20,"text":285,"correct":22},{"key":24,"text":482,"correct":22},"8",{"key":28,"text":484,"correct":22},"7",{"key":31,"text":45,"correct":26},{"id":487,"libraryId":5,"type":15,"typeLabel":16,"stem":488,"options":489,"answer":31,"analysis":33},935421,"下列关于石油化工企业总平面布置的做法中，错误的是（ ）。",[490,492,494,496],{"key":20,"text":491,"correct":22},"厂区主要出入口不少于两个，并设置在不同方位",{"key":24,"text":493,"correct":22},"可能散发可燃气体的工艺装置、罐组、装卸区或全厂性污水处理场等设施，宜布置在人员集中场所及明火或散发火花地点的全年最小频率风向的上风侧",{"key":28,"text":495,"correct":22},"工艺装置区，液化烃储罐区、可燃液体储罐区、装卸区及化学危险仓库区按规定设置环形消防车道",{"key":31,"text":497,"correct":26},"消防站的设置位置便于消防车迅速通往工艺装置区和罐区，宜位于生产区全年最大频率风向的下风侧",{"id":499,"libraryId":5,"type":15,"typeLabel":16,"stem":500,"options":501,"answer":31,"analysis":33},935422,"有爆炸危险厂房的平面布置，主要检查有爆炸危险的甲、乙类生产部位和设备、疏散楼梯、办公室和休息室、排风设备在厂房内的布置。下列有爆炸危险厂房的平面布置不符合现行国家工程消防技术标准的是（ ）。",[502,504,506,508],{"key":20,"text":503,"correct":22},"有爆炸危险的甲、乙类生产部位，布置在单层厂房靠外墙的泄压设施或多层厂房顶层靠外墙的泄压设施附近",{"key":24,"text":505,"correct":22},"有爆炸危险的设备避开厂房的梁、柱等主要承重构件布置",{"key":28,"text":507,"correct":22},"在爆炸危险区域内的楼梯间、室外楼梯或与相邻区域连通处，设置门斗等防护措施",{"key":31,"text":509,"correct":26},"办公室、休息室不得布置在有爆炸危险的甲、乙类厂房内，也不得贴邻布置在厂房附近",{"id":511,"libraryId":5,"type":15,"typeLabel":16,"stem":512,"options":513,"answer":20,"analysis":33},935423,"某住宅建筑高度 49m，每层建筑面积为 30m × 50m，下列该住宅楼消防车道及救援场地的设计，不符合规范要求的是（ ）。",[514,516,518,520],{"key":20,"text":515,"correct":26},"沿建筑的一个长边设置消防车道，并沿一个短边和部分长边连续布置消防车登高操作场地",{"key":24,"text":517,"correct":22},"消防车道的净宽度和净空高度均为 4m",{"key":28,"text":519,"correct":22},"沿建筑的两个长边设置消防车道，消防车登高操作场地长度和宽度分别为 15m 和 10m，间隔距离 30m",{"key":31,"text":521,"correct":22},"与消防车登高操作场地相对应的范围内，设置直通楼梯间的入口",{"id":523,"libraryId":5,"type":156,"typeLabel":157,"stem":524,"options":525,"answer":536,"analysis":33},935424,"下列关于锅炉房的布置，不符合规范要求的是（ ）。",[526,528,530,532,534],{"key":20,"text":527,"correct":26},"某煤粉锅炉的锅炉房设置在住宅建筑首层靠外墙部位（住宅首层为自行车库）",{"key":24,"text":529,"correct":26},"设置在住宅建筑地下二层的常（负）压燃油锅炉房通过建筑内设置的中央空调系统通风换气",{"key":28,"text":531,"correct":26},"设置在住宅建筑内，采用相对密度为0．8的气体为燃料的燃气锅炉房设置在地下一层靠外墙部位",{"key":31,"text":533,"correct":26},"设置在住宅建筑内的燃气锅炉房，其疏散门经过相邻变压器室后再经过一段8m长的疏散走道通向室外",{"key":169,"text":535,"correct":22},"设置在某二类高层住宅建筑内的燃气锅炉房设置了火灾自动报警系统","ABCD",{"id":538,"libraryId":5,"type":156,"typeLabel":157,"stem":539,"options":540,"answer":551,"analysis":33},935425,"下列关于幼儿用房设置的做法错误的是（ ）。",[541,543,545,547,549],{"key":20,"text":542,"correct":26},"幼儿园的儿童用房设置在公共建筑第三层，该建筑非承重外墙采用耐火极限为0．50h的不燃材料",{"key":24,"text":544,"correct":22},"儿童游乐场设在建筑高度为26m综合楼的第三层",{"key":28,"text":546,"correct":26},"幼儿早教中心设在地下一层",{"key":31,"text":548,"correct":26},"儿童游乐厅设在高层综合楼内，该楼层有2部疏散楼梯，其中一部供幼教中心专用",{"key":169,"text":550,"correct":26},"儿童活动用房与相邻区域用耐火极限为2．00h的防火隔墙和1．00h的不燃性楼板分隔，隔墙上设置了符合规范要求的防火卷帘","ACDE",{"id":553,"libraryId":5,"type":156,"typeLabel":157,"stem":554,"options":555,"answer":566,"analysis":33},935426,"下列关于剧场及其观众厅的说法符合规范要求的是（ ）。",[556,558,560,562,564],{"key":20,"text":557,"correct":22},"剧场设置在民用建筑内时，应采用耐火极限不低于2．00h的防火隔墙和1．00h的不燃性楼板与其它区域进行分隔，墙上设置的门应采用乙级防火门",{"key":24,"text":559,"correct":22},"观众厅的一个厅、室的建筑面积不宜大于400㎡，疏散门不应少于2个",{"key":28,"text":561,"correct":26},"剧场设置在民用建筑内时，至少应设置1个独立的安全出口和疏散楼梯",{"key":31,"text":563,"correct":26},"剧场建筑的舞台与观众厅之间的隔墙应采用耐火极限不低于3．00h的防火隔墙分隔",{"key":169,"text":565,"correct":26},"设置在高层建筑内时，应设置火灾自动报警系统及自动喷水灭火系统","CDE",{"id":568,"libraryId":5,"type":156,"typeLabel":157,"stem":569,"options":570,"answer":581,"analysis":33},935427,"下列关于工业建筑之间的防火间距的说法中，错误的是（ ）。",[571,573,575,577,579],{"key":20,"text":572,"correct":26},"某建筑高度30m的难燃铝塑加工厂房，与耐火等级为二级，建筑高度8m的桐油厂房相邻，相邻侧外墙24m以下部分为无门、窗、洞口的防火墙，两者之间的防火间距为6m",{"key":24,"text":574,"correct":26},"某建筑高度24m的焦化厂精萘厂房，屋顶耐火极限为1．00h，与耐火等级为二级的建筑高度18m的焦油仓库相邻，相邻的外墙为防火墙，两者的防火间距为4m",{"key":28,"text":576,"correct":26},"某焦化厂焦油厂房，屋顶承重构件采用耐火极限为0．50h的难燃性材料，与建筑高度相同的沥青厂房相邻，沥青厂房屋顶承重构件耐火极限为1．00h，其面向焦油厂房一侧外墙为防火墙，两者的防火间距不限",{"key":31,"text":578,"correct":22},"某建筑高度为20m的化肥厂氢氮压缩车间，每层建筑面积为500㎡，地上3层，与建筑高度为12m的氨气压缩车间相邻，氨气压缩车间耐火等级为二级，屋顶耐火极限1．00h且无天窗，其面向氢氮压缩车间的外墙为防火墙，两者之间的防火间距为6m",{"key":169,"text":580,"correct":26},"某多层镁粉制作厂房，与多层镁粉储存仓库相邻，耐火等级均为二级，两座建筑的外墙均为不燃性墙体，无可燃性屋檐，所开通风窗不正对，相邻外墙的开窗面积均不大于其外墙面积之和的5％，两者的防火间距7．5m","ABCE",{"id":583,"libraryId":5,"type":156,"typeLabel":157,"stem":584,"options":585,"answer":536,"analysis":33},935428,"下列关于建筑防火间距的说法中，错误的是（ ）。",[586,588,590,592,594],{"key":20,"text":587,"correct":26},"某建筑高度为27m的住宅楼与建筑高度为8m的石蜡裂解厂房相邻，其面向厂房相邻一侧的外墙为防火墙，两者之间的防火间距可为4m",{"key":24,"text":589,"correct":26},"某建筑高度为20m，耐火等级为二级的服装仓库与建筑高度为18m耐火等级为二级的医院相邻，服装仓库与医院相邻一侧的外墙为防火墙，两者之间的防火间距可为4m",{"key":28,"text":591,"correct":26},"某建筑高度为28m的制衣厂房与建筑高度为30m的住宅相邻，其面向住宅一侧的外墙为无门、窗、洞口的防火墙，屋顶耐火极限1．00h，且屋顶无天窗则两者之间的防火间距不应小于6m",{"key":31,"text":593,"correct":26},"某建筑高度为36m，耐火等级为二级的印刷厂房与建筑高度为18m，耐火等级为三级的医院相邻，印刷厂与医院相邻一侧的外墙上的门、窗、洞口设置了甲级防火门、窗，两者之间的防火间距可为4m",{"key":169,"text":595,"correct":22},"某建筑高度32m的自熄性塑料仓库与建筑高度为30m的住宅相邻，仓库面向住宅一侧的外墙为无门、窗、洞口的防火墙，则两者之间的防火间距可不限",{"id":597,"libraryId":5,"type":156,"typeLabel":157,"stem":598,"options":599,"answer":566,"analysis":33},935429,"某建筑高度为52m的住宅，沿周边设置环形消防车道，下列关于该住宅消防车登高操作场地的布置不符合规定的是（ ）。",[600,602,604,606,608],{"key":20,"text":601,"correct":22},"沿一个建筑长边的底边连续布置消防车登高操作场地",{"key":24,"text":603,"correct":22},"消防车登高操作场地及其下面的建筑结构、管道和暗沟等，能承受重型消防车的压力",{"key":28,"text":605,"correct":26},"消防车登高操作场地范围内的裙房进深为5m",{"key":31,"text":607,"correct":26},"连续布置消防车登高操作场地确有困难，可间隔布置，且间隔距离为30m",{"key":169,"text":609,"correct":26},"消防车登高操作场地对应的一侧设有汽车库出入口",{"id":611,"libraryId":5,"type":156,"typeLabel":157,"stem":612,"options":613,"answer":624,"analysis":33},935430,"某办公楼，设置1部消防电梯、1部客梯。消防机构对该建筑电梯进行检查，下列结果，符合规定的是（ ）。",[614,616,618,620,622],{"key":20,"text":615,"correct":26},"消防电梯在首层经过30m长的走道通向室外",{"key":24,"text":617,"correct":26},"在首层的消防电梯入口处设置供消防队员专用的操作按钮",{"key":28,"text":619,"correct":22},"消防电梯轿厢的内部装修采用铝塑板纤维石膏板",{"key":31,"text":621,"correct":22},"普通客梯井道内设置煤气管道",{"key":169,"text":623,"correct":22},"消防电梯井道设置排烟风机电缆","AB",{"id":626,"libraryId":5,"type":156,"typeLabel":157,"stem":627,"options":628,"answer":566,"analysis":33},935431,"下列关于消防电梯的说法中，错误的是（ ）。",[629,631,633,635,637],{"key":20,"text":630,"correct":22},"消防电梯的井底应设排水设施，排水井容量不应小于2m3，排水泵的排水量不应小于10L／s",{"key":24,"text":632,"correct":22},"消防电梯的行驶速度从首层至顶层的运行时间不宜大于60s",{"key":28,"text":634,"correct":26},"建筑高度大于32m的高层厂房（仓库），每个防火分区内宜设置1台消防电梯",{"key":31,"text":636,"correct":26},"消防电梯应集中设置在同一防火分区内",{"key":169,"text":638,"correct":26},"住宅建筑的消防电梯与防烟楼梯间前室合用，其使用面积不应小于10㎡",{"id":640,"libraryId":5,"type":156,"typeLabel":157,"stem":641,"options":642,"answer":536,"analysis":33},935432,"防火检查中，通过对消防车登高面的设置，以及消防车登高操作场地的（ ）等检查，核实消防车登高操作场地的设置是否符合现行国家工程建设消防技术标准的要求。",[643,645,647,649,651],{"key":20,"text":644,"correct":26},"长度",{"key":24,"text":646,"correct":26},"宽度",{"key":28,"text":648,"correct":26},"承载能力",{"key":31,"text":650,"correct":26},"坡度",{"key":169,"text":652,"correct":22},"高度",[654,657,660,663,666,669],{"id":15,"name":655,"category":7,"favorite":656},"领导干部任职前廉政法规知识测试题",92,{"id":658,"name":659,"category":7,"favorite":15},595,"建筑结构与设备",{"id":661,"name":662,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":664,"name":665,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":667,"name":668,"category":7,"favorite":8},534,"BIM工程师",{"id":670,"name":668,"category":7,"favorite":8},535]