[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"lib-605-10":3},{"library":4,"page":9,"limit":10,"total":11,"questions":12,"related":658},{"id":5,"name":6,"category":7,"favorite":8},605,"消防技术综合能力(一级、二级)","建筑工程",0,10,50,2974,[13,34,46,58,70,82,94,106,118,130,142,154,166,178,190,202,214,226,238,250,262,274,286,298,310,322,340,352,364,376,388,400,415,430,445,459,471,486,501,515,529,544,556,568,580,595,610,622,634,646],{"id":14,"libraryId":5,"type":15,"typeLabel":16,"stem":17,"options":18,"answer":30,"analysis":33},935126,1,"单选题","（2020年真题）某消防技术服务机构对某高层建筑的机械加压送风系统进行防火检查，根据现行国家标准《建筑防烟排烟系统技术标准》（GB 51251），下列防火检查结果中，不符合规范要求的是（ ）。",[19,23,26,29],{"key":20,"text":21,"correct":22},"A","风机房内的机械加压送风机为离心风机，其进风口直通室外",false,{"key":24,"text":25,"correct":22},"B","竖向安装在管道井内的机械加压送风管道为镀锌钢板风管",{"key":27,"text":28,"correct":22},"C","防烟楼梯间每隔3层安装一个常开式百叶送风口。",{"key":30,"text":31,"correct":32},"D","防烟楼梯间前室每层安装一个常开式加压送风口。",true,"",{"id":35,"libraryId":5,"type":15,"typeLabel":16,"stem":36,"options":37,"answer":20,"analysis":33},935127,"（2020年真题）某二级耐火等级的4层制衣厂房，矩形平面，长100m，宽40m，层高均为5m。地上二层沿长边方向在厂房中部布置通长的疏散内走道，该走道净宽为3m。下列防火检查结果中，不符合现行国家标准要求的是（ ）。",[38,40,42,44],{"key":20,"text":39,"correct":32},"地上二层内走道采用自然排烟形式，走道两端各设置一个平开玻璃窗",{"key":24,"text":41,"correct":22},"地上三层采用机械排烟形式，各防烟分区内任一点至排烟口的最远距离为22m",{"key":27,"text":43,"correct":22},"地上三层采用机械排烟形式，排烟管道设计风速为15m\u002Fs",{"key":30,"text":45,"correct":22},"地上四层采用自然排烟形式，屋面上设置的可熔性采光带面积为600m2",{"id":47,"libraryId":5,"type":15,"typeLabel":16,"stem":48,"options":49,"answer":27,"analysis":33},935128,"（2020年真题）某消防技术服务机枃对某建筑高度为58m的高层公共建筑的防烟楼梯间进行防火检査。下列检查结果中,不符合现行国家标准要求的是（ ）",[50,52,54,56],{"key":20,"text":51,"correct":22},"楼梯间每个2层设置了1个常开式百叶送风口",{"key":24,"text":53,"correct":22},"前室每层设置了1个常闭式加压送风口,并设手动开启装置",{"key":27,"text":55,"correct":32},"楼梯间顶部设置了1个净面积为0.9㎡的固定窗",{"key":30,"text":57,"correct":22},"机械加压送风系统管道井的检修门为乙级防火门",{"id":59,"libraryId":5,"type":15,"typeLabel":16,"stem":60,"options":61,"answer":27,"analysis":33},935129,"（2020年真题）某建筑地下车库设有防烟排烟系统，封装安装形式为明装，材料为钢板，钢板厚度设计未作要求。对风管进行进场检验,下列检验结果中不符合现行国家标准《建筑防烟排烟系统技术标准》（GB 51251）的是（ ）。",[62,64,66,68],{"key":20,"text":63,"correct":22},"长边尺寸为450 mm的矩形排烟管道的板材厚度测量值为0.8 mm",{"key":24,"text":65,"correct":22},"长边尺寸为400 mm的矩形送风管道的板材厚度测量值为0.6 mm",{"key":27,"text":67,"correct":32},"长边尺寸为1100 mm的矩形排烟管道的板材厚度测量值为1.0 mm",{"key":30,"text":69,"correct":22},"长边尺寸为1000 mm的矩形，送风管道的板材厚度测量值为0.8mm",{"id":71,"libraryId":5,"type":15,"typeLabel":16,"stem":72,"options":73,"answer":30,"analysis":33},935130,"（2020年真题）建筑内设置的机械排烟系统进行维护保养的下列做法中符合现行国家标准建筑防烟排烟系统技术标准，GB51251的是（ ）。",[74,76,78,80],{"key":20,"text":75,"correct":22},"每半年对排烟风机进行一次功能检测启动试验",{"key":24,"text":77,"correct":22},"每半年对活动排烟垂壁进行一次功能检测启动试验",{"key":27,"text":79,"correct":22},"每年对全部排烟防火阀进行一次手动启动实验",{"key":30,"text":81,"correct":32},"每年对全部机械排烟系统进行一次联动实验和性能检测",{"id":83,"libraryId":5,"type":15,"typeLabel":16,"stem":84,"options":85,"answer":20,"analysis":33},935131,"（2019年真题）根据现行国家标准《建筑设计防火规范》(GB50016)，下列消防配电线路的敷设方式中，不符合规范要求的是（）",[86,88,90,92],{"key":20,"text":87,"correct":32},"阻燃电线穿封闭式普通金属线槽明敷设",{"key":24,"text":89,"correct":22},"矿物绝缘类不燃性电缆直接敷设在电缆井内",{"key":27,"text":91,"correct":22},"耐火电缆直接敷设在电缆井内",{"key":30,"text":93,"correct":22},"阻燃电缆在吊顶内穿涂刷防火涂料保护的金属管敷设",{"id":95,"libraryId":5,"type":15,"typeLabel":16,"stem":96,"options":97,"answer":24,"analysis":33},935132,"(2017年真题) 某省政府机关办公大楼建筑高度为31.8m，大楼地下一层设置发电机作为备用电源，市政供电中断时柴油发电机自动启动。根据现行国家标准《建筑设计防火规范》GB50016，市政供电中断时，自备发电机最迟应在（)s内正常供电。",[98,100,102,104],{"key":20,"text":99,"correct":22},"10",{"key":24,"text":101,"correct":32},"30",{"key":27,"text":103,"correct":22},"20",{"key":30,"text":105,"correct":22},"60",{"id":107,"libraryId":5,"type":15,"typeLabel":16,"stem":108,"options":109,"answer":20,"analysis":33},935133,"(2018年真题) 消防部门对某大厦的消防电源及其配电进行验收，下列验收检查结果中，不符合现行国家标准《建筑设计防火规范》(GB50016)的是( )",[110,112,114,116],{"key":20,"text":111,"correct":32},"大厦的消防配电干线采用阻燃电缆直接明敷设在与动力配电线路共用的电缆井内，并分别布置在电缆井的两侧",{"key":24,"text":113,"correct":22},"大厦的消防用电设备采用了专用的供电回路，并在地下一层设置了柴油发电机作为备用消防电源",{"key":27,"text":115,"correct":22},"大厦的消防配电干线按防火分区划分，配电支线未穿越防火分区",{"key":30,"text":117,"correct":22},"消防控制室、消防水泵房、防烟和排烟风机房的消防用电设备供电，在其配电线路的最末一级配电箱处设置了自动切换装置",{"id":119,"libraryId":5,"type":15,"typeLabel":16,"stem":120,"options":121,"answer":20,"analysis":33},935134,"(2016年真题) 为防止电气火灾发生，与采取有效措施，预防电气线路过载，下列预防电气线路过载的措施中，正确的是（??）",[122,124,126,128],{"key":20,"text":123,"correct":32},"根据负载的情况选择合适的电线",{"key":24,"text":125,"correct":22},"安装电气火灾监控量",{"key":27,"text":127,"correct":22},"安装剩余电流保护装置",{"key":30,"text":129,"correct":22},"安装测温式电气水灾监控探测器",{"id":131,"libraryId":5,"type":15,"typeLabel":16,"stem":132,"options":133,"answer":30,"analysis":33},935135,"(2018年真题)对某印刷厂的印刷成品仓库进行电气防火检查，下列检查结果中，不符合现行国家标准《建筑设计防火规范》(GB 50016)的是( )",[134,136,138,140],{"key":20,"text":135,"correct":22},"仓库安装了 40W 白炽灯照明",{"key":24,"text":137,"correct":22},"对照明灯具的发热部件采取了隔热措施",{"key":27,"text":139,"correct":22},"在仓库外部设有 1 个照明配电箱",{"key":30,"text":141,"correct":32},"在仓库内部设有 2 个照明开关",{"id":143,"libraryId":5,"type":15,"typeLabel":16,"stem":144,"options":145,"answer":24,"analysis":33},935136,"(2016年真题) 对建筑物进行防火检查时，应注意检查建筑物的消防用电负荷设置的合理性。下列建筑中，消防用电应按一级负荷供电的是（??）",[146,148,150,152],{"key":20,"text":147,"correct":22},"座位数超过1500个的电影院",{"key":24,"text":149,"correct":32},"建筑高度大于50m的乙、丙厂房和丙类库房",{"key":27,"text":151,"correct":22},"座位数超过3000个的体育馆",{"key":30,"text":153,"correct":22},"省级电信和财贸金融建筑",{"id":155,"libraryId":5,"type":15,"typeLabel":16,"stem":156,"options":157,"answer":24,"analysis":33},935137,"(2015年真题) 下列关于消防供配电线路说法中，错误的是（）。",[158,160,162,164],{"key":20,"text":159,"correct":22},"消防设备供电线路穿越不同防火分区穿孔处应做防火封堵",{"key":24,"text":161,"correct":32},"消防供电线路穿越不同防火分区穿孔处所用封堵材料，均应为无机材料",{"key":27,"text":163,"correct":22},"消防设备供电线路应采用阻燃电缆或耐火电缆",{"key":30,"text":165,"correct":22},"消防供电线路进入配电柜.控制器等电气柜的穿孔处应做防火封堵",{"id":167,"libraryId":5,"type":15,"typeLabel":16,"stem":168,"options":169,"answer":20,"analysis":33},935138,"(2015年真题) 下列关于电气防火说法中，错误的是（）。",[170,172,174,176],{"key":20,"text":171,"correct":32},"在供配电线路上加装过流保护装置可保证该线路不会引发火灾",{"key":24,"text":173,"correct":22},"在供配电线路上加装剩余电流式电气火灾监控探测器，可有效降低电气火灾发生的概率",{"key":27,"text":175,"correct":22},"采用矿物绝缘电缆可保证该线路本身不会着火",{"key":30,"text":177,"correct":22},"供配电线路上加装过电压保护装置可有效降低火灾发生的概率",{"id":179,"libraryId":5,"type":15,"typeLabel":16,"stem":180,"options":181,"answer":27,"analysis":33},935139,"(2015年真题) 下列接线方式中，符合电气防火要求的是（）。",[182,184,186,188],{"key":20,"text":183,"correct":22},"将2根不同线径的单芯铜导线直接压接在同一端子上",{"key":24,"text":185,"correct":22},"将铜导线和铝导线直接绞结后用胶布缠绕",{"key":27,"text":187,"correct":32},"将铜导线和铝导线烫锡后接到接线端子上",{"key":30,"text":189,"correct":22},"将单芯导线烫锡后绞结，再用防水胶布缠绕",{"id":191,"libraryId":5,"type":15,"typeLabel":16,"stem":192,"options":193,"answer":27,"analysis":33},935140,"（2020年真题）对某一类高层公共建筑的消防电源及其配电系统检查的下列结果中,不符合现行国家标准《建筑设计防火规范》（GB50016）的是（ ）",[194,196,198,200],{"key":20,"text":195,"correct":22},"建筑总配电室内的消防电源配电柜分别有两个区域的35KV变电站供电",{"key":24,"text":197,"correct":22},"消防用电设备采用专业的供电回路,其配电箱独立设置",{"key":27,"text":199,"correct":32},"消防配电线路采用阻燃电缆,与其他配电线路分别布置在同一电缆井的两侧",{"key":30,"text":201,"correct":22},"消防控制室內设置的专用双电源配电箱设有自动切换装置",{"id":203,"libraryId":5,"type":15,"typeLabel":16,"stem":204,"options":205,"answer":24,"analysis":33},935141,"（2020年真题）某消防技术服务机构对某铝粉加工车间进行了防火检查。下列电气设备和线路敷设的检查结果中，不符合现行国家标准要求的是（ ）",[206,208,210,212],{"key":20,"text":207,"correct":22},"电气线路选用了铜芯绝缘导线",{"key":24,"text":209,"correct":32},"车间内电源插座开口的一面与地面垂直",{"key":27,"text":211,"correct":22},"电气线路和设备安装了过载短路和接电保护",{"key":30,"text":213,"correct":22},"设备的接地装置与防雷接地装置分开设詈",{"id":215,"libraryId":5,"type":15,"typeLabel":16,"stem":216,"options":217,"answer":20,"analysis":33},935142,"（2020年真题）对某纺织厂的生产车间和仓库的电气线路检查的下列结果中，符合现行国家标准《建筑设计防火规范》（GB50016）的是（ ）。",[218,220,222,224],{"key":20,"text":219,"correct":32},"生产车间内配电线路穿金属代管保护，紧贴通关管道",{"key":24,"text":221,"correct":22},"生产车间内额定功率为100W的荧光高压贡灯直接安装在木质格栅板上",{"key":27,"text":223,"correct":22},"仓库内采用卤钨灯作为照明灯具，其引入线采用瓷管作隔热保护",{"key":30,"text":225,"correct":22},"仓库内靠近疏散门的墙面上设有专用配电箱",{"id":227,"libraryId":5,"type":15,"typeLabel":16,"stem":228,"options":229,"answer":24,"analysis":33},935143,"（2019年真题）对某多层办公楼设置的自带蓄电池非集中控制型消防应急照明和疏散指示系统功能进行调试,根据现行国家标准消防应急照明和疏散指示系统功能进行调试,根据现行国家标准《消防应急照明和疏散指示系统技术标准》(GB51309)下列调试结果中不符合规范要求的是（）",[230,232,234,236],{"key":20,"text":231,"correct":22},"手动操作应急照明配电箱的应急启动按钮,应急照明配电箱切断主要电源输出",{"key":24,"text":233,"correct":32},"启动应急照明配电箱的应急按钮,其所配接的持续型灯具的光源由节电点亮模式转入应急点亮模式的时间为10s",{"key":27,"text":235,"correct":22},"走廊的最低地面水平照度为1.0lx",{"key":30,"text":237,"correct":22},"灯具应急点亮的持绩工作时间达到45min",{"id":239,"libraryId":5,"type":15,"typeLabel":16,"stem":240,"options":241,"answer":27,"analysis":33},935144,"（2019年真题）某消防技术服务机构对不同工程项目的消防应急灯具在蓄电池电源供电时的持续工作时间进行检测，根据现行国家标准《消防应急照明和疏散指示系统技术标准》(GB51309)，下列检测结果中，不符合规范要求的是（）",[242,244,246,248],{"key":20,"text":243,"correct":22},"某建筑高度为55m，建筑面积为10000㎡的办公建筑的消防应急灯具持续工作时间为0.5h",{"key":24,"text":245,"correct":22},"某建筑面积为1500㎡的幼儿园的消防应急灯具持续工作时间为0.5h",{"key":27,"text":247,"correct":32},"某建筑面积为1500㎡的养老院的消防应急灯具持续工作时间为0.5h",{"key":30,"text":249,"correct":22},"某建筑面积为1000㎡的KTV的消防应急灯具持续工作时间为0.5h",{"id":251,"libraryId":5,"type":15,"typeLabel":16,"stem":252,"options":253,"answer":27,"analysis":33},935145,"(2017年真题) 根据现行国家消防技术标准，关于建筑内消防应急照明和疏散指示标志的检查结果中，不符合标准要求的是（??）",[254,256,258,260],{"key":20,"text":255,"correct":22},"人员密集场所安全出口标志设置的在疏散门的正上方",{"key":24,"text":257,"correct":22},"疏散走道内灯光疏散指示标志的间距为19.5m",{"key":27,"text":259,"correct":32},"灯光疏散指示标志均设置在疏散走道的顶棚上",{"key":30,"text":261,"correct":22},"袋形疏散走道内灯光疏散指示标志间距为9m",{"id":263,"libraryId":5,"type":15,"typeLabel":16,"stem":264,"options":265,"answer":24,"analysis":33},935146,"(2017年真题) 对建筑内的消防应急照明和疏散指示系统应定期进行维护保养，根据现行国家标准《建筑消防设施的维护与管理》（GB25201-2010），下列检测内容中，不属于消防应急照明系统检测内容的是（??）",[266,268,270,272],{"key":20,"text":267,"correct":22},"切断正常供电，测试电源切换和应急照明电源充电、放电功能",{"key":24,"text":269,"correct":32},"通过报警联动，测试非消防用电应急强制切断功能",{"key":27,"text":271,"correct":22},"通过报警联动，检查应急照明系统自动转入应急工作状态的控制功能",{"key":30,"text":273,"correct":22},"测试应急照明系统应急电源供电时间",{"id":275,"libraryId":5,"type":15,"typeLabel":16,"stem":276,"options":277,"answer":20,"analysis":33},935147,"(2016年真题) 对建筑进行防火检查时，应对建筑内设置的应急照明和疏散指示标志进行检查，下列关于公共建筑内安装应急照明灯具的说法中，错误的是()",[278,280,282,284],{"key":20,"text":279,"correct":32},"在侧面墙上顶部安装时其底部距地面不得低于1.8m",{"key":24,"text":281,"correct":22},"消防应急照明灯具应均匀布置",{"key":27,"text":283,"correct":22},"在距地面1m以下墙面上置装时应采用嵌入式安装",{"key":30,"text":285,"correct":22},"在侧面墙上顶部安装时其底部距地面不得低于2m",{"id":287,"libraryId":5,"type":15,"typeLabel":16,"stem":288,"options":289,"answer":30,"analysis":33},935148,"(2018年真题)对一家大型医院安装的消防应急照明和疏散指示系统的安装质量进行检查。下列检查结果中，符合现行国家标准《建筑设计防火规范》(GB50016)的是（ ）。",[290,292,294,296],{"key":20,"text":291,"correct":22},"消防控制室内的应急照明灯使用插头连接在侧墙上部的插座上",{"key":24,"text":293,"correct":22},"疏散走道的灯光疏散指示标志安装在距离地面1.1m的墙面上",{"key":27,"text":295,"correct":22},"主要疏散走道的灯光疏散指示标志的安装间距为30m",{"key":30,"text":297,"correct":32},"门诊大厅、疏散走道的应急照明灯嵌入式安装在吊顶上",{"id":299,"libraryId":5,"type":15,"typeLabel":16,"stem":300,"options":301,"answer":20,"analysis":33},935149,"(2018年真题)消防技术服务机构对某高层写字楼的消防应急照明系统进行检测，下列检测结果中，不符合现行国家标准《建筑设计防火规范》(GB 50016)的是( )",[302,304,306,308],{"key":20,"text":303,"correct":32},"在二十层楼梯间前室测得的地面照度值为 4.0lx",{"key":24,"text":305,"correct":22},"在二层疏散走道测得的地面照度值为 2.0lx",{"key":27,"text":307,"correct":22},"在消防水泵房切断正常照明前、后测得的地面照度值相同",{"key":30,"text":309,"correct":22},"在十六层避难层测得的地面照度值为 5.0lx",{"id":311,"libraryId":5,"type":15,"typeLabel":16,"stem":312,"options":313,"answer":24,"analysis":33},935150,"(2016年真题)消防技术服务机构对某大型商场内设置的疏散照明设施进行检测。下列检测结果中不符合《建筑设计防火规范》（GB50016-2014）要求的是（??）。",[314,316,318,320],{"key":20,"text":315,"correct":22},"避难间疏散照明的地面最低水平照度为10.0lx",{"key":24,"text":317,"correct":32},"营业厅疏散照明的地面最低水平照度为2.0lx",{"key":27,"text":319,"correct":22},"楼梯间疏散照明的地面最低水平照度为5.5lx",{"key":30,"text":321,"correct":22},"前室疏散照明的地面最低水平照度为6.0lx",{"id":323,"libraryId":5,"type":324,"typeLabel":325,"stem":326,"options":327,"answer":339,"analysis":33},935151,2,"多选题","（2020年真题）对某老年人照料设施设置的消防应急照明和疏散指示系统检的下列结果中，符合现行国家标准《消防应急照明和疏散指示系统技术标准》（GB 51309）的有（ ）。",[328,330,332,334,336],{"key":20,"text":329,"correct":32},"系统自动应急启动后，应急照明控制器发出自动应急启动信号",{"key":24,"text":331,"correct":22},"系统自动应急启动后，A型应急照明配电箱保持其供电回路输出",{"key":27,"text":333,"correct":22},"应急照明灯具点亮后，防烟楼梯间地面的水平照度为5.1lx",{"key":30,"text":335,"correct":32},"系统内所有灯具光源应急点亮时间为0.2s",{"key":337,"text":338,"correct":22},"E","系统手动应急启动后，应急照明灯具光源的持续点亮时间为40min","AD",{"id":341,"libraryId":5,"type":15,"typeLabel":16,"stem":342,"options":343,"answer":30,"analysis":33},935152,"（2020年真题）某商业综合体设置了集中电源,集中控制型消防应急照明和疏散指示系统,根据现行国家标准《消防应急照明和疏散指示系统技术标准》（GB51309）,不属于该系统部件连接方式的是（ ）。",[344,346,348,350],{"key":20,"text":345,"correct":22},"应急照明控制器直接与应急照明集中电源连接",{"key":24,"text":347,"correct":22},"应急照明集中电源,直接与消防应急照明灯具连接",{"key":27,"text":349,"correct":22},"应急照明控制器直接与应急照明控制器连接",{"key":30,"text":351,"correct":32},"应急照明控制器直接与应急照明配电箱连接",{"id":353,"libraryId":5,"type":15,"typeLabel":16,"stem":354,"options":355,"answer":27,"analysis":33},935153,"（2020年真题）某消防技术服务机构对某酒店设置的集中电源，集中控制型消防应急照明和疏散指示系统进行了调试。根据现行国家标准《消防应急照明和疏散指示系统技术标;准》（GB 51309），集中电源应调试的主要功能不包括（ ）。",[356,358,360,362],{"key":20,"text":357,"correct":22},"故障报警功能",{"key":24,"text":359,"correct":22},"消音功能",{"key":27,"text":361,"correct":32},"—健检查功能",{"key":30,"text":363,"correct":22},"电源分配输出功能",{"id":365,"libraryId":5,"type":15,"typeLabel":16,"stem":366,"options":367,"answer":24,"analysis":33},935154,"（2019年真题）某消防技术服务机构对某宾馆的火灾自动报警系统进行年度检测,下列检测结果中不符合现行国家标准《火灾自动报警系统施工及验收规范》国标50166要求的是（）",[368,370,372,374],{"key":20,"text":369,"correct":22},"断开一个探测回路与控制器之间的连线56秒时控制器发出故障信号",{"key":24,"text":371,"correct":32},"报警控制器在故障状态下,使任一非故障部位的探测器发岀火灾报警信号,85秒时控制器发出火灾报警信号",{"key":27,"text":373,"correct":22},"将一个探测回路中任意探测器的接线断开,30秒时控制器发出故障信号",{"key":30,"text":375,"correct":22},"断开备用电源与控制器之间的连线，66秒时控制器发出故障信号",{"id":377,"libraryId":5,"type":15,"typeLabel":16,"stem":378,"options":379,"answer":24,"analysis":33},935155,"（2019年真题）某消防施工单位对某酒店的自动消防设施进行安裝施工，根据现行国家标准《火灾自动报警系统设计规范》(GB50116)，下列消防设备中，可直接与火灾报警控制器连接的是（）。",[380,382,384,386],{"key":20,"text":381,"correct":22},"可燃气体探测器",{"key":24,"text":383,"correct":32},"可燃气体报警控制器",{"key":27,"text":385,"correct":22},"非独立式电气火灾监控探测器",{"key":30,"text":387,"correct":22},"集中电源非集中控制型消防应急照明灯具",{"id":389,"libraryId":5,"type":15,"typeLabel":16,"stem":390,"options":391,"answer":20,"analysis":33},935156,"（2019年真题）某消防技术服务机构对某商场疏散通道上设置的常开防火门的联动功能进行调试,下列调试结果中符合国家标准《火灾自动报警系统设计规范》(GB50116)要求的是（）",[392,394,396,398],{"key":20,"text":393,"correct":32},"防火门所在防火区内两只独立的火灾探测器警报后,联动控制防火门关闭口",{"key":24,"text":395,"correct":22},"防火门所在防火分区内任一只火灾探测器报警后,联动控制防火门关闭",{"key":27,"text":397,"correct":22},"防火门所在防火区内任一只手动火灾报警按钮报警后,联动控制防火门关闭上",{"key":30,"text":399,"correct":22},"防火门所在防火分区及相邻防火分区各一只火灾探测器警报后,联动控制防火门关闭",{"id":401,"libraryId":5,"type":324,"typeLabel":325,"stem":402,"options":403,"answer":414,"analysis":33},935157,"（2019年真题）某消防救援机构对高某髙层办公楼火灾自动报警系统进行消防监督检查,下列检查结果中符合现行国家标准要求的有（）",[404,406,408,410,412],{"key":20,"text":405,"correct":32},"消防控制室图形显示装置能显示系统那个消防用电设备的供电电源和备用电源",{"key":24,"text":407,"correct":32},"消防控制室图形显示装置能显示该办公楼的消防安全管理信息",{"key":27,"text":409,"correct":32},"消防控制室内的消防联动控制器能远程控制常开防火门关闭",{"key":30,"text":411,"correct":22},"消防控制室内的消防联动控制器能远程控制防火卷帘的升降",{"key":337,"text":413,"correct":32},"消防控制室内的消防联动控制器能远程控制所有电梯停于首层或电梯转化换层","ABCE",{"id":416,"libraryId":5,"type":324,"typeLabel":325,"stem":417,"options":418,"answer":429,"analysis":33},935158,"（2019年真题）某消防技术服务机构对某会展中心的自动消防设施进行维护保养,下列做法和结果中,不符合现行国家标准要求的有（）。",[419,421,423,425,427],{"key":20,"text":420,"correct":32},"对1只感烟探测器喷烟直至报警,探测器所在区域显示器在5s后发出报警信号",{"key":24,"text":422,"correct":22},"断开消防控制室图形显示装置与其连接的各消防设备的连线,图形显示装置在1min时发出的故障信号",{"key":27,"text":424,"correct":32},"在同一防火分区内,1只手动报警按钮和1只感烟探测器同时发出火灾报警信号。该防火分区内用于防火分隔的防火卷帘直接下降至地面。",{"key":30,"text":426,"correct":32},"检查发现火灾显示盘损坏,维护人员直接将其拆下,并立即更换新的产品。",{"key":337,"text":428,"correct":22},"在消防控制室手动选择2个广播分区启动应急广播,该区域正在播音的背景音乐广播停止,消防应急广播启动","ACD",{"id":431,"libraryId":5,"type":324,"typeLabel":325,"stem":432,"options":433,"answer":444,"analysis":33},935160,"(2017年真题) 根据现行国家标准《建筑消防设施的维护管理》(GB25201-2010)，对火灾自动报警系统报警控制器的检测内容， 主要包括（??）",[434,436,438,440,442],{"key":20,"text":435,"correct":22},"联动控制器及控制模块的手动、 自动联动控制功能",{"key":24,"text":437,"correct":32},"火灾显示盘和CRT显示器的报警、 显示功能",{"key":27,"text":439,"correct":32},"火灾报警、 故障报警、 火灾优先功能",{"key":30,"text":441,"correct":32},"自检、 消音、 复位功能",{"key":337,"text":443,"correct":32},"打印机打印功能","BCDE",{"id":446,"libraryId":5,"type":324,"typeLabel":325,"stem":447,"options":448,"answer":414,"analysis":33},935161,"(2017年真题) 根据现行国家标准《火灾自动报警系统施工及验收规范》(GB50166-2007)，下列火灾自动报警系统的功能中，应每季度进行检查和试验的有（??）",[449,451,453,455,457],{"key":20,"text":450,"correct":32},"分期分批试验探测器的动作及确认灯显示功能",{"key":24,"text":452,"correct":32},"试验火灾警报装置的声光显示功能",{"key":27,"text":454,"correct":32},"试验主、备电源自动切换功能",{"key":30,"text":456,"correct":22},"试验非消防电源强制切断功能",{"key":337,"text":458,"correct":32},"试验相关消防控制设备的控制显示功能",{"id":460,"libraryId":5,"type":15,"typeLabel":16,"stem":461,"options":462,"answer":20,"analysis":33},935162,"(2018年真题) 对某大型商业综合体的火灾自动报警系统的安装质量进行检查，下列检查结果中不符合现行国家标准《火灾自动报警系统施工验收规范》(GB 50166)的是（??）",[463,465,467,469],{"key":20,"text":464,"correct":32},"在高度为 12m 的共享空间设置的红外光束感烟火灾探测器的光束轴线至顶棚的垂直距离为 1.5m",{"key":24,"text":466,"correct":22},"在商场顶棚安装的点型感烟探测器距多孔送风顶棚孔口的水平距离为 0.6m",{"key":27,"text":468,"correct":22},"在厨房内安装的可燃气体探测器位于天然管道及用气部位的上部顶棚处",{"key":30,"text":470,"correct":22},"在宽度为 24m 的餐饮区走道顶棚上安装的点型感烟探测器间距为 12.5m",{"id":472,"libraryId":5,"type":324,"typeLabel":325,"stem":473,"options":474,"answer":485,"analysis":33},935163,"(2018年真题) 对某展览馆安装的火灾自动报警系统进行验收前检测，下列检测结果中，符合现行国家标准《火灾自动报警系统施工及验收规范》（GB 50166）的有（）。",[475,477,479,481,483],{"key":20,"text":476,"correct":32},"使用发烟器对任一感烟探测器发烟，火灾报警控制器发出火灾报警信号",{"key":24,"text":478,"correct":32},"在火灾报警控制器处于故障报警状态下，对任一非故障部位的探测器发出火灾报警信号后 55s，控制器发出火灾报警信号",{"key":27,"text":480,"correct":22},"消防联动控制器接收到任意两只独立的火灾探测器的报警信号后，联动启动消防泵",{"key":30,"text":482,"correct":32},"断开消防联动控制器与输入\u002F输出模块的连线后 80s，控制器发出故障信号",{"key":337,"text":484,"correct":22},"消防联动控制器接收到两只独立的火灾探测器的报警信号后，火警信号所在防火分区的火灾声光警报器启动","ABD",{"id":487,"libraryId":5,"type":324,"typeLabel":325,"stem":488,"options":489,"answer":500,"analysis":33},935164,"(2018年真题) 消防工程施工单位的技术人员对某商场的火灾自动报警系统进行联动调试。下列对防火门和防火卷帘联动调试的结果中，符合现行国家标准要求的有( )。",[490,492,494,496,498],{"key":20,"text":491,"correct":32},"常开防火门所在防火分区内的两只独立的火灾探测器报警后，防火门关闭",{"key":24,"text":493,"correct":22},"常开防火门所在防火分区内的一只手动火灾报警按钮动作后，防火门关闭",{"key":27,"text":495,"correct":22},"防火分区内一只专门用于联动防火卷帘的感温探测器报警后，疏散走道上的防火卷帘下降至距楼板面1.8m处",{"key":30,"text":497,"correct":32},"防火分区内两只独立的感烟探测器报警后，疏散走道上的防火卷帘下降至距楼板面1.8m处",{"key":337,"text":499,"correct":32},"防火分区内两只独立的感烟探测器报警后，用于防火分区分隔的防火卷帘直接下降至楼板面","ADE",{"id":502,"libraryId":5,"type":324,"typeLabel":325,"stem":503,"options":504,"answer":485,"analysis":33},935165,"(2016年真题)消防设施检查机构的人员对建筑物内安装的火灾自动报警系统进行检查时，对引入火灾报警及联动控制器的电缆和导线进行检查，下列检查结果中，符合现行国家消防技术标准要求的有（??）。",[505,507,509,511,513],{"key":20,"text":506,"correct":32},"端子板的每个接线端，接线最多为2根",{"key":24,"text":508,"correct":32},"24V供电的控制线路采用电压等级为300V\u002F500V的铜芯导线",{"key":27,"text":510,"correct":22},"接地导线采用截面积16mm2铝芯导线",{"key":30,"text":512,"correct":32},"每根电缆芯和导线留有200mm的余量",{"key":337,"text":514,"correct":22},"传输总线采用解决为0.5mm2的阻燃双绞线",{"id":516,"libraryId":5,"type":324,"typeLabel":325,"stem":517,"options":518,"answer":444,"analysis":33},935166,"(2016年真题) 根据《火灾自动报警系统施工及验收规范》GB 50166要求，下列关于火灾自动报警系统周期性维护保养的说法中，正确的是（??）。",[519,521,523,525,527],{"key":20,"text":520,"correct":22},"点型感烟火灾探测器投入运行3年后，应每隔2年至少全部清洗一遍",{"key":24,"text":522,"correct":32},"每年应用专用检测仪器对所安装的全部探测器试验至少1次",{"key":27,"text":524,"correct":32},"每年应用专用检测仪器对所安装的全部手动报警装置试验至少1次",{"key":30,"text":526,"correct":32},"每年应对全部防火卷帘的试验至少1次",{"key":337,"text":528,"correct":32},"每年应对全部电动防火门的试验至少1次",{"id":530,"libraryId":5,"type":324,"typeLabel":325,"stem":531,"options":532,"answer":543,"analysis":33},935167,"(2016年真题)在对建筑由火灾自动报警系统联动启动的雨淋喷水灭火系统进行检测时，应检测雨淋阀组联动控制功能，根据现行国家消防技术标准的规定，下列关于开启雨淋阀组的联动触发信号的说法中，正确的有（??）。",[533,535,537,539,541],{"key":20,"text":534,"correct":32},"同一报警区域内两只及以上独立的感温火灾探测器的报警信号",{"key":24,"text":536,"correct":22},"同一报警区域内两只及以上独立的感烟火灾探测器的报警信号",{"key":27,"text":538,"correct":22},"同一报警区域内一只感烟火灾探测器与一只手动火灾报警按钮的报警信号",{"key":30,"text":540,"correct":22},"同一报警区域内一只感烟火灾探测器与一只感温火灾探测器的报警信号",{"key":337,"text":542,"correct":32},"同一报警区域内一只感温火灾探测器与一只手动火灾报警按钮的报警信号","AE",{"id":545,"libraryId":5,"type":15,"typeLabel":16,"stem":546,"options":547,"answer":24,"analysis":33},935168,"(2017年真题)某消防设施检测机构对建筑内火灾自动报警系统进行检测时，对手动火灾报警按钮进行检查。 根据现行国家消防技术标准， 关于手动火灾报警按钮安装的说法中， 正确的是（??）",[548,550,552,554],{"key":20,"text":549,"correct":22},"墙上手动火灾报警按钮的底边距离楼面高度应为1.5m",{"key":24,"text":551,"correct":32},"手动火灾报警按钮的连接导线的余量不应小于150mm",{"key":27,"text":553,"correct":22},"墙上手动火灾报警按钮的底边距离楼面高度应为1.7m",{"key":30,"text":555,"correct":22},"手动火灾报警按钮的连接导线的余量不应大于100mm",{"id":557,"libraryId":5,"type":15,"typeLabel":16,"stem":558,"options":559,"answer":30,"analysis":33},935169,"(2017年真题)消防设施检测机构对某单位的火灾报警系统进行验收前的检测，根据现行国家标准《火灾自动报警系统施工及 验收规范》GB50166，该单位的下列做法中， 错误的是（??）",[560,562,564,566],{"key":20,"text":561,"correct":22},"对消防电梯进行2次报警联动控制功能检验",{"key":24,"text":563,"correct":22},"对自动喷水系统给水泵在消防控制室内进行3次远程启泵操作试验",{"key":27,"text":565,"correct":22},"对防排烟风机进行4次报警联动启动试验",{"key":30,"text":567,"correct":32},"对各类消防用电设备主、 备用电源的自行转换装置进行1次 转换试验",{"id":569,"libraryId":5,"type":15,"typeLabel":16,"stem":570,"options":571,"answer":27,"analysis":33},935170,"(2017年真题)消防设施检测机构的人员对某建筑内火灾自动报警系统进行检测时， 对在宽度小于3m的内走道顶棚上的点型感烟探测器进行检查。下列检测结果中，符合现行国家消防技术标准要求的是（）",[572,574,576,578],{"key":20,"text":573,"correct":22},"探测器的安装间距为16m",{"key":24,"text":575,"correct":22},"探测器至端墙的距离为8m",{"key":27,"text":577,"correct":32},"探测器的安装间距为14m",{"key":30,"text":579,"correct":22},"探测器至端墙的距离为10m",{"id":581,"libraryId":5,"type":324,"typeLabel":325,"stem":582,"options":583,"answer":594,"analysis":33},935171,"(2017年真题)某公共建筑火灾自动报警系统的控制器进行功能检查。 下列检查结果中， 符合现行国家消防技术标准要求的有（??）",[584,586,588,590,592],{"key":20,"text":585,"correct":22},"控制器与探测器之间的连线短路， 控制器在120s时发出的故障信号",{"key":24,"text":587,"correct":22},"在故障状态下，使一非故障部位的探测器发出火灾报警信号，控制器在70s时发出火灾报警信号",{"key":27,"text":589,"correct":32},"控制器与探测器之间的连线短路， 控制器在 50s 时发出故障信号",{"key":30,"text":591,"correct":32},"在故障状态下，使一非故障部位的探测器发出火灾报警信号，控制器在50s时发出火灾报警信号",{"key":337,"text":593,"correct":32},"控制器与备用电源之间的连线短路， 控制器在90s时发出故障信号","CDE",{"id":596,"libraryId":5,"type":324,"typeLabel":325,"stem":597,"options":598,"answer":609,"analysis":33},935172,"(2018年真题)某大厦地下车库共设置两樘防火卷帘，对其进行联动检查试验时，使两个独立的感烟探测器动作后，一樘防火卷帘直接下降到楼地面，另一樘防火卷帘未动作，但联动控制器显示控制该防火卷帘的模块已经动作。防火卷帘未动作的原因可能有( )。",[599,601,603,605,607],{"key":20,"text":600,"correct":22},"防火卷帘手动按钮盒上的按钮损坏",{"key":24,"text":602,"correct":32},"防火卷帘控制器未接通电源",{"key":27,"text":604,"correct":32},"防火卷帘控制器中的控制继电器损坏",{"key":30,"text":606,"correct":22},"联动控制防火卷帘的逻辑关系错误",{"key":337,"text":608,"correct":32},"联动模块至防火卷帘控制器之间线路断路","BCE",{"id":611,"libraryId":5,"type":15,"typeLabel":16,"stem":612,"options":613,"answer":27,"analysis":33},935173,"(2018年真题)某消防技术服务机构对办公楼內的火灾自动报警系统进行维护保养。在检查火灾报警控制器的信息显示与查询功能时，发现位于会议室的1只感烟探测器岀现故障报警信号。感烟探测器岀现故障报警信号，可排除的原因是()。",[614,616,618,620],{"key":20,"text":615,"correct":22},"感烟探测器与底座接触不良",{"key":24,"text":617,"correct":22},"感烟探测器本身老化损坏",{"key":27,"text":619,"correct":32},"感烟探测器底座与吊顶脱离",{"key":30,"text":621,"correct":22},"感烟探测底座一个接线端子松脱",{"id":623,"libraryId":5,"type":15,"typeLabel":16,"stem":624,"options":625,"answer":20,"analysis":33},935174,"(2018年真题)消防工程施工单位对某体育场安装的火灾自动报警系统进行检测。下列调试方法中，不符合现行国家标准《火灾自动报警系统施工及验收规范》（GB50166）的是（ ）",[626,628,630,632],{"key":20,"text":627,"correct":32},"使任一总线回路上多只火灾探测器同时处于火灾报警状态，检查控制器的火警优先功能",{"key":24,"text":629,"correct":22},"断开火灾报警控制器与任一探测之间的连线，检查控制器的故障报警功能",{"key":27,"text":631,"correct":22},"向任一感烟探测器发烟，检查点型感烟探测器的报警功能，火灾报警控制器的火灾报警功能",{"key":30,"text":633,"correct":22},"使总线隔离器保护范围内的任一点短路，检查总线隔离器的隔离保护功能",{"id":635,"libraryId":5,"type":15,"typeLabel":16,"stem":636,"options":637,"answer":27,"analysis":33},935175,"(2016年真题) 某建筑物内火灾自动报警系统施工结束后，调试人员对通过管路采样的吸气式火灾探测器进行调试。下列调试方式和结果中，不符合现行国家消防标准要求的是（??）",[638,640,642,644],{"key":20,"text":639,"correct":22},"在其中一根采样管最末端（最不利处）采样孔加入试验烟，控制器在120s内发出火灾报警信号",{"key":24,"text":641,"correct":22},"断开其中一根探测器的采样管路，控制器在100s内发出故障信号",{"key":27,"text":643,"correct":32},"断开其中一根探测器的采样管路，控制器在120s内发出故障信号",{"key":30,"text":645,"correct":22},"在其中一根采样管最末端（最不利处）采样孔加入试验烟，控制器在100s内发出火灾报警信号",{"id":647,"libraryId":5,"type":15,"typeLabel":16,"stem":648,"options":649,"answer":27,"analysis":33},935176,"(2016年真题) 对剩余电流式电气火灾监控系统进行检查时，应主要检查剩余电流式探测器安装情况。检查发现的下来做法中，正确的是（??）",[650,652,654,656],{"key":20,"text":651,"correct":22},"将相线和PE线穿过剩余电流式探测器",{"key":24,"text":653,"correct":22},"将PE线和中性线穿过剩余电流式探测器",{"key":27,"text":655,"correct":32},"将相线和中性线穿过剩余电流式探测器",{"key":30,"text":657,"correct":22},"将相线、中性线和PE线穿过剩余电流式探测器",[659,662,665,668,671,674],{"id":15,"name":660,"category":7,"favorite":661},"领导干部任职前廉政法规知识测试题",92,{"id":663,"name":664,"category":7,"favorite":15},595,"建筑结构与设备",{"id":666,"name":667,"category":7,"favorite":15},715,"招标采购专业知识与法律法规",{"id":669,"name":670,"category":7,"favorite":15},848,"市政方向-通用基础",{"id":672,"name":673,"category":7,"favorite":8},534,"BIM工程师",{"id":675,"name":673,"category":7,"favorite":8},535]