[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937660":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},937660,605,1,"单选题","对报警阀组进行年度检测时各类报警阀组（装置）要求中不正确的是。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","湿式报警阀组检查时，开启末端试水装置必须在3min内，消防水泵自动启动",true,{"key":16,"text":17,"correct":18},"B","干式报警阀组检查时，开启末端试水装置出水1min后，出水压力≥0.05MPa",false,{"key":20,"text":21,"correct":18},"C","预作用报警装置检查时，开启末端试水装置，火灾报警控制器确认火灾2min后，其出水压力≥0.05MPa",{"key":23,"text":24,"correct":18},"D","检查消防控制设备准确显示电磁阀、电动阀、水流指示器以及消防水泵动作信号，反馈信号准确","2020新教材P217 湿式报警阀组（1）检测内容及要求。湿式报警阀组功能按照下列要求进行检测：1.开启末端试水装置，出水压力不低于0.05MPa，水流指示器、湿式报警阀、压力开关动作。2.报警阀动作后，测量水力警铃声强，不得低于70dB。3.开启末端试水装置5min内，消防水泵自动启动。4.消防控制设备准确接收并显示水流指示器、压力开关及消防水泵的反馈信号。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]