[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937659":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},937659,605,1,"单选题","下列关于干式报警阀组的安装及质量检测要求，说法正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","安装完成后，向报警阀气室注入高度为100~150mm的清水",false,{"key":16,"text":17,"correct":14},"B","充气连接管道的直径不得小于20mm，并应安装止回阀、截止阀",{"key":19,"text":20,"correct":14},"C","安全排气阀安装在空压机上，超压时及时排气，保证系统安全",{"key":22,"text":23,"correct":24},"D","加速器安装在靠近报警阀的位置，加速器能加速开启报警阀，排气充水灭火",true,"2020新教材P199 D正确；A选项应为“高度为50~100mm的清水”；B选项应为“充气连接管道的直径不得小于15mm”；C选项的安全排气阀座安装在气源与报警阀组之间的管路上，并靠近报警阀组一侧。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]