[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937640":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937640,605,1,"单选题","某3层商业建筑，采用湿式自动喷水灭火系统保护，共设计有2800个喷头保护吊顶下方空间。该建筑自动喷水灭火系统报警阀组的设置数量不应少于（ ）个。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","2",false,{"key":16,"text":17,"correct":14},"B","3",{"key":19,"text":20,"correct":21},"C","4",true,{"key":23,"text":24,"correct":14},"D","5","“一个报警阀组控制的喷头数应符合下列规定：1湿式系统、预作用系统不宜超过800只”，2800÷800=3.5，取整为4。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]