[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937639":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937639,605,1,"单选题","干式系统，预作用系统均对配水管道的充水时间有限制要求，规定充水时间的目的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","迅速充水更有利于排气",false,{"key":16,"text":17,"correct":14},"B","充水时间的规定可以防止系统误喷",{"key":19,"text":20,"correct":21},"C","充水时间的规定主要是要求系统启动后立即喷水",true,{"key":23,"text":24,"correct":14},"D","充水越快，水头损失越小","《喷规》8.0.9条文解释：对干式、预作用及雨淋系统报警阀出口后配水管道的充水时间提出了新的要求：干式系统不宜超适1min，预作用和雨淋系统不宜超过2min。其目的，是为了达到系统启动后立即喷水的要求。选项A，迅速充水更有利于排气，不正确。选项B，充水时间的规定可以防止系统误喷，不正确。选项C，充水时间的规定主要是要求系统启动立即喷水，正确。选项D，充水越快，水头损失越小，不正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]