[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937638":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937638,605,2,"多选题","下列关于消火栓系统维护管理的说法，不正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","每年应监测市政给水管网的压力和供水能力",true,{"key":16,"text":17,"correct":18},"B","每月应对高位消防水箱的水位等进行一次检测",false,{"key":20,"text":21,"correct":18},"C","每日应对柴油机消防水泵的启动电池的电量进行检测",{"key":23,"text":24,"correct":14},"D","每天应对消防储水设施进行室内温度和水温检测",{"key":26,"text":27,"correct":18},"E","每季度应对消火栓进行一次漏水检查，发现有不正常的消火栓应及时更换","AD","2020新教材P172 每季度应监测市政给水管网的压力和供水能力，A选项错误；根据14.0.3-4，每月应对消防水池、高位消防水池、高位消防水箱等消防水源设施的水位等进行一次检测，B选项正确；根据14.0.4-4，每日应对柴油机消防水泵的启动电池的电量进行检测，每周应检查储油箱的储油量，每月应手动启动柴油机消防水泵运行一次，C选项正确；根据14.0.3-5，在冬季每天应对消防储水设施进行室内温度和水温检测，当结冰或室内温度低于5℃时，应采取确保不结冰和室温不低于5℃的措施，D选项错误；根据14.0.7，每季度应对消火栓进行一次外观和漏水检查，发现有不正常的消火栓应及时更换，E选项正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]