[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937626":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},937626,605,1,"单选题","下列关于消防水带压力试验的说法，不正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","截取1.2m长的消防水带做试验",false,{"key":16,"text":17,"correct":14},"B","加压至试验压力，保压5min",{"key":19,"text":20,"correct":21},"C","爆破压力应不小于消防水带试验压力的3倍",true,{"key":23,"text":24,"correct":14},"D","常用8型消防水带的试验压力为1.2MPa，爆破压力不小于2.4MPa","2020新教材P180 试验时将1.20m长的试样一端与水源相接，另一端用带有排气阀的密封装置封闭。保持试样平直，使试样灌满水并排尽其中的空气，关闭排气阀。以5.0MPa\u002Fmin～10.0MPa\u002Fmin的速率升压至表3规定的试验压力，保压5min，试样不应有渗漏现象。然后以该速率升压至试样爆破，判断是否符合表3的规定，AB选项正确；根据表3，常用8型消防水带的设计工作压力为0.8MPa，试验压力为1.2MPa，最小爆破压力为2.4MPa,C选项爆破压力应不小于消防水带设计工作压力的3倍，C选项错误，D选项正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]