[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937619":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},937619,605,1,"单选题","消防水带安装前的压力试验：截取（ ）长的水带，使用手动试压泵或电动试压泵平稳加压至试验压力，保压（ ）。检查是否有渗漏现象，有渗漏则不合格。在试验压力状态下，继续加压，升压至试样爆破，其爆破时压力应不小于水带工作压力的（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1.2m，5min，3倍",true,{"key":16,"text":17,"correct":18},"B","1.0m，3min，1.5倍",false,{"key":20,"text":21,"correct":18},"C","1.5m，10min，1.1倍",{"key":23,"text":24,"correct":18},"D","1.2m，3min，3倍","2020新教材P180 “截取1.2m长的水带，使用手动试压泵或电动试压泵平稳加压至试验压力，保压5min，检查是否有渗漏现象，有渗漏则不合格。在试验压力状态下，继续加压，升压至试样爆破，其爆破时压力应不小于水带工作压力的3倍”，故A正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]