[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937604":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},937604,605,1,"单选题","下列关于消火栓系统部件的进场检验数量及产品性能要求说法，不正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","旋转型消火栓其内部构造应合理，转动部件应为铜或不锈钢",false,{"key":16,"text":17,"correct":18},"B","消火栓固定接口性能检查数量从每批中抽查1%，但不应少于10个",true,{"key":20,"text":21,"correct":14},"C","外观检查应按安装总数全数检查",{"key":23,"text":24,"correct":14},"D","消火栓铸铁阀体外部应涂红色油漆，内表面应涂防锈漆，手轮应涂黑色油漆","2020新教材P192 旋转型消火检其内部构造应合理，转动部件应为铜或不锈钢，A选项正确；根据12.2.3-14，性能检查数量：消火栓固定接口应进行密封性能试验，应以无渗漏、无损伤为合格。试验数量宜从每批中抽查1%，但不应少于5个，B选项错误；根据12.2.3-18，外观和一般检查数量应全数检查，C选项正确；根据12.2.3-7，铸铁阀体外部应涂红色油漆，内表面应涂防锈漆，手轮应涂黑色油漆，D选项正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]