[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937579":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937579,605,2,"多选题","下列关于消防给水系统试压调试的做法，错误的有（ ）。",[11,15,18,21,25],{"key":12,"text":13,"correct":14},"A","在环境温度为4℃的情况下进行水压试验",true,{"key":16,"text":17,"correct":14},"B","水压严密性试验在水压强度试验和管网冲洗合格前进行",{"key":19,"text":20,"correct":14},"C","水压强度试验的测试点应设在系统管网的最高点",{"key":22,"text":23,"correct":24},"D","气压严密性试验的介质采用空气",false,{"key":26,"text":27,"correct":24},"E","消防给水系统的水源干管、进户管和室内埋地管道在回填前与系统同时进行水压强度试验和水压严密性试验","ABC","2020新教材P170 水压试验时环境温度不宜低于5℃，当低于5℃时，水压试验应采取防冻措施，A选项错误；根据12.4.4，水压严密性试验应在水压强度试验和管网冲洗合格后进行。试验压力应为系统工作压力，稳压24h，应无泄漏，B选项错误；根据12.4.3，水压强度试验的测试点应设在系统管网的最低点，C选项错误；根据12.4.7气压严密性试验的介质宜采用空气或氮气，D选项正确；根据12.4.6消防给水系统的水源干管、进户管和室内埋地管道应在回填前单独或与系统同时进行水压强度试验和水压严密性试验，E选项正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]