[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937578":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937578,605,2,"多选题","下列关于消防给水系统减压阀安装要求的说法，正确的有（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","减压阀前后应安装压力表",true,{"key":16,"text":17,"correct":14},"B","减压阀水流方向应与供水管网水流方向一致",{"key":19,"text":20,"correct":21},"C","减压阀安装应在供水管网试压后、冲洗前进行",false,{"key":23,"text":24,"correct":14},"D","减压阀前应有过滤器",{"key":26,"text":27,"correct":14},"E","减压阀处应有压力试验用排水设施","ABDE","2020新教材P154 消防给水系统减压阀的安装应符合下列要求： 1）安装位置处的减压阀的型号、规格、压力、流量应符合设计要求 2）减压阀安装应在供水管网试压、冲洗合格后进行。 3）减压阀水流方向应与供水管网水流方向一致。 4）减压阀前应有过滤器。 5）减压阀前后应安装压力表。 6）减压阀处应有压力试验用排水设施。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]