[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937576":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937576,605,2,"多选题","某民用建筑的室内消防给水系统的管道采用镀锌钢管，消防水泵扬程为100m，水泵零流量时的压力为1.32MPa，下列关于该系统管网试压和冲洗的说法中，正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","当试压过程中出现渗漏时，应停止试压，放空介质后重新再试",false,{"key":16,"text":17,"correct":18},"B","水压强度试验的测试点应设在管网最低处",true,{"key":20,"text":21,"correct":18},"C","管网冲洗应在水压强度试验合格后分段进行",{"key":23,"text":24,"correct":18},"D","水压严密性试验应在水压强度试验和管网冲洗合格后进行",{"key":26,"text":27,"correct":14},"E","气压严密性试验的介质宜采用空气或氮气，试验压力应为0.28MPa，且稳压24h，压力降不应大于0.05MPa","BCD","2020新教材P170 系统试压过程中，当出现泄漏时，应停止试压，并应放空管网中的试验介质，消除缺陷后，应重新再试，A选项错误；根据12.4.3，水压强度试验的测试点应设在系统管网的最低点，B选项正确；根据12.4.1-4，管网冲洗应在试压合格后分段进行。冲洗顺序应先室外，后室内，先地下，后地上，室内部分的冲洗应按供水干管、水平管和立管的顺序进行，C选项正确；根据12.4.4，水压严密性试验应在水压强度试验和管网冲洗合格后进行，D选项正确；根据12.4.7，气压严密性试验的介质宜采用空气或氮气，试验压力应为0.28MPa，且稳压24h，压力降不应大于0.01MPa，E选项错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]