[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937575":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937575,605,2,"多选题","下列关于消防给水系统架空管道支吊架安装要求的说法，不正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","配水管宜在中点设一个防晃支架，当管径小于DN50时可不设",false,{"key":16,"text":17,"correct":18},"B","配水干管及配水管，配水支管的长度超过15m，每15m至少设1个防晃支架，当管径不大于DN50可不设",true,{"key":20,"text":21,"correct":14},"C","管径大于DN50的管道拐弯、三通及四通位置处应设1个防晃支架",{"key":23,"text":24,"correct":18},"D","架空管道每段管道设置的防晃支架不少于2个",{"key":26,"text":27,"correct":14},"E","当管道改变方向时应增设1个防晃支架","BD","2020新教材P169 架空管道的下列部位应设置固定支架或防晃支架： 1）配水管宜在中点设一个防晃支架，但当管径小于DN50时可不设。 2）配水干管及配水管，配水支管的长度超过15m，每15m长度内应至少设1个防晃支架，但当管径不大于DN40可不设。 3）管径大于DN50的管道拐弯、三通及四通位置处应设1个防晃支架。根据12.3.21，架空管道每段管道设置的防晃支架不应少于1个，当管道改变方向时，应增设防晃支架。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]