[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937572":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},937572,605,2,"多选题","稳压设备的检测验收要求为（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","稳压泵的型号性能等符合设计要求",true,{"key":16,"text":17,"correct":14},"B","稳压泵的控制符合设计要求，并有防止稳压泵频繁启动的技术措施",{"key":19,"text":20,"correct":21},"C","稳压泵在1h内的启停次数符合设计要求，不大于6次／h",false,{"key":23,"text":24,"correct":21},"D","火灾时稳压泵不需要工作，无需设置备用电源",{"key":26,"text":27,"correct":14},"E","稳压泵吸水管应设置明杆闸阀，稳压泵出水管应设置消声止回阀和明杆闸阀","ABE","2020新教材P161 选项A、B、E正确：选项C错误，稳压泵在1h内的启停次数不大于15次／h，而不是6次／h；选项D错误，发生火灾时管网压力降低，首先启动的是稳压泵，故需要设置备用电源。验收要求为：稳压泵供电应正常，自动手动启停应正常：关掉主电源，主、备电源能正常切换。",{"id":6,"name":31,"category":32,"favorite":33},"消防技术综合能力(一级、二级)","建筑工程",0]