[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937550":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},937550,605,1,"单选题","下列给水管网支吊架的安装不符合规范规定的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","架空管道支架、吊架、防晃（固定）支架的安装固定牢固",false,{"key":16,"text":17,"correct":18},"B","配水支管每15m长度内设一个防晃支架，当管径不大于DN50mm时不设",true,{"key":20,"text":21,"correct":14},"C","设计的吊架在管道的每一支撑点处能承受5倍于充满水的管重",{"key":23,"text":24,"correct":14},"D","当管道穿梁安装时，穿梁处做一个吊架","2020新教材P168 （6）下列部位应设置固定支架或防晃支架:1）配水管宜在中点设1个防晃支架，但当管径小于DN50mrn时可不设。 2）配水干管及配水管，配水支管的长度超过15m，每15m长度内应至少设1个防晃支架，但当管径不大于DN40mm时可不设。 3）管径大于DN50mm的管道拐弯、三通及四通位置处应设1个防晃支架。 4）防晃支架的强度，应满足管道、配件及管内水的重量再加50%的水平方向推力时不损坏或不产生永久变形。当管道穿梁安装时，管道再用紧固件固定于混凝土结构上，可作为l个防晃支架处理。 （7）架空管道每段管道设置的防晃支架应不少于1个;当管道改变方向时，应增设防晃支架;立管应在其始端和终端设防晃支架或采用管卡固定。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]