[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-937527":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},937527,605,1,"单选题","下列关于消防水泵接合器安装要求的说法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","不应安装在玻璃幕墙下方",true,{"key":16,"text":17,"correct":18},"B","墙壁消防水泵接合器的安装应符合设计要求，设计无要求时，其安装高度距地面宜为1.1m",false,{"key":20,"text":21,"correct":18},"C","安装在墙壁上的水泵接合器与墙面上的门、窗、孔、洞的净距离不应大于2.0m",{"key":23,"text":24,"correct":18},"D","地下消防水泵接合器的安装，应使进水口与井盖底面的距离不大于0.4m，且不应小于井盖的直径","2020新教材P161 消防水泵接合器的安装应符合下列规定： 1）墙壁消防水泵接合器的安装应符合设计要求。设计无要求时，其安装高度距地面宜为0.7m；与墙面上的门、窗、孔、洞的净距离不应小于2.0m，黑钻押题，金考典软件考前更新，下载链接 www.jinkaodian.com 且不应安装在玻璃幕墙下方。 2）地下消防水泵接合器的安装，应使进水口与井盖底面的距离不大于0.4m，且不应小于井盖的半径。",{"id":6,"name":27,"category":28,"favorite":29},"消防技术综合能力(一级、二级)","建筑工程",0]